Installation Sheet January, 2016 Supersedes June 2013

Similar documents
Installation Sheet January, 2016 Supersedes February, 2013

Lighting and Heating Control Electrically Held Lighting Contactors

OTEC Transfer switch open transition

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

SIGNAL WORDS QUALIFIED PERSON

contactor may be required to interrupt up to 200% current. The N.O. contacts are equipped with permanent magnet blowouts to meet this requirement.

Instruction sheet WARNING. October, 2014

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

A. Submit manufacturer's literature and technical data before starting work.

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

CR193 Vacuum Limitamp* Contactors

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Power Break Circuit Breakers

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

High Frequency SineWave Guardian TM

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

User s Manual. Automatic Switch-Mode Battery Charger

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Horizontal Circuit Switchers

CHAPTER IX ELECTRICAL

Transfer switch OTEC open or delayed transition

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

QSSE, QSSEX INDUSTRIAL Battery Chargers

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

PROCESS ELECTRONICS CORPORATION

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

OBAE, OBAEXU, ON BOARD Battery Chargers

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

XENON POWER SUPPLY 4000 Watt Gladiator IV

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

Control Relays Overview

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

Transfer switch OTEC and OTECSE open transition

Horizontal Circuit Switchers

Lighting and Heating Control

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

CIRCLE SEAL CONTROLS

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

NEMA Contactors & Starters (Freedom)

ST Charger. Industrial Battery Charger

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

Electric Motor Controls BOMA Pre-Quiz

Design Standard. Purpose: Design Standard:

Installation Instructions For Motor Control Center (MCC) Units

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

CALTRAP INSTALLATION AND OPERATIONS MANUAL

Typical Specification

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

CIRCLE SEAL CONTROLS

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

OBE, OBEXU, ON BOARD Battery Chargers

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

MERCURY CONTACTORS & RELAYS

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY CLOSED, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY CLOSED, P/N SERIES

COM Overcurrent Relay

Florham Park, NJ USA Call (ASCO) for sales or service

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

Florham Park, NJ USA Call (ASCO) for sales or service

Instructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

QPET, QPETXU Battery Chargers

Catalog Number Identification with Elements Explained

MAGNETIC MOTOR STARTERS

Instructions for Replacing

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

MINE CHARGER INSTALLATION AND OPERATION MANUAL MODEL NUMBERS: MSP MSQ MSR MSS

E.S.P. Embedded Sensing Probes for Motor Brushes

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A39 UNIVERSAL SCR CHARGER

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

GP/GPA GROUND FAULT PROTECTION

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

XENON POWER SUPPLY Compact Model 220 Volt Equipment Type

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

Transcription:

s Installation Sheet January, 016 Supersedes June 01 E87010-A0105-T00-A6-CLM0 Lighting and Heating Contactor 60, 100, 00 Amp,, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting and heating contactors can control tungsten, fluorescent and metal vapor lamp or heating loads. (Table 1 below shows the voltage and current rating for various loads). Each contactor and its associated load should be protected against short circuits by a suitable branch circuit protective device selected in accordance with the National Electric Code (NEC). Table 1 Contactor Catalog Number CLM0D... CLM0E... CLM0F... Cont. Current, Amp. 60 100 00 Tungsten Max. Volts, line-line 480 480 480 Max. Volts, line-neutral 77 77 77 Ballast Max. Volts, line-line 600 600 600 Max. Volts, line-neutral 46 46 46 Heating Max. Volts, line-line 600 600 600 Max. Volts, line-neutral 46 46 46 Table 1 - This industrial type contactor is designed to be installed, operated, and maintained by adequately trained personnel. These instructions do not cover all the variations of all of the topics covered herein. Contact your local sales office if you have questions regarding the product. Theory of Operation Each contactor contains a permanent magnet built into its structure that will maintain the contactor in its energized state indefinitely without using control power. When energized, DC voltage is applied to produce a magnetic field that reinforces the polarity of the permanent magnet and the contactor closes. Immediately, the current to the coil is disconnected by the coil clearing auxiliary contact. In order to open the contactor, it is necessary to create a field through the coil in the reverse direction to the permanent magnet. This momentarily cancels the magnetic attraction and the contactor drops out. Each CLM contactor has an electronic control module CLMKCMR which is used to energize and close the contactor and for the release circuit. It is designed for short time actuation of 1- cycles only. All coils are designed with a small wattage resistor in addition to a diode at coil voltages higher than 10 volts. Remote solid state switching devices have off state leakage currents. They may also pass utility transient voltages through to the device electronics. The low level off state voltages are insufficient to actuate the contactor but large enough to burn out the resistors. Normal actuating voltages are quickly disconnected from the coils and control module by the latch clearing contacts. Coil and module failures are possible when used with solid state relays and PLC outputs. 4-volt systems are ok to use, but 10 volts and above should be discouraged. If higher voltages cannot be avoided, an interposing relay should be used. Care should be taken when servicing that leads do not become changed from their factory installed terminals, or improper operation and possibly permanent damage to the contactor could result. CAUTI - Device sensitive to current polarity. Risk of damage to this device. Do not apply voltage directly to the coil terminals of this device! The permanent magnet will be demagnetized and the rectifier will be damaged if alternating current or wrong polarity direct current is applied directly to the coil. CAUTI - High inrush. Can cause damage to this device. Avoid attempting to manually latch or delatch the contactor.

CAUTI - Coil must be wired correctly. Risk of damage to this device. All control wiring for contactor operation must only be made to the coil isolationcontact terminals # & # and terminal connection points. Wiring made to any other terminal points will burn out the coil and diode. If a coil burnout occurs, both the coil and diode must be replaced. Installation The nameplate ratings of the contactor must agree with the power supply and the rating of the load. Contactor mounting should be solid to prevent vibration. When the contactor is provided with a channel iron base, grout the base in place. The preferred and recommended mounting position of the contactor is in a vertical plane. Before making any connections, be certain that all leads to be handled are de-energized. power off, operate contactors, relays and interlocks to see that they work freely. See that all terminals and current carrying connections are clean and tight. Power Circuit Terminals Terminals are marked as suitable for either copper or aluminum conductors. Range of Conductor Sizes Contactor 60A 100A 00 A CU/AL Terminals #14-4 AWG #6-1/0 AWG #4-00 AWG (Wire with conductors rated 75 0 C. If conductors rated higher than 75 0 C are used, their size must be based on torque ampacity values for 75 0 C conductors.).terminals torque values are shown in Table. 7 9 1 11 4 6 5 6 1 Fig. 1 60 Ampere, CLM0F10 Contactor (Exploded View for clarity) 8 10 1 45 50 Table - Recommended Driving Torque Location (Qty.) Driving Torque Figure 1 (lb.-in.) Item 60 Ampere Contactors Cover Screw () 8-9 6 Coil Wire Connector () 8-9 1 Stationary Contact Screw (/pole) 18-0 10 Main Power Connector (/pole) - 1 100 and 00 Ampere Contactors Cover Screw () 18-0 6 Coil Wire Connector () 8-9 1 Stationary Contact Screw (/pole) 18-0 10 Main Power Connector (/pole) 90-100 1 (100 Amp.) Main Power Connector (/pole) 75-00 1 (00 Amp.) Table - Fuse Block Kits To meet NEC requirements concerning common control fusing, the following fuse kit catalog numbers are available for protection of the control circuit conductors. Cat. No. Description KCCF1 For one pole fuse holder KCCF1 For two pole fuse holder Order Fuse Separately by Ampere Control Conductor Size Suggested Fuse Size * ** #16 AWG 10 AMP #14 AWG 15 AMP * Buss Fuse KTK or equivalent ** When using a control transformer, select fuse size based on NEC code

Black White Momentary Maintained CLM CTTOR CTROL VOLTAGE L1 Contact Inspection refer to Figure 1 Loosen the two arc chute screws (6) located immediately above and below the nameplate and remove the arc chute (7). The contacts (8) are visible. Re-tighten the screws per Table. Contact Wear and Replacement refer to Figure 1, Table. CAUTI: Install arcbox prior to energization Contacts are designed for a long service life based on a specific electrical load under normal service and environmental conditions. If any one of these factors is altered, a shorter service life or a breakdown will result. Contactors are subject to both mechanical and electrical wear during their operation. In most cases mechanical wear is insignificant. The erosion of the contacts is due to electrical wear. During arcing, material from each contact is vaporized and blown away from the useful contacting surface. Note: When contact replacement is required, it is necessary to replace both stationary and moving contacts plus moving contact overtravel springs. After replacement, manually operate switch to be sure binding does not occur. Fig. CLMFCAK11 Connection Diagram for Separate Control. (Magnetically-latched contactors are equipped with coils designed for intermittent duty only. Faulty coil action can be caused by a defective coil or damaged control module. Replacement of both is recommended when the contactor will not pull in or drop out. Coil replacement for the purpose of changing the control voltage rating does not require auxiliary contact or control module replacement.) Coil Replacement refer to Figure 1, Table. Loosen the two screws at each side of the upper base and remove the wire connections. Loosen the assembly screws (1). Pull the loosened upper base structure () forward. Unplug the coil () from the upper base, plug in a new coil and replace the upper base structure while depressing the kick-out springs (4) to ensure they set in the molded seats in the crossbar (5). Reconnect the four coil leads. Tighten the assembly screws referring to Table. Mechanically operate the unit to ensure there is no binding of the crossbar. After removing the arc chute (7) and with replacement contacts in hand, compress the overtravel spring (9) and remove the moving contact (8) from the crossbar (5). Remove any power connections. Remove screws (10) and lift out the stationary contact carriers (11). The new contacts are then installed by reversing the above procedure and referencing Table for torque specifications. Moving contacts should be free to move, overtravel spring seated, and the crossbar free to move when the arc chute is in position. Silver cadmium oxide contact buttons require NO dressing or lubrication during their life. Magnet - Armature Assembly Self alignment and permanent air gap features of the magnet armature make replacement unnecessary. Mating pole face surfaces should be kept clean. Short Circuit s This lighting contactor is suitable for use on a circuit capable of delivering not more than the current (rms symmetrical amperes) shown in circuits rated not more than the voltage shown in tables 6, 7, and 8 on the following pages. Table 4 - Coil Data Coil Data Contactor 60A 60A 100A 100A Model L Coil Data - Typical Values Poles -4 4-5 - 4-5 - 4-5 Inrush VA 410 600 900 100 900 100 Dropout VA 40 40 00 10 00 10

1 Momentary L1 Control Voltage Maintained Remote Device L1 Lead 'A' (Not Provided) L CLM CTTOR Black White T1 T T CLMFCAK11 CLM CTTOR Black White CLMFCAK11 Fig. Connection for Common Control Fig. 4 Connection for Wire Separate Control CTROL VOLTAGE (L1) 1 () X Table 5 - Renewal Parts H O A SELECTOR SWITCH REMOTE DEVICE CLM CTTOR BLK RED WHITE RED RED Fig. 5 Connection for Hand/Off/Auto Control

Fig. 6 Dimension Drawing 60, 100 and 00 Amp Device CAUTI - Coil must be wired correctly. Risk of damage to the device. All control wiring for contactor operation must only be made to the coil isolation contact terminals #, # and terminal connection points. Wiring made to any other terminal points will burn out the coil and diode. If a coil burnout occurs, both the coil and the diode must be replaced. Storage Electrical control equipment which is to be stored prior to its installation, should be checked before placing in storage for possible damage during transit. It should then be repacked and stored in a location which is clean and dry. When storage is in or near buildings under construction, provide covers to protect the equipment against dust, moisture and falling objects. Apparatus stored for long periods may corrode. Damage, while stored, will be minimized by maintaining the best possible storage conditions, and by periodically inspecting the equipment and arresting the progress of corrosion and other forms of deterioration which may be found. A small amount of heat will stop corrosion that occurs from moisture due to condensation. Table 6 - Operating Coils for 60 Ampere Contactors Voltage V Freq. Hz Part Number -4 Pole 4-5 Pole 4 60 Hz CLMDC04 CLMD5C04 110/10 50/60 Hz CLMDC10 CLMD5C10 08 60 Hz CLMDC08 CLMD5C08 0/40 50/60 Hz CLMDC40 CLMD5C40 77 60 Hz CLMDC77 CLMD5C77 440/480 50/60 Hz CLMDC480 CLMD5C480 550/600 50/60 Hz CLMDC600 CLMD5C600 Table 7 - Operating Coils for 100 and 00 Ampere Contactors Voltage V Freq. Hz Part Number -4 Pole 4-5 Pole 4 60 Hz CLMEC04 CLME5C04 110/10 50/60 Hz CLMEC10 CLME5C10 08 60 Hz CLMEC08 CLME5C08 0/40 50/60 Hz CLMEC40 CLME5C40 77 60 Hz CLMEC77 CLME5C77 440/480 50/60 Hz CLMEC480 CLME5C480 550/600 50/60 Hz CLMEC600 CLME5C600

Model L Replacement Coils Order by part number, voltage and frequency Troubleshooting Problem Cause Corrective Action Table 8-100 Ampere Contactor Short Circuit Protective Device (SCPD) Class H Fuse Class J Fuse Class R Fuse Class T Fuse Type CB 1 Max. SCPD Current Voltage 5,000A 150A Circuit Breaker Interrupting 5,000A Short-Circuit 5,000A Contacts Contacts Chatter Welding Low Voltage Abnormal Inrush Current Insufficient Contact Pressure Low Voltage Preventing Magnet from Sealing Foreign Matter Preventing Contacts from Closing Check supply voltage, especially during starting. Check coil voltage rating. Increase voltage or change coil rating as required. Check for grounds, shorts, or excessive load current. Replace contacts and springs, check contacts for abnormal wear or damage. Check supply voltage to coil, especially for momentary dip during startup. Clean contacts with LPS CFC-Free Electro Contact Cleaner. Contacts used at low current and voltage should be cleaned with Freon. Type CLB 150A 150,000A Short Circuit Remove fault and check to be sure fuse or breaker size is correct. Excessive Inrush Current Use next larger size contactor. Table 9-00 Ampere Contactor Short Circuit Protective Device (SCPD) Class H Fuse Class J Fuse Class R Fuse Class T Fuse Type CB 1 Type CB+CL Type CLB Max. SCPD 1 Inverse-Time Circuit Breaker Current Voltage 10,000A 50A 50A 50A Circuit Breaker Interrupting 5,000A 00,000A 150,000A Short-Circuit 5,000A Short Contact Life or Overheating Coils Filing or Dressing Interrupting Excessively High Currents Weak Contact Pressure Foreign Matter on Contact Surface Short Circuit or Ground Fault Loose Connection in Power Circuit DO NOT FILE SILVER CTTS. Rough spots or discoloration will not harm contacts of impair their efficiency. Check for grounds, shorts or excessive currents. Use larger size contactor. Replace contacts and springs, check contacts for abnormal wear or damage. Clean contacts with LPS CFC-Free Electro Contact Cleaner. Take steps to reduce entry of foreign matter into enclosure. Remove fault and check to be sure fuse or breaker size is correct. Clean and tighten. Caution - All control wiring for contactor operation must only be made to the coil isolation contact terminals # and #, and terminal connection points. Wiring made to any other terminals will burn out the coil and diode. If a coil burnout occurs, both the coil and diode must be replaced. Inverse Time with Built-In Current-Limiting Fuses Inverse Time Current-Limiting Breaker Open Circuit Mechanical Damage Replace with new coil. Handle and store new coils carefully. Table 10 - Contact s Auxiliary Contact s (A600, R00) Voltage Continuous Make Break 10-600 V 10A 700VA 70VA 7-10 V 10A 60A 70VA 8-7 V 10A 60A 10A 8-00 VDC 1A 8VA 8VA These instructions do not purport to cover all details or variations in equipment nor to provide for possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should problems arise which are not covered sufficiently for the purchaser s purpose, the matter should be referred to the local SIemens Industry, Inc., Sales Office. Overheated Coil Magnetic and Magnetic and Mechanical Parts Mechanical Parts Failure to Pick-up and Seal Incorrect Coil Low Voltage Wrong Coil or Wrong Connection Mechanical Obstruction Coil Open or Overheated Check coil rating and replace with correct coil. Each CLM contactor has an electronic control module CLMKCMR which is used to energize and close the contactor and for the release circuit. It is designed for short time actuation of 1- cycles only. All coils are designed with a small wattage resistor in addition to a diode at coil voltage higher than 10 Volts. Remote solid state switching devices have off state leakage currents. They may also pass utility transient voltages through to the device electronics. The low level off state voltages are insufficient to actuate the contactor but large enough to burn out the resistors. Normal actuating voltages are quickly disconnected from the coils and control module by the latch clearing contacts. Coil and module failures are possible when used with solid state relays and PLC outputs. 4-Volt systems are ok to use, but 10 volts and above should be discouraged. If higher voltages cannot be avoided, an interposing relay should be used. Check system voltage and voltage dips during starting. Check coil marking and wiring. With power off, check for movement of armature and contacts. Replace. The contents of this instruction sheet shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Industry, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Industry, Inc. Any statements contained herein do not create new warranties or modify the existing warranty. Failure to Drop-Out Sticky Substance on Pole Faces Release Coil not Energized Worn or Rusted Parts Causing Binding Contacts Welded Clean pole faces with LPS CFC-Free Electro Contact Cleaner. Check coil, coil circuit or length of leads from supply voltage to coil. Coil may be open or lead length is excessive. Replace unit. See Welding under Contacts.