DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Similar documents
SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

A. Submit manufacturer's literature and technical data before starting work.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Design Standard. Purpose: Design Standard:

SECTION PANELBOARDS

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

University of Houston Master Construction Specifications Insert Project Name

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SECTION MOTOR CONTROLLERS

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Medium Voltage Metal-Enclosed Switches

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

University of Houston Master Construction Specifications Insert Project Name

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

SECTION MOTOR CONTROLLERS

7. SERVICES OVER 600 VOLTS

Medium Voltage Metal-Enclosed Switches

Three-Phase Pole Mounted Recloser

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller

C1000 Series Automatic Cap Bank

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Quik-Spec Coordination Panelboard Specifications

SECTION DISTRIBUTION AND GROUNDING

GE 8000-Line Motor Control Centers

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

OTEC Transfer switch open transition

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

BGE STRATEGIC CUSTOMER ENGINEERING

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

Introduction. Features. Intelligent Technologies Motor Control Center Structures

Chapter 6 Generator-Voltage System

A. This section includes unit capacitors for power factor correction.

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Critical Power Switchboards. Selection and Application Guide

www. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

SWITCHGEAR DIVISION PRODUCT PROFILES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

Switchgear. Low Voltage

Electrical Switchgear Replacement Montgomery County Community College

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

WARREN COUNTY, N.Y. M/E REFERENCE

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

MEDIUM-VOLTAGE SWITCHGEAR

BUSWAY Low Voltage (Pow-R-Flex)

MEDIUM VOLTAGE SWITCHGEAR SECTION

SECTION MOTOR CONTROL

Generator Fire Safety: Generator assemblies should be located outside the building.

Low Voltage Switchgear

POWERCON CORPORATION

Power Break II Switchboard

SECTION ELECTRIC DISTRIBUTION

Transfer switch OTEC and OTECSE open transition

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

AIR COOLED RECTIFIER SPECIFICATION S-50-A

10 Commercial, Industrial, Agricultural Services

COMMERCIAL QUICK REFERENCE

Transfer switch OTEC open or delayed transition

Quick Start Guide TS 910 & TS 920

AMENDMENT ELECTRIC SERVICE MANUAL 2014

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

33KV INDOOR SWITCHGEAR

Underground Distribution Switchgear

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi

Medium Voltage. ANSI C37.20 and NEMA SG-5

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Transcription:

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation only. 1.1.2. Institute of Engineering and Electronic Engineers (IEEE): 1.1.2.1. C37.13-08 Low-voltage AC Power Circuit Breakers Used in Enclosures 1.1.2.2. C37.20.1-07 Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear 1.1.2.3. C57.13-08 Instrument Transformers 1.1.2.4. C62.41.1-03 Surge Environment in Low-voltage (1000V and less) AC Power Circuits 1.1.2.5. C62.45-92 Surge Testing for Equipment connected to Low-Voltage AC Power Circuits 1.2. National Electrical Manufacturers Association (NEMA): 1.2.1. C37.51-10 Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies Conformance Test Procedures 1.2.2. National Fire Protection Association (NFPA): 1.2.2.1. 70-11 National Electrical Code (NEC). 1.2.3. Underwriters Laboratories, Inc. (UL): 1.2.3.1. 891-05 Switchboards 1.2.3.2. 977-07 Safety Fused Power-Circuit Devices 1.2.3.3. 1053-99 Ground Fault Sensing and Relaying Equipment 1.2.3.4. 1558-99 Metal-Enclosed Low-Voltage Power Circuit 1.3. FACTORY TESTS 1.3.1. Switchgear shall be thoroughly tested at the factory, with the circuit breakers in the connected position in their compartments. Tests shall be in accordance with IEEE C37.20.1 and NEMA C37.51. Factory tests shall be certified, and shall include the following tests: 1.3.1.1. Design tests. 1.3.1.2. Production tests. 1.3.1.3. Conformance tests. 1.3.2. The following additional tests shall be performed: 1.3.2.1. Verify that circuit breaker sizes and types correspond to drawings, and the Overcurrent Protective Device Coordination Study. 1.3.2.2. Verify tightness of bolted electrical connections by calibrated torque-wrench method in accordance with manufacturer s published data.

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 2 of 5 1.3.2.3. Confirm correct operation and sequencing of key-type mechanical interlock systems for multiple circuit breakers by attempting closure on locked-open devices, and attempting to open locked-closed devices, and making key exchange with devices operated in offnormal positions. 1.3.2.4. Verify correct barrier and shutter installation and operation. 1.3.2.5. Exercise all active components. 1.3.2.6. Inspect indicating devices for correct operation. 1.3.2.7. Perform an insulation-resistance test, phase to ground, on each bus section, with phases not under test grounded, in accordance with manufacturer s published data. 1.3.2.8. Perform insulation-resistance tests on control wiring with respect to ground. Applied potential shall be 500 V DC for 300-volt rated cable and 1000 V DC for 600-volt rated cable, or as required if solid-state components or control devices cannot tolerate the applied voltage. 1.3.2.9. Perform phasing checks on double-ended or dual-source switchgear to insure correct bus phasing from each source. 1.4. GENERAL 1.4.1. Switchgear shall be a complete, grounded, continuous-duty, integral assembly, metal clad, dead-front, dead-rear, self-supporting, indoor type switchgear assembly, tamperproof, weatherproof, outdoor type switchgear assembly with metal housing and a walk-in protected aisle, as warranted by the local conditions of the project. 1.4.2. Incorporate devices shown on the drawings and all related components required to fulfill operational and functional requirements. 1.4.3. Switchgear shall be, depending on the local conditions of the project: 1.4.3.1. Type 1 front accessible 1.4.3.2. Type 2 front, side, and rear accessible. 1.4.4. Short circuit ratings shall not be less than 1200 ka. 1.4.5. Switchgear shall be assembled, connected, and wired at the factory so that only external circuit connections are required at the construction site. Split the structure only as required for shipping and installation. Packaging shall provide adequate protection against rough handling during shipment. 1.4.6. All non-current-carrying parts shall be grounded. 1.5. HOUSING 1.5.1. Frames and enclosures: 1.5.1.1. The assembly shall be braced with reinforcing gussets using bolted connections to assure rectangular rigidity.

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 3 of 5 1.5.1.2. The enclosure shall be steel, leveled, and not less than the gauge required by applicable publications. 1.5.1.3. Die-pierce the holes for connecting adjacent structures to insure proper alignment, and to allow for future additions. 1.5.1.4. All bolts, nuts, and washers shall be cadmium-plated steel. 1.5.2. Circuit breaker compartments: 1.5.2.1. An individual compartment shall be supplied for each circuit breaker and each future circuit breaker as shown on the drawings. Compartments shall be provided with isolated wireways for control wiring between devices. 1.5.2.2. Separate each compartment so that the circuit breaker, buses, and cable terminations are in separate compartments with steel partitions or barriers of approved and properly installed insulation. 1.5.2.3. Each compartment furnished with a circuit breaker (active or spare) shall be fully equipped as noted on drawings and specified below. 1.5.2.4. Each compartment noted as space for future circuit breaker, as shown on drawings, shall be fully equipped for positioning and connecting the breaker. Provide all equipment required to implement the future breaker installation. 1.5.3. Auxiliary compartments: 1.5.3.1. Compartments shall be provided for auxiliaries, metering, and transition or termination sections as required by the manufacturer, and as shown on drawings. Compartments shall be provided with isolated wireways for control wiring between devices. 1.5.4. Compartment doors: 1.5.4.1. The doors shall permit convenient removal and interchanging of circuit breakers between compartments. The doors shall be capable of a swing approaching 180 degrees. 1.5.4.2. Concealed or semi-concealed hinges shall be provided to attach the doors. Weld the hinges to the equipment structure and to the compartment doors. 1.5.4.3. Receptacles: Provide one 2P, 3W, 20-amp heavy-duty duplex ground fault current interrupter (GFI) receptacle for each three compartments or fraction thereof. Space receptacles equidistant along the interior wall of the aisle space. Install a separate 20- amp circuit for every three (3) receptacles. 1.5.4.4. All branch circuit wiring shall be installed in conduit and shall be not less than No. 12 AWG. 1.5.5. Finish: 1.5.5.1. All metal surfaces shall be thoroughly cleaned, phosphatized and factory primed prior to applying baked enamel or lacquer finish. 1.5.5.2. Provide a light gray finish for indoor switchgear.

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 4 of 5 1.6. BUSES 1.6.1. Bus Bars and Interconnections: 1.6.1.1. Provide copper phase and neutral buses, fully rated for the amperage as shown on the drawings for the entire length of the switchgear. Bus laminations shall have a minimum of 6 mm (1/4 inch) spacing. 1.6.1.2. Mount the buses on appropriately spaced insulators and brace to withstand the available short circuit currents. 1.6.1.3. The bus and bus compartment shall be designed so that the acceptable NEMA standard temperature rises are not exceeded. 1.6.1.4. Install a copper ground bus the full length of the switchgear assembly. 1.6.1.5. Main Bonding Jumper: An un-insulated copper bus, size as shown on drawings, shall interconnect the neutral and ground buses, when the switchgear is used to establish the system common ground point. 1.6.1.6. All bolts, nuts, and washers shall be cadmium-plated steel. Bolts shall be torqued to the values recommended by the manufacturer. 1.7. LOW-VOLTAGE POWER CIRCUIT BREAKERS 1.7.1. General: Circuit breakers shall be dead front, drawout, stored energy type with solid state trip devices. Arcing contacts shall be renewable. 1.7.2. Rating: Circuit breakers shall be 3 pole, 600 volts AC and below, 60 cycle with frame size, trip rating and functions, and system voltage as shown on drawings. Breakers shall have 30 cycle short time current ratings. 1.7.3. Drawout Mounting: Provide a racking mechanism to position and hold the breaker in the connected, test, or disconnected position. Provide an interlock to prevent movement of the breaker into or out of the connected position unless the breaker is tripped open. 1.7.4. Trip Devices: Breakers shall be electrically and mechanically trip free and shall have trip devices in each pole. Unless otherwise indicated on drawings, each breaker shall have overcurrent and short-circuit, and integral ground fault trip devices. Trip devices shall be of the solid state type with adjustable pick-up settings, with both long time and short time elements, and integral trip unit testing provisions. Devices shall have time-delay band adjustment. Long-time delay element shall have inverse time characteristics. Main circuit breakers shall not have instantaneous trip function. 1.7.5. Position Indicator: Provide a mechanical indicator visible from the front of the unit to indicate whether the breaker is open or closed. 1.7.6. Trip Button: Equip each breaker with a mechanical trip button accessible from the front of the door. 1.7.7. Padlocking: Provisions shall be included for padlocking the breaker in the open position.

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 5 of 5 1.7.8. Operation: breakers 1600 ampere frame size and less shall be manually operated. Breakers larger than 1600 ampere frame size shall be electrically operated, complete with visual verification (indicator lights). Breakers shall have digital read out capability complete with network connectivity. 1.7.9. Interlocks shall be provided that will prevent disconnecting the breaker from the bus stabs or inserting the breaker into the bus stabs unless the breaker is in the tripped (open) position. Interlocks shall be provided to only allow installation of the properly rated breakers in the appropriate rated cells. 1.7.10. Fused Circuit Breakers: The fuses used with combination fused breakers shall be highinterrupting capacity current-limiting type and coordinated with the circuit breaker. Fuses shall be on the line side of the breaker on a common drawout carriage (except 3000 and 4000 ampere breakers). Circuit breakers of 3000 and 4000 ampere frame size may have their fuses in a separate compartment with drawout mounting. A feature shall be included which trips the breaker when any fuse blows. An interlock shall prevent the reclosure of the breaker until the blown fuse is replaced. A blown fuse indicator shall be provided on the front of the breaker. In the case of fuses in a separate compartment, an interlock shall be provided to require the breaker to be open before it is possible to open the fuse compartment door. 1.8. CONTROL WIRING 1.8.1. Switchgear control wires shall not be less than No. 14 AWG copper 600 V rated. Install wiring complete at the factory, adequately bundled and protected. Provide separate control circuit fuses in each breaker compartment and locate for ease of access and maintenance. 1.9. NAMEPLATES AND MIMIC BUS 1.9.1. Nameplates: For Normal Power system, provide laminated black phenolic resin with white core with 12 mm (1/2 inch) engraved lettered nameplates next to each circuit breaker. For Essential Electrical System, provide laminated red phenolic resin with white core with 12 mm (1/2 inch) engraved lettered nameplates next to each circuit breaker. Nameplates shall indicate equipment served, spaces, or spares in accordance with one line diagram shown on drawings. Nameplates shall be mounted with plated screws on front of breakers or on equipment enclosure next to breakers. Mounting nameplates only with adhesive is not acceptable. 1.9.2. Mimic Bus: Provide an approved mimic bus on front of each switchgear assembly. Color shall be black for the Normal Power system and red for the Essential Electrical System, either factory-painted plastic or metal strips. Plastic tape shall not be used. Use symbols similar to one line diagram shown on drawings. Plastic or metal strips shall be mounted with plated screws.