Auto Mains Failure AMF Controller AE03
Auto Mains Failure DESCRIPTION AMF Controller AE03 is an Automatic Mains Failure controller, which activates the generator during power failure & vice versa. The panel includes mc based controller. The operation is controlled automatically in Auto Mode as well as manually in the Manual Mode. Apart from the activating & deactivating, AMF03 can control the GENSET according to the engine side parameters like Water Temp., Lub oil pressure etc. And alternator side parameter like under voltage, over voltage, under frequency etc. Also it gives us various indications & power measurement. It s having LCD display & user friendly setting parameter. Software also provides inbuilt help menu. SPECIFICATIONS DC supply: 2V DC (Battery supply) Starter output: Signal for relay coil Fuel start/stop output: Signal for relay coil (In CCPL case controls ECU supply) Over all dimensions: (for controller) : 96mm x 96mm x 00mm Approx. weight or controller : 750 gms.
Auto Mains Failure FEATURES Microprocessor based design Automatic engine start and stop LCD Display with key pad Solid state fuel stop & crank outputs LED indication for few operations. OPERATION Auto mode: In this mode panel monitors the mains supply (3 phase or single phase). As the incoming mains supply either fail or drops below preset limit i.e. 80V (by default) the generator will be started and load will be transferred to genset, panel will indicate that load is transferred to genset with LED indication. When the AC mains supply returns within limit, the panel will wait for preset time & will transfer the load to mains (indication through LED). The engine will be instructed to stop after preset time. Manual mode: Manual mode is used to start & run the engine with start push button. And it can be stopped by pressing the stop push button. Off mode: Off mode is used to keep the Genset off condition in case of mains fail. Nor AMF controller will transfer the Load on DG. Night mode: Night mode is the special mode in which the Genset will be kept in Off Mode in the specific period of the day. This period is settable. Test mode: Test mode will be active in AUTO / MANUAL mode while mains present. To enter into test mode, press test key, and observe the indications on LCD display.
Auto Mains Failure Indication Remote start Charging fail Warning (any warning fault) Shut down fault (any) Mains present DG on Mains CB close DG CB close Indications on LCD display Battery voltage Alternator voltage (for three phases i.e.ph, PH2, PH3) Load current (for three phases i.e.ph, PH2, PH3) Alternator power in kw Alternator power in KVA Alternator KwH Alternator KVAH Power factor (pf) for three phases Alternator supply frequency
Auto Mains Failure Key switches F F2 PROG ESC Increment Decrement Enter Left Right ACK. Start Stop Sensor / switches required Lop switch Fuel level switch 25% Charge Fail Water in Fuel Remote Start Remote Stop Apart from this there will be 2 PF contacts that can be programmed as per our requirement. No need to have separate relay card. Every warning fault / shutdown fault will be displayed on the LCD display. Also we can program the parameters as per or requirement with the help of keys provided on the controller. This will b totally user friendly. No need to have separate energy meter, as controller displayed all the required readings.
Programmable Parameters No. Parameter Range Start delay 0-59sec Standard if not set 5 sec 2 Mains restore time -59 sec 5 sec 3 Mains under voltage 70-500V 90V 4 Mains Over voltage 70-500V 250V 5 Warm up time -59 sec 5 sec 6 Cool down time -59 sec 30 sec 7 Generator under voltage 70-500V 90V 8 Generator over voltage 70-500V 250V 9 CT ratio 0-000A 50:5 0 Generator over load Low frequency 0 - disable or value 0-99Hz 47Hz 2 High frequency 0-99Hz 53Hz 3 Generator fail Alarm 4 Crank Time -20sec 5 sec 5 Charge Fail Level 3-24 volts 8 volt 6 Rest time -59 sec 5 sec 7 Crank attempt -0 attempt 3 attempt 8 LLOP bypass time 0-59 sec 5sec 9 Stop Time 0-59 sec 0 sec
Programmable Parameters No. Parameter Range 20 Horn time 0-59 sec 2 Fuel type 22 Faults for programmable relay- pull to stop 2 pull to start -2 faults (table) 23 Faults for programmable relay-2-2 faults (table) 2 24 Faults for programmable relay-3-2 faults (table) 3 25 Faults for programmable relay-4-2 faults (table) 4 26 Single / three phase 27 Low fuel programmable 28 Alarm Time for shut down single phase three phase -Shut down fault 0 only LED indi. -59 sec 29 Alarm 2 Time for shut down -59 sec sec 30 Low Fuel Time for shut down 3-5 min 0 min 3 R.P.M. selection; Frequency = 50 Hz Remote signal Enable/ Disable for Single phase Continuous On time = 500 RPM 2 = 3000 RPM Disable Enable Min 32 33 Standard if not set 20 sec sec 0 480 min
List of Faults Fault no. Faults Start Fail 2 LLOP 3 Over speed 4 Low Battery 5 Charge fail 6 HWT 7 Low fuel 8 Over load 9 Alarm 0 Alarm 2 Fail to Stop 2 Generator voltage fail
TERMINAL DETAILS