EATON 9315 UPS 200 TO 300 KVA Specifications Input Voltage Range See table below Frequency Range (60Hz) 57-64 Hz (50Hz) 47-53 Hz Surge Protection Meets ANSI C62.41, Category A & B EN 50091-2 and EN50082-2 Power Factor 0.95 Typical at full load with input filter Output Voltage Regulation Better than +/- 1% Voltage THD Less than 5% (100% nonlinear load); Less than 3% (100% linear load) Transient Response Less than 5% for 100% load, step full recovery within 1 cycle (2.5 ms) Frequency Regulation (Free Run) +/- 0.005 Hz Frequency Sync Range +/- 0.5 Hz Frequency Slew Rate 1 Hz/sec. Load Crest Ratio 3:1 Battery Battery Type Sealed, maintenance-free lead acid Recharge time 10-12x discharge to 95% capacity Safety UL 1778 Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed All Cabinets provide seismic mounting features selectable DC ground fault detection capability Environmental and Safety Audible Noise <65 dba at 1 meter Ambient Operating Temperature 0C to 40C Ambient Storage Temperature -20C to +70C Altitude 5000 ft. (1500 m) without derating Relative Humidity 5-95% non-condensing
EMI Suppression Meet FCC Class A, Subpart J of Part 15 and EN 50091 (CIPR22,ClassA) Electrostatic Discharge Withstands 25 kv without damage or disturbance to load * Specifications subject to change without notice. MODEL SELECTION GUIDE 9315-200 9315-250 /200 9315-250 9315-225 9315-300 /225 9315-300 200 kva /160 kw 200 kva /160 kw 250 kva /200 kw 225 kva /180 kw 225 kva /180 kw 300 kva /240 kw Input voltage volts 400 400 400 208 480 480 480 600 480 600 Output Voltage volts 400 400 400 208 208 480 480 600 480 600 Input Voltage Range Minimum volts 340 340 340 177 408 408 408 510 408 510 Maximum volts 440 440 440 229 528 528 528 660 528 660 Input /Output Frequency Hz 50/60 50/60 50/60 60 60 60 60 60 60 60 AC Input (with input filter) Nominal Amps amps 254 245 318 544 245 245 245 200 326 267 Maximum Amps amps 317 306 397 680 306 306 306 250 408 333 AC Input (without input filter) Nominal Amps amps 288 288 374 640 288 288 288 236 384 314 Maximum Amps amps 360 360 360 800 360 360 360 294 480 392 Bypass Input Nominal Amps amps 290 290 360 625 625 271 271 217 360 289 AC Output Nominal Amps amps 290 290 360 625 625 271 271 217 360 289
10 Minutes Max. amps 363 363 450 782 782 339 339 272 450 361 DC Link Nominal DC Voltage volts 420 420 420 480 480 480 480 480 480 480 Float Voltage volts 473 473 473 540 540 540 540 540 540 540 End of Discharge volts 351 351 351 401 401 401 401 401 401 401 Maximum Amps amps 457 457 571 450 450 450 450 450 600 600 Physical attributes (without battery) Installed Weight lbs 3812 4177 4177 6363 3863 3863 4177 6677 4177 6677 Installed Width inches 65 65 65 103 65 65 65 93 65 93 System Efficiencies 100% Load % 92 92 91 91 92 92 92 91 92 91 75% Load % 92 90 90 91 92 92 92 90 92 91 50% Load % 92 88 89 90 91 91 91 88 92 89 Full Load Heat Dissipation BTU/Hr. (x1000) 47.8 47.8 59.7 61.8 53.7 46.2 39.2 61.7 71.7 82.4 KCal/Hr. (x1000) 12.5 12.5 15.0 15.5 13.5 11.6 9.8 15.5 18.1 20.8 Inverter Efficiency (full load) - % 93 93 93 93 92 93 94 93 93 93 BATTERY RUN TIMES (IN MINUTES) 50 Hz Applications Model Number 9315-200 9315-250 kva 200 200 200 200 250 250
kw 160 180 160 180 200 225 Battery Type Number Parallel Strings J27 - UPS12-270 2 9 7 9 7 5 - C28 - HRL12280 2 9 7 9 7 5 - J31 - UPS12-310 2 11 9 11 9 7 6 C33 - HRL12330 2 12 10 12 9 8 6 J37 - UPS12-370 2 15 11 15 11 11 8 C39 - HRL12390 2 16 13 16 13 11 9 J47 - UPS12-475 2 19 15 19 15 13 9 C50 - HRL12500 2 20 17 20 17 14 11 J27 - UPS12-270 3 17 13 17 13 12 9 C28 - HRL12280 3 18 14 18 13 13 10 J31 - UPS12-310 3 21 18 21 18 15 12 C33 - HRL12330 3 22 19 22 19 16 13 J37 - UPS12-370 3 27 22 27 22 19 15 C39 - HRL12390 3 27 23 27 23 20 17 J47 - UPS12-475 3 37 29 37 29 26 21 C50 - HRL12500 3 37 30 37 30 27 22 J27 - UPS12-270 4 27 21 27 21 19 15 C28 - HRL12280 4 27 22 27 21 20 16 J31 - UPS12-310 4 32 27 32 27 24 19 C33 - HRL12330 4
Nominal DC Link Voltage 420 420 420 420 420 420 60 Hz Applications Model Number 9315-225 9315-300 kva 225 225 225 225 300 300 kw 180 202 180 202 240 270 Battery Type Number Parallel Strings J27 - UPS12-270 2 9 7 9 7 - - C28 - HRL12280 2 9 7 9 7 - - J31 - UPS12-310 2 12 9 12 9 7 5 C33 - HRL12330 2 13 10 13 10 7 5 J37 - UPS12-370 2 15 12 15 12 9 7 C39 - HRL12390 2 17 15 17 15 10 7 J47 - UPS12-475 2 20 16 20 16 11 8 C50 - HRL12500 2 22 18 22 18 13 10 J27 - UPS12-270 3 17 14 17 14 11 9 C28 - HRL12280 3 19 16 19 16 12 9 J31 - UPS12-310 3 22 18 22 18 14 10 C33 - HRL12330 3 24 20 24 20 15 13 J37 - UPS12-370 3 28 22 28 22 18 14 C39 - HRL12390 3 29 24 29 24 19 16 J47 - UPS12-475 3 38 31 38 31 25 19 C50 - HRL12500 3 38 32 38 32 26 21 J27 - UPS12-270 4 28 22 28 22 17 14
C28 - HRL12280 4 28 23 28 23 18 15 J31 - UPS12-310 4 32 27 32 27 22 18 C33 - HRL12330 4 33 28 33 28 23 19 J37 - UPS12-370 4 40 33 40 33 28 22 C39 - HRL12390 4 40 34 40 34 28 23 J47 - UPS12-475 4 55 48 55 48 38 31 C50 - HRL12500 4 54 47 54 47 35 29 Nominal DC Link Voltage 480 480 480 480 480 480 EATON 9315 UPS 400 TO 500 KVA Specifications Input Voltage Range See table below Frequency Range (60 Hz) 57-64 Hz Surge Protection Meets ANSI C62.41, Category A & B EN 50091-2 and EN50082-2 Power Factor 0.95 Typical at full load with input filter Output Voltage Regulation Better than +/- 1% Voltage THD Less than 5% (100% nonlinear load); Less than 3% (100% linear load) Transient Response Less than 5% for 100% load, step full recovery within 1 cycle Frequency Regulation (Free Run) +/- 0.005 Hz Frequency Sync Range +/- 0.5 Hz Frequency Slew Rate 1 Hz/sec. Load Crest Ratio 3:1 Power Factor 0.9 (Optional) Battery
Battery Type Sealed, valve regulated lead acid Recharge time 10-12x discharge to 95% capacity Safety UL 1778 Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed All Cabinets provide seismic mounting features selectable DC ground fault detection capability Environmental and safety Audible Noise <72 dba at 1 meter Ambient Operating Temperature 0 C to 40 C Ambient Storage Temperature -20 C to +70 C Altitude 5000 ft. (1500 m) without derating Relative Humidity 5-95% non-condensing EMI Suppression Meet FCC Class A, Subpart J of Part 15 and EN 50091-2 (CIPR22,ClassA) Electrostatic Discharge Withstands 25kV without damage or disturbance to load * Specifications subject to change without notice. MODEL SELECTION GUIDE 9315-400 9315-400/300 9315-500 9315-500/400 400 kva/320 kw 300 kva/240 kw 500 kva/400 kw 400 kva/320 kw Input Range Input Voltage volts 400 400 480 480 480 208 Output Voltage Output Voltage volts 400 400 480 480 208 208 Input Voltage Range Minimum volts 340 340 408 408 408 177 Maximum volts 440 440 528 528 528 229 Input /Output Frequency Hz 50/60 50/60 60 60 60 60 AC Input (with input filter) Nominal Amps amps 508 381 556 445 445 1025
Maximum Amps amps 635 476 640 560 560 1280 AC Input (without input filter) Nominal Amps amps 598 448 654 523 523 N/A Maximum Amps amps 747 560 800 640 640 N/A Bypass Input Nominal Amps amps 577 433 600 480 480 1280 AC Output Nominal Amps amps 577 433 600 480 1110 1110 10 Minutes Max. amps 721 541 750 600 1388 1388 DC Link Nominal DC Voltage volts 420 420 480 480 480 480 Float Voltage volts 473 473 540 540 540 540 End of Discharge volts 351 351 401 401 401 401 Maximum Amps amps 914 686 1000 800 800 800 Physical Attributes (with-out battery) Installed Weight lbs 6100 6100 6100 6100 10,100 14,100 Installed Width inches 74 74 74 74 123 172 System Efficiencies 100% Load % 94 94 94 92 91 90 75% Load % 94 94 94 92 91 90 50% Load % 94 93 94 91 90 89 Full Load Heat Dissipation BTU/Hr. (x1000) 69.8 52.3 87.2 107.3 107.3 119.0 KCal/Hr. (x1000) 17.6 13.2 22 24.1 27.1 30.0 Inverter Efficiency (full load) - % 95 95 95 92.5 92.5 92.5
BATTERY RUN TIMES (IN MINUTES) 50 Hz Applications Model Number 9315-400 kva 300 300 400 400 kw 240 270 320 360 Battery Type Number Parallel Strings J37 - UPS12-370 2 7 5 - - C39 - HRL12390 2 7 5 - - J47 - UPS12-475 2 8 6 - - C50 - HRL12500 2 9 7 - - J27 - UPS12-270 3 9 7 - - C28 - HRL12280 3 9 7 - - J31 - UPS12-310 3 11 9 6 - C33 - HRL12330 3 12 9 6 - J37 - UPS12-370 3 15 11 9 7 C39 - HRL12390 3 16 12 10 7 J47 - UPS12-475 3 19 15 11 8 C50 - HRL12500 3 20 16 12 10 J27 - UPS12-270 4 14 11 9 7 C28 - HRL12280 4 14 12 10 7 J31 - UPS12-310 4 18 14 11 9 C33 - HRL12330 4 19 15 12 10 J37 - UPS12-370 4 23 19 15 11 C39 - HRL12390 4 24 20 15 12 J47 - UPS12-475 4 31 26 19 15
C50 - HRL12500 4 31 27 20 16 Nominal DC Link Voltage 420 420 420 420 60 Hz Applications Model Number 9315-500 kva 400 400 500 500 kw 320 360 400 450 Battery Type Number Parallel Strings J47 - UPS12-475 2 5 - - - C50 - HRL12500 2 6 - - - J27 - UPS12-270 3 6 - - - C28 - HRL12280 3 6 - - - J31 - UPS12-310 3 8 6 5 - C33 - HRL12330 3 9 6 5 - J37 - UPS12-370 3 12 9 7 6 C39 - HRL12390 3 13 10 7 6 J47 - UPS12-475 3 15 10 9 7 C50 - HRL12500 3 17 13 10 7 J27 - UPS12-270 4 11 9 7 5 C28 - HRL12280 4 12 9 7 5 J31 - UPS12-310 4 14 10 9 7 C33 - HRL12330 4 15 12 10 7 J37 - UPS12-370 4 18 14 13 10 C39 - HRL12390 4 19 16 14 11
J47 - UPS12-475 4 25 19 17 13 C50 - HRL12500 4 23 19 18 14 Nominal DC Link Voltage 480 480 480 480 POWERWARE 9315 UPS 625 TO 750 KVA Specifications Input Voltage Range +10% to -15% Frequency Range +/-5% Surge Protection Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2 Power Factor 0.95 Typical at full load with input filter Output Voltage Regulation Better than +/- 1% Voltage THD Less than 5% (100% nonlinear load); Less than 3% (100% linear load) Transient Response Less than 5% for 100% load, step full recovery within 1 cycle Frequency Regulation (Free Run) +/- 0.005 Hz Frequency Sync Range +/- 0.5 Hz Frequency Slew Rate 1 Hz/sec. Load Crest Ratio 3:1 Safety (pending) UL 1778 Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed EN 50091-1 All Cabinets provide seismic mounting features, selectable DC ground fault detection capability Environmental Audible Noise <75 dba at 1 meter Ambient Operating Temperature 0 C to 40 C Ambient Storage Temperature -20 C to 70 C
Altitude 5000 ft. (1500 m) at 40 C without derating Relative Humidity 5-95% non-condensing EMC Meet FCC Class A, EN 50091-2 (CISPR 22, Class A, Restricted Access) Electrostatic Discharge Withstands 25kV without damage or disturbance to load *Specifications subject to change without notice. MODEL SELECTION GUIDE 9315-750 9315-750/625 750 kva/600 kw 625 kva/500 kw Input Voltage volts 480 600 480 600 Output Voltage volts 480 600 480 600 Input Voltage Range Minimum volts 408 510 408 510 Maximum volts 528 660 528 600 Input/Output Frequency Hz 60 60 60 60 AC Input (with input filter) Nominal Amps amps 913 730 761 609 Maximum Amps amps 1141 913 951 761 Bypass Input Nominal Amps amps 902 722 752 601 AC Input (without input filter) Nominal Amps amps 902 722 752 601 10 minutes max amps 1128 902 940 752 DC Link Nominal DC Voltage volts 384 384 384 384 Float Voltage volts 432 432 432 432 End of Discharge volts 320 320 320 320
Nominal Amps amps 1954 9554 1628 1628 Physical Attributes (w/o batt.) Single Module RT Configurations Installed Weight lbs 13,200 13,200 13,200 13,200 Installed Width inches 149" 149" 149" 149" Multimodule Configurations Installed Weight lbs 12,600 12,600 12,600 12,600 Installed Width inches 126 5/8" 126 5/8" 126 5/8" 126 5/8" System Efficiencies 100% Load % 94 94 94 94 75% Load % 94 94 94 94 50% Load % 93 93 93 93 Full Load Heat Dissipation BTU/Hr. (x1000) 130.8 130.8 109.0 109.0 KCal/Hr. (x1000) 33.0 33.0 27.5 27.5 Inverter Efficiency (Full Load) % 95 95 95 95