Close-Open (Short-Circuit) Time Results Interpretation

Similar documents
Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

Pretest Module 29 High Voltage Unit 1

Miniature circuit breaker Application guide

Extracting Valuable Information from HV Circuit Breaker Testing. Charles Sweetser - OMICRON MIPSYCON 2014

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Air-insulated switchgear UniGear type ZS1

KD LV Motor Protection Relay

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Power systems Protection course

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Selective Coordination

Arc flash hazard mitigation

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Components for EEx e Panels

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Circuit breaker interlocking and operation requirements SIEMENS

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

The X, Y, and Z of Circuit Breaker Control

ABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems. Generator Circuit- Breaker Systems

MAGNETIC MOTOR STARTERS

Live Tank Circuit Breakers Buyer s Guide

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Design Standards NEMA

HD4. Gas insulated MV circuit-breakers kv A ka

XM1 - Motor protection relay

Ultra Fast Earthing Switch UFES retrofit Overview

GE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work

Contactors type AF1350-AF1650

Pretest Module 29 High Voltage

Pankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers. Technical Seminar: PLN

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Miniature Circuit Breaker

Medium voltage products. Fuses

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

FUSE TECHNOLOGY Ambient temperature

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Exercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers

Exercise 4-1. Friction Brakes EXERCISE OBJECTIVE DISCUSSION. Understand the construction and operation of friction brakes.

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

GENERATOR & SINGLE-FUNCTION PROTECTION

Tmax Molded Case Circuit Breakers

Electromagnetic Industries LLP

POB series Coil Tester & Power Supply Units

SF 6 Gas Insulated Load Break Switch

Advance 27 ANSI 27 kv switchgear

CB to 1000 A. 1 to 4 single pin main poles with silver pad contacts.

Horizontal Circuit Switchers

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Dynamic Resistance Measurement for Circuit Breakers Applying high DC current

SECTION MOTOR CONTROL

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

Horizontal Circuit Switchers

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Copyright 2003 Advanced Power Technologies, Inc.

POB series Coil Tester & Power Supply Units

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

4-Day Power System Analysis, Coordination, System Studies

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Vacuum Generator Circuit Breaker - A trend-setting power plant technology

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

CI-TI Contactors - VLT Frequency Converters

SF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Publication No.: PSG

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

NRBM Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute

Dual Power. Protection. Protection

MINIATURE CIRCUIT BREAKER

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

Brief Operating Description: Longer Motor Life Starts with a Switch

OHB Outdoor sulphur Hexafluoride circuit-breaker

Outdoor vacuum breaker for railway applications - FSK II

Electrical network protection VIP30, VIP35. User s manual 12/2008

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

1492-CB 1492-GH 1492-GS

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

Functions provided by measuring relays in railway equipment

CP Automatic capacitor bank

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

A Revolution in Circuit Breaker Operating Mechanism Technology

Controls. THERMAL OVERLOAD RELAYS RW..D (up to 40A)

Medium voltage products. Fuses

TECHNICAL DESCRIPTION

UniSafe 36 Product Presentation. ABB Elektrik Sanayi A.S. - Page 1

Live Tank Circuit Breakers kV Reliability through Technical Excellence

High-voltage high-breaking capacity VV fuse-links

Transcription:

Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection relay system detects the short circuit and trips the breaker. In the test event the timing device can be programmed to start a trip command as soon as the contacts close. This gives the fastest short-circuit time (C-O time) operation the breaker is capable of doing. Most HV circuit breaker mechanisms are characterized as being trip-free. Performing trip-free operation simply requires the circuit breaker to be able to open without any delay once the auxiliary switch (contact), that controls the application of the electric signal to the operating coils, closes. Under these conditions the main contacts of the circuit breaker are allowed to touch instantly. This means the trip-free characteristic requires the circuit breaker to open at any instant that a trip command is issued to the unit, even if the circuit breaker is in the process of closing. To achieve this, the mechanism, interrupters and drive system must be able to withstand the forces of the sudden change of direction. In other cases a circuit breaker must close before it opens. For example, suppose a breaker is being closed manually by operating the contact closing mechanism or remotely. While the contacts are in the process of closing suppose a fault occurs in the system with the relay closing the trip circuit of the breaker. The trip-free mechanism allows the circuit breaker to be tripped by the relay even if the contacts are in the process of closing. The major international standards for circuit breakers are IEC and ANSI /IEEE. One section of IEC 62271-100 High-voltage alternating current circuit-breakers standard describes the circuit-breaker-related time definitions. C-O (Close-open) time definition according to IEC is: Interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation. This standard also states: Unless otherwise stated, it is assumed the opening release incorporated in the circuit breaker is energized at the instant when the contacts touch in the first pole during closing. This represents the minimum close-open time. 1

Close-open (measured during test) should be distinguished from the make-break time (measured when a CB is under load), as illustrated in the Figure 1. According to the IEC standard make-break time is: Interval of time between the initiation of current flow in the first pole during a closing operation and the end of the arcing time during the subsequent opening operation (Figure 1). NOTE: The make-break time may vary due to the variation of the pre-arcing time. Figure 1. C-O (Trip free) operation C-O time (also called dwell time) is the amount of time the breaker is in the closed position during a close-open operation. C-O time value is compared to the manufacturer's specifications. For the puffer SF6 circuit breakers, too short CO time (during trip-free operation) compared to specification can cause longer arcing time or in the worst case a failure to break a short-circuit during subsequent opening. It is because too short C-O time could mean CB didn't get time to close enough (during closing in the trip-free operation) to provide compression volume large enough to produce the blast of SF6 gas to extinguish the arc. Longer C-O time means longer short-circuit time during the potential fault. Due to high electric current, there may be high thermal stress in the insulation and conducting parts of CB. As the thermal stress in the circuit breaker is proportional to the period of short circuit, the breaking capacity of a circuit breaker depends upon the operating time that is C-O time. When checking the C-O time of the breaker during timing tests, the auxiliary switch (contact) adjustment should be checked. The auxiliary switches are adjustable for most HV circuit breaker operating mechanisms. These switches are adjusted at the factory to set 2

close-open time and close open travel during a trip-free or C-O operation of the breaker according to manufacturer s specifications. In case C-O time value is out of range, the auxiliary switches can be adjusted to bring the C-O time within tolerance. C-O timing results in the DV-Win software The contacts close-open times for a circuit breaker with one break per phase are displayed in the Figure 2.In the graphic display C-O times are marked for each pole and for breaker separately. Also, as shown in the Figure 2. C-O time is calculated and displayed in the tab Numerical results for each phase and breaker separately. Figure 2. C-O operation graphical and numerical results (one break per phase) For a circuit breaker with two breaks per phase, graphical results for C-O operation are displayed in the Figure 3. In the graphic display C-O times are marked for each contact separately. Also, C-O time is calculated and displayed in the tab Numerical results for each contact, phase and breaker separately. 3

Note: For a circuit breaker with more than one break per phase, phase C-O time is calculated as interval of time between the instant when the last contact touched in the pole during closing and the instant when the first contact separated in the pole during subsequent O operation. Breaker C-O time is interval of time between the instant when the metallic continuity is established in the first pole during a closing operation and the instant when all poles have separated during the subsequent opening operation. Figure 3. C-O operation graphical and numerical results (two breaks per phase) As can be seen from the Figure 3, the C-O time in the phase A (14.6 ms) is much shorter than the C-O time of the other two phases (34 ms and 29.2 ms). Also, it is much shorter than minimum opening time (25 ms) for this CB. Since closing time of phase A is within tolerance (i.e. phase A is not slower at closing that could cause shorter C-O time) it indicates there is no problem with operating mechanism of the phase A but with auxiliary contact of type a adjustment. It tells the auxiliary contact a closes earlier than it should, causing the phase A to open faster at the next subsequent opening. 4