Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

Similar documents
ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Pretest Module 29 High Voltage Unit 1

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

SF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1

Extensible Unit - VCE2a

NEW Solutions for Underground System Growth

Arc-Flash Mitigation Technologies. Dennis Balickie

University of Houston Master Construction Specifications Insert Project Name

www. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

Chapter 6 Generator-Voltage System

Power systems Protection course

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Transformer Protection

Solar Power Switchgear & Energy Storage Renewable Energy Systems

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

SWITCHGEAR DIVISION PRODUCT PROFILES

Medium Voltage Metal-Enclosed Switches

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

MAGNETIC MOTOR STARTERS

Switchgear and Distribution Systems for Engineers and Technicians

BGE STRATEGIC CUSTOMER ENGINEERING

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Integrated Power Solutions

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

MEDIUM VOLTAGE AIS ANSI SWITCHGEAR Advance and Advance 27. Non-arc-resistant MV ANSI switchgear

A. Submit manufacturer's literature and technical data before starting work.

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Motor Protection. Voltage Unbalance & Single-Phasing

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Advance 27 ANSI 27 kv switchgear

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Installation and Construction Notes for EVSE4

NEXT STEP B) SAFETY :

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Cobra-S. Catalog Cobra-S

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

Medium Voltage Metal-Enclosed Switches

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)

7. SERVICES OVER 600 VOLTS

SECTION PANELBOARDS

The safest, most reliable Switchgear in the market today

Horizontal Circuit Switchers

PROTECTION OF THE BRANCH CIRCUIT

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Wind Power Solutions. Make Energy Renewable and Reliable!

Close-Open (Short-Circuit) Time Results Interpretation

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

MEDIUM VOLTAGE PRODUCTS

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

CLIENT: PROJECT: PO#: ESTIMATOR:

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

Transmission & Distribution Glossary of Electrical Terms

Basics of Medium Voltage Motor Control Starter Power Components & Starter Types

SECTION MOTOR CONTROL

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Service Entrance Methods

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

OTEC Transfer switch open transition

COOPER POWER CA280012EN

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Horizontal Circuit Switchers

TIME REQUIREMENT GUIDE (TRG)

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI

SafeGear TM Motor Control Center Arc resistant metal-clad construction

www. ElectricalPartManuals. com outdoor oillnaken type GC aingle tank descrlpllve bullella page l 14.4 lev 100,380 and BOO mva 23 lev 280 mva

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Shippensburg University

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

When power interruptions happen.

Zone Selective Interlock Module. For GE Circuit Breakers

Solid Dielectric, Single Phase Reclosers

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ELECTRICAL HAZARD EXAMPLES

Transcription:

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals Mike Schmaderer

Questions Feel free to interrupt There are no dumb questions

Just what exactly is Switchgear?

The term switchgear, used in association with the electric power system, or grid, refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.

Substation vs Switchgear Substation Easier to maintain Easier to modify Lower arc flash incident energy Switchgear (Substation in a box) Smaller footprint Better at keeping animals out Build off sight Out of weather (maybe)

Open Switchgear

Traditional Switchgear Breakers all in the bottom May require a ramp

Enclosure Side View

Two High Construction Takes up less space Lift is required for breakers in top row

Combination Lift is required

Typical One Line

Switchgear One Line

Laid Out to Minimize Load on the Bus

Laid Out to Meter Generation

Laid Out to Facilitate Maintenance

Laid Out to Facilitate Maintenance

Fused Switches

Outdoor Metal Clad Switchgear

Arc Resistant Designed to vent energy from an arc safely away from operators Extra support Costs about 30% more

Arc Reduction Techniques Bus Differential Protection Instantaneous Tripping With blocking Arc Relaying Strategically placed fiber Combined with overcurrent Remote Switching

Things to Consider Before Ordering Gear Number of Feeders Generators Tie(s) and Bus Tie Bus Ampacity Entrance Top Entrance Bottom Entrance Throat Connected Bastard

Things to Consider Before Ordering Gear CTs PTs For Relaying For Metering Location For Metering For Relaying For Synchronizing Location

Things to Consider Before Ordering Gear Breaker Arrangement Single high Two high Location of feeders, generators, tie Continuous Current Rating of the Breaker Interrupting Capability of the breaker Must be able to interrupt max fault current Arc Flash

Insulation Porcelain (glass) Glastic Indoor only Polymer Skirts

Breaker -Interrupters How does the Breaker extinguish the arc? Air Blast Under Oil SF6 Vacuum

Torqueing Requirements

Torque τ = torque σ y = yielding stress of material D = bolt diameter c = coefficient of friction Yield Strength (Mpa) Aluminum 241 Steel 248 Brass 200

Torque US Recommended Bolt Torque Recommended Torque Size Grade 2 Grade 5 Grade 8 18-8 S/S Bronze Brass Coarse Fine Coarse Fine Coarse Fine Coarse Fine Coarse Fine Coarse Fine #4* - - - - - - 5.2-4.8-4.3 - #6* - - - - - - 9.6-8.9-7.9 - #8* - - - - - - 19.8-18.4-16.2 - #10* - - - - - - 22.8 31.7 21.2 29.3 18.6 25.9 1/4 4 4.7 6.3 7.3 9 10 6.3 7.8 5.7 7.3 5.1 6.4 5/16 8 9 13 14 18 20 11 11.8 10.3 10.9 8.9 9.7 3/8 15 17 23 26 33 37 20 22 18 20 16 18 7/16 24 27 37 41 52 58 31 33 29 31 26 27 1/2 37 41 57 64 80 90 43 45 40 42 35 37 9/16 53 59 82 91 115 129 57 63 53 58 47 51 5/8 73 83 112 128 159 180 93 104 86 96 76 85 3/4 125 138 200 223 282 315 128 124 104 102 118 115 7/8 129 144 322 355 454 501 194 193 178 178 159 158 1 188 210 483 541 682 764 287 289 265 240 235 212

Torque Torque Values = inch-lbs Bolt Size 18-8 Stainless Steel Brass Aluminum 2024-T4 316 Stainless Steel Nylon 2-56 2.5 2.0 1.4 2.6 0.44 4-40 5.2 4.3 2.9 5.5 1.19 4-48 6.6 5.4 3.6 6.9 6-32 9.6 7.9 5.3 10.1 2.14 6-40 12.1 9.9 6.6 12.7 8-32 19.8 16.2 10.8 20.7 4.30 8-36 22.0 18.0 12.0 23.0 10-24 22.8 18.6 13.8 23.8 6.61 10-32 31.7 25.9 19.2 33.1 8.20 1/4" - 20 75.2 61.5 45.6 78.8 16.00 1/4" - 28 94.0 77.0 57.0 99.0 20.80 5/16" - 18 132.0 107.0 80.0 138.0 34.90 5/16" - 24 142.0 116.0 86.0 147.0 3/8" - 16 236.0 192.0 143.0 247.0 3-8" - 24 259.0 212.0 157.0 271.0 7/16" - 14 376.0 317.0 228.0 393.0 7/16" - 20 400.0 357.0 242.0 418.0 1/2" - 13 517.0 422.0 313.0 542.0 1/2" - 20 541.0 443.0 328.0 565.0 9/16" - 12 682.0 558.0 413.0 713.0 9/16" - 18 752.0 615.0 456.0 787.0 5/8" - 11 1110.0 907.0 715.0 1160.0 5/8" - 18 1244.0 1016.0 798.0 1301.0 3/4" - 10 1530.0 1249.0 980.0 1582.0 3/4" - 16 1490.0 1220.0 958.0 1558.0 7/8" - 9 2328.0 1905.0 1495.0 2430.0 7/8" - 14 2318.0 1895.0 1490.0 2420.0 1" - 8 3440.0 2815.0 2205.0 3595.0 1"- 14 3110.0 2545.0 1995.0 3250.0

Maintenance Cleaning Relay Testing Breakers Ductor High potential Function Testing

Switchgear Maintenance When is the last time that the bus and bus supports were cleaned Are the heaters working Do they get turned off Dirt and Moisture Most are hard to get out of service Even with generation Ethanol Plant Example

Switchgear Maintenance Moving parts seldom operate Switching load Clearing faults Generator breakers operate more often Breakers/Switches Battery Relays

Functional Trip Testing Electrical mechanical relays Spin the disk Microprocessor based relays Force a trip Inject current Through test switches Inject primary current Through the CT s

Breakers Heaters Year round Trip/Close coils Rewind motors Exercise the breaker Lubricate the Mechanism

Relays Monitor current and voltage Overcurrent Directional overcurrent Voltage Impedance Etc.

Relays Relays should be tested periodically Suggest generator and tie relays every three years Suggest feeder relays every five to six years Function of the value of the asset they are protecting Test should include a functional test of the breaker

Types of Relays Ice cube Interposing Lockout Electromechanical Solid state (Static) Microprocessor-based (Digital/Numerical)

DC/Battery System Stored Energy Battery Charger Trip coils Close coils Rewind Motors?

Battery Check it once a month Turn off AC breaker for one hour Monitor voltage drop Compare to previous months Don t let the voltage drop more than 10% DC rewind motors

Common Switchgear and Substation Issues

Mechanism gummed up Caused by dirt and inactivity Will not trip Common during the winter Especially in outdoor breakers Often causes a blown fuse or a trip coil to burn up

Rewind motor will not stop winding Broken or misaligned gear Often causes motor to burn up Pull motor rewind fuses

Rewind motor winds up, unwinds, and rewinds continuously Latch does not catch Caused by dirt and grim Common during the winter Especially in outdoor breakers Often causes motor to burn up Pull motor rewind fuses and lubricate latch

Breaker will not close after a trip Blown fuse in close circuit Burnt up close coil Lockout relay not reset Sync switch not turned on

Broken Pole or linkage One or more phases not making contact Current imbalance Voltage imbalance Hard on generators

Check voltage and current often Voltage Use voltmeter to check all three phases Use sync scope to check sync PT Current Use ammeter to check current on all three phases Multifunction meters Microprocessor based relays

Other things to consider Record faults Phase Time Weather conditions Interrupting rating Fault study Arc Flash

Once again, if you are not 100% sure, get help

Questions?