Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2

Similar documents
Flowrite TM AP 599 Series 8-inch Pneumatic Valve Actuator

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

Flowrite AP 599 Series

Powers TM Controls RL 243 SW Switching Relay

VE VVG Series Electronic Two-way Valves Normally Closed

Powers Controls Powertop Two-Way Valves Normally Open

Flowrite 599 Series High Pressure Close-Off 2-Way Valves, 2-1/2 to 6-Inch, Flanged Iron Body, ANSI Classes 125 & 250

Powers TM Controls SW 141 Differential Static Airflow Switches

Powers Controls No. 6 Damper Actuators Tandem Mounting

Powers Controls 656 Powermite Valve with 3-inch Top Rebuilding

Flowrite EA 599 Series SQX Electronic Valve Actuator 24 Vac, 3-Position Control

Powermite 599 MT Series SQS Electronic Valve Actuator, 24 Vac, Floating Control (3-position)

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac 3-Position (Floating) Control

Powers TM Controls EA 338 Electronic Actuator

599 Series Zone Valve Bodies:

Powers Controls RL 147 Positioning Relay

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Proportional Control

Powers TM Controls VP 656 Powermite Three-way Mixing Valves (Flared Type)

Packing Replacement Kit for Flowrite VF 599 Series Valves

Flowrite EA 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

SED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options

POWERS TM CONTROLS SW 786 Selector Switch

POWERS TM CONTROLS LC Pneumatic Damper Actuator

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Floating Control

SED2 Variable Frequency Drives

Flowrite 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Laboratory Exhaust Air Terminal

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

Rebuild/Repack Kits for Flowrite VF 599 Series 2-1/2 to 6-inch Valves

Powers Controls No. 6 Pneumatic Damper Actuator

POWERS Controls No. 4 Pneumatic Damper Actuator

SAX Electronic Valve Actuator

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

599 Series 6-Way Ball Valves

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

Technical Instructions Document No EA GQD May 6, OpenAir GQD Series. Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators

Flowrite 599 Series. Technical Bulletin. 1/2 to 2-Inch Valve (2-Way & 3-Way) and Actuator Assembly Selection. Document No.

Powers Controls Maximum Thrust Ratings of Pneumatic Damper Actuators

SKD U Electronic Valve Actuator

Flowrite 599 Series Two-Way Valves, 1/2 to 2- inch Bronze Body, ANSI 250

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Pressure Independent Control Series

Powers Controls Powermite Two-Way Flared Valves Normally Open/Normally Closed

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Powers Controls TT 184 Temperature Transmitters

Powermite 599 MT Series Terminal Unit Valve and Actuator Assembly Selection

Powermite 599 MT Series Terminal Unit Valve and Actuator Assembly Selection

SAX Electronic Valve Actuator

POWERS Controls. Technical Instructions Document No P25 AP December 3, No. 6 Pneumatic Damper Actuator.

Pressure Independent Control Series

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

SKP Series SKP15 U.. Gas Valve Actuator with Safety Shutoff Function

Powers Controls No. 4 Pneumatic Damper Actuator

Flowrite 599 Series Two-Way Valves, 1/2 to 2- inch Bronze Body, ANSI 250

SAV Electronic Valve Actuator

599 Series Zone Valves

Powermite 599 Series MT Series Terminal Unit Three-way Valves

AV-8020 Series Floating Control Actuated Valve

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac Proportional Control

SKD U Electronic Valve Actuator

Flowrite VF 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

SKD62UA Series Electronic Valve Actuator, Advanced Features

Pressure Independent Control Series 2-Way Valves and Electronic Valve Actuators

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

599 Series Ball Valve and Actuator Assemblies Selection

599 Series Ball Valve and Actuator Assemblies Selection

VVP45 and VXP45 Series Two-port and Three-port Seat Valves ANSI Class 250 Short-stroke Valves

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

SED2-BT300-XX-C09 Migration Kits. Product Numbers

Powermite 599 Series MT Series Terminal Unit Two-way Valves

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

599 Series Zone Valve Bodies:

VOG Series VOG15.01xU1 Oil Safety Shut-off Valves with Proof of Closure (POC)

599 Series 2-Way Ball Valves

Accessories/Kits Ball Valve Bracket Kit (includes bracket, mounting screws, shaft and handle)

Distributed By: M&M Control Service, Inc Product Product Code Technical Instructions Page #

TEC Actuator Package. Product and Part Numbers. Product Description. Installation Instructions Document No October 27, 2010 CAUTION:

Auxiliary Equipment. Table of Contents. Auxiliary Equipment H-1. Product Product Code Technical Instructions Page #

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Ball Valve Bracket Kit

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE #

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

Laboratory Room Controller

Laboratory Room Single Duct Supply Air Terminal

Flowrite 599 Series Two-Way Valves 1/2 to 2-inch Bronze Body

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

599 Series 2-Way Ball Valves

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Differential pressure switch for monitoring air pressure in HVAC systems.

Transcription:

Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2 Document No. 155-078P25 VE 265-2 Description The VE 265 Electro-Pneumatic Valve is a general purpose, electrically operated, twoposition 3-way valve designed to control airflow. It can be used for interlock between an electrical system and a pneumatic control system. This compact, lightweight air valve has barbed, plastic tube connections marked: 1 - Normally closed 2 - Normally open 3 - Common Available types are Open Frame (yoke) and Junction Box (splice box). Features UL and CSA approved for general purpose Valve may be mounted in any position Mounting holes provided in the yoke Wide selection of AC voltages Product Numbers Table 1. Product Enclosure Type AC Voltage 60Hz 50Hz Product Number Junction Box 24 265-1001 Junction Box 120 110 265-1002 Junction Box 208 265-1003 Junction Box 240 220 265-1004 Junction Box 277 265-1005 Junction Box 480 440 265-1006 Open Frame 24 265-1007 Open Frame 120 110 265-1008

Three-way Electro-pneumatic (EP) Valve Model 2 Warning/Caution Notations WARNING: CAUTION: Personal injury/loss of life may occur if you do not perform a procedure as specified. Equipment damage, or loss of data may occur if you do not perform a procedure as specified. Specifications Application Material: Body Celcon plastic Internal Buna N, copper, Stainless Steel Ambient Temperature: Junction Box Type 0 F to 100 F (0 C to 38 C) Open Frame Type 0 F to 110 F (0 C to 43 C) Control Fluid Air Only Max. Air Pressure 30 psig (207 kpa) Airflow Capacity: Airflow 600 SCIM (164 ml/s) @ Inlet Pressure 20 psig (138 kpa) @ Differential Pressure 1 psig (7 kpa) Cv Flow Factor 0.06 in. 2 Electrical Ratings: Voltages 24 to 480 Vac Power consumption 5.7 Watts Current drain Inrush 17.3 VA Holding 9.2 VA Mounting bracket has: 1 oval and 1 open-ended hole; it is part of the yoke. Air Connections Barbed fittings for 1/4-inch (6.4 mm) OD plastic tubing Shipping Weight Open Frame Type 0.37 lb (0.17 kg) Junction Box Type 0.54 lb (0.24 kg) Dimensions See Figure 2 These valves are commonly used to alternately apply pressure to, and exhaust pressure from, pneumatically controlled devices (valves, damper actuators) by an electrical input energizing or de-energizing the solenoid of the valve. A standard method is shown in Figure 1. The input air is connected to Port 1 (normally closed), and the output is connected to Port 3 (common). When the solenoid is energized, Port 1 connects to Port 3 permitting the thermostat to control the damper actuator. When the solenoid is de-energized, Port 2 (normally open) is connected to Port 3 exhausting air from the actuator permitting it to return to its normal position. Other valves can be provided to meet specific OEM requirements. Contact National OEM Sales for information. Page 2

Three-way Electro-pneumatic (EP) Valve Model 2 Application, Continued Figure 1. Standard Application. Installation General These valves are designed for either wall mounting or panel mounting and may be mounted in any position. The coil and enclosure may be rotated 360 in relation to the body, if necessary. Make certain there is sufficient space around the valve for ease of future servicing. These valves require no adjustment or calibration. CAUTION: Be sure power is off during installation and servicing. NOTE: Media filtration although these valves have no sliding parts and are generally not sensitive to small amounts of foreign material, filtration of oil and dirt from air line is recommended. Dirt or foreign material in the media may cause excessive leakage, excessive wear or, in exceptional cases, malfunction. Lubrication is not required. Air Connections Electrical Connection Wall Mounting (Junction Box Type) Panel Mounting (Open Frame Type) Coil Housing Temperature All pneumatic piping connections are sized for 1/4-inch (6 mm) OD polyethylene tubing. The connections are sharp, barb-type connections. Electrical supply must conform to nameplate rating. Connect coil leads to electrical circuit using standard electrical practice. Wiring connections on the junction box models are made via splices inside the box. Knock-outs are provided in the box. Grounding screw is provided at rear of box. Wire leads provide a means of connection on the open frame models. Use standard wire nut connectors when making these connections (not included). If the valve is to be wall mounted, holes must be drilled for the mounting screws (not included). Drill holes for No. 8 screws. Either the mounting holes in the yoke or the knock-out mounting holes on the inside of the splice box may be used. Panel mounting the valve is similar to wall mounting the device. Line up the No. 8 mounting holes and slot in yoke with holes in the panel or drill new holes. Attach the valve to the panel using mounting screws (not included). Standard valves are supplied with coils designed for continuous duty service. Normal free space must be provided for proper ventilation. When the coil is energized continuously for long periods of time, the coil housing will become hot. The coil is designed to operate permanently under these conditions. Page 3

Three-way Electro-pneumatic (EP) Valve Model 2 Troubleshooting Table 1. Troubleshooting. Problem Valve fails to operate External leakage Internal leakage Noise or buzzing Procedure 1. Check electrical supply with voltmeter. 2. Check coil with ohm meter for short or open coil. 3. Check pressure line for dirt. Replace valve. Standard valve design permits 40 cc/min. max. @ 50 psi. Check voltage with voltmeter to be sure it corresponds with nameplate rating. Also check pressure for same. Service Coil Replacement Replacement coils are the only replacement parts available. For replacement part numbers, see Service Parts. Since the body and sleeve are permanently staked together, only the coil can be replaced. The procedure to replace a coil is as follows: 1. Disconnect coil from electrical service. 2. Remove air pressure. 3. Remove top clip and pull coil off. 4. Put new coil on and replace clip. Service Parts 5. Connect electrical service and air pressure. Table 3. Service Parts. Current Products E.P. Product Number Repair Coil (pkg. 3) 265-1001 265-060 265-1002 265-061 265-1003 265-062 265-1004 265-063 265-1005 265-064 265-1006 265-065 265-1007 265-060 265-1008 265-061 Page 4

Three-way Electro-pneumatic (EP) Valve Model 2 Dimensions Figure 2. Dimensions in Inches (Millimeters). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers is a registered trademark of Product or company names mentioned herein may be the trademarks of their respective owners. 2005 Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. 155- Printed in the USA Page 5