INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Similar documents
Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

SERIES PC INSTRUCTION AND OPERATION MANUAL

Medium and high pressure pumps

HORIZONTAL SPLIT CASING PUMP

Impeller Replacement

PROCESS PUMPS (INDIA) PVT LTD

S3 General Installation

INSTRUCTION MANUAL INTERNAL GEAR PUMP TITAN G-4124A SERIES=> FLANGED TITAN G-124A SERIES => FLANGED MODELS:

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

PROCESS PUMPS (INDIA) PVT LTD

PROCESS PUMPS (INDIA) PVT LTD

INSTRUCTIONS Installation Operation Repair

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

This instruction is valid for all ACF/UCF pump models shown on page 2

SUMP PUMP ASP-25 OPERATION & MAINTENANCE GUIDE

MAINTENANCE AND REPAIR INSTRUCTIONS

VSCP Vertical Suspended Column Pump Operation & Maintenance Manual

Installation, Operation and Maintenance Manual SCP/SFP SELF PRIMING PUMPS

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING VACUUM PUMPS

OPERATION & MAINTENANCE MANUAL HANGZHOU FLYING TECHNOLOGY CO., LTD.

TECHNICAL SERVICE MANUAL GENERAL PURPOSE BRACKET MOUNTED PUMPS SERIES 115 MODELS G, GX2, H and HX4

ABS Dry Installed Waste Water Pumps Series FR

This instruction is valid for all ACF/UCF pump models shown on page 2

NECO Pumping Systems

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

INSTRUCTION MANUAL AC2516 REVISION D INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Series 1580 In-Line Mounted Centrifugal Fire Pumps

2.- HANDLING OF VALVES BEFORE ASSEMBLY 3.- FITTING THE VALVE TO THE REST OF THE ASSEMBLY 5.- PERIODICAL INSPECTION OF THE VALVE AND MAINTENANCE

SERVICE MANUAL 200 SERIES MOTORIZED 20352, 20452, 20551, 20552, AND MODELS

END SUCTION CENTRIFUGAL PUMPS

Series Base mounted pump. Installation and operating instructions

OWNER S TECHNICAL MANUAL

TECHNICAL SERVICE MANUAL GENERAL PURPOSE JACKETED PUMPS SERIES 230 MODELS HX4, KK, LQ, Q, M, N

OWNER S TECHNICAL MANUAL. 6336N 2.5kg Grease Kit

5000/6000 SERIES BALL VALVES INSTALLATION - MAINTENANCE MANUAL

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

The ELM Series Slurry Pump Installation and Operating Manual


PROCESS PUMPS (INDIA) PVT LTD

High-pressure pumps Series HP49

TYPE E Main Valve Sizes 3 /8 through 12

INSTALLATION AND SERVICE INSTRUCTIONS FOR 1008 AND 1010 SERIES PUMPS

TECHNICAL SERVICE MANUAL HEAVY-DUTY BRACKET MOUNTED PUMPS SERIES 120 and SERIES 124 MODELS J, K, KK, L, LQ, LL AND LM

WARMAN PUMPS ASSEMBLY, OPERATING AND MAINTENANCE INSTRUCTIONS PART 2C SERIES A SOLUTION PUMPS TYPE S AND SH PC2C

Maintenance and Service Instruction

Starting up hydraulic systems

TECHNICAL SERVICE MANUAL INSTALLATION, START UP, TROUBLESHOOTING, SERIES SG-04, SG-05 & SG-07 spur gear PUMPS

Principals of Operation... 1 Rotary Vane Priming Pump VPE and VPES... 2 Rotary Vane Priming Pump VPO and VPOS Priming Valve...

Installation and Start-up Instruction. This instruction is valid for all standard low pressure pumps: LPD, ACD, ACE, ACG/UCG, ACF/UCF, LPQ and ABQ

INSTRUCTION AND REPAIR MANUAL MODELS 341A, 342A AND 344A 6

1750 RPM Centrifugal Pumps

METERING/DOSING PUMP CLOSE-COUPLED B4015D, B4050D, B4100D, B4190D, B2400D, AND B4400D MODELS

Contents. Identification

PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user

GT-200 GATE VALVES PN16, Screwed end

KP-C Series. Close Coupled End Suction Centrifugal Pumps. Installation, Operation and Maintenance

INSTALLATION INSTRUCTION & TECHNICAL MANUAL FLOWMETER

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling.


Agri KAM INSTALLATION, OPERATION AND MAINTENANCE MANUAL. A View of KBL Dewas Manufacturing Plant. A Kirloskar Group Company KIRLOSKAR BROTHERS LIMITED

END SUCTION CENTRIFUGAL PUMPS

Elite. KSB Australia Pty Ltd. Centrifugal Pump

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING VACUUM PUMPS WITH MECHANICAL SEALS DELTA B75

AJAX PUMPS PUMPS AJAX. ~Pli~r. on s SYDNEY BRISBANE ADELAIDE PERTH. ~Pli~[ ODS ~ISTON PURPOSES

PROCESS PUMPS (INDIA) PVT LTD

Model GP Triplex Ceramic Plunger Pump Operating Instructions/ Manual

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

Operating Manual for Rotary Gear Pumps CMI, S.A. (Mendaro, Guipuzkoa, Spain)

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS

Installation and Service Instructions. ST Series Pumps

1750 RPM Centrifugal Pumps

General. Shaft Seal. Nozzle Orientations. Field of Application. Design. Drive. Bearings. Product Catalogue

ISO 9001 CERTIFIED COMPANY INDUSTRIAL PUMPS. Installation & Operational Manual For BACK-PULL-OUT PUMP

MET-PRO. Fybroc series 1600 horizontal pumps. Global Pump Solutions I N S T A L L A T I O N M A N U A L

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Mr. Proprietor

Unistream Pumps UNISTREAM RANGE CENTRIFUGAL PUMP OPERATORS INSTRUCTIONS ++44(0) (0) Telephone: Fax:

TECHNICAL SERVICE MANUAL

PRODUCT OBSOLETED 4Q16

PR Series Positive Rotary Pumps

TABLE OF CONTENT. 7-Operating mechanisms of Non-return valve with hydraulic damping cylinder

Operating Instructions

SERIES G3DB/AG3DB ELEVATOR

Table of Contents Illustrations

SAM TURBO INDUSTRY LIMITED

M Series Condensate Recovery Unit

OPERATION MANUAL INTERNAL GEAR PUMP. Models: NG-H, NG-HL, NG-K, NG-KK, NG-L, NG-LQ, NG-LL, NG-LS, NG-Q, NG-QS. Tel: Fax:

series 1500 horizontal pumps

Instruction manual. Installation requirements. Power Take-Off. Pump mounting: Spline shaft DIN 5462 / ISO 14. Mounting flange ISO 7653-D.

DELTA STYLE 9500 CARTRIDGE SPLIT SEAL INSTALLATION INSTRUCTIONS INTRODUCTION:

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company

End Suction Centrifugal

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual

Series Base mounted pump. Installation and operating instructions

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

General Service Centrifugal Pump. 1. Application. 3. Designation. 2. Design. 4. Operating Data. Operating Instructions Nº A2744.

JACKALL HYDRAULIC SYSTEM

TOTE TYPE INK PUMPS WARNING. Doc. No. INK 018U-05 Model No IP140S3-TE IP140S12-TE IP200S25-TE IP250S20-TE

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

SELF PRIMING CHEMICAL SERVICE PUMPS

Transcription:

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Contents Section 1. General Observations... 2 2. Operation... 4 3. Control During Operation... 5 4. Trouble Shooting... 6 5. Maintenance... 7 Please read these Operating instructions before installation and operation of the pump. Should the pump or pumping set suffer damages because these instructions have not been followed the guarantee will become void. 1

1. GENERAL OBSERVATIONS 1.1 Location of Unit The installation location should provide enough room for inspection and maintenance work. The room should be well aired. If the temperature of the pumped liquid is high (80 C to max. 120 C) the room temperature should not exceed 40 C (otherwise use special motors). The pump-motor unit should be firmly fastened to its base in such a way that loosening through vibration is avoided during operation. Depending on the type of installation, horizontal and vertical installations are possible. The appropriate type of electric motor has to be selected. If vertically installed the position of the motor underneath the pump should be avoided since leakage through the mechanical seal may penetrate into the motor bearings. The pipework should be connected and supported in such a way that no stress is introduced into the pump casing. After unfastening the flange bolts, both flanges should spring apart by the thickness of the gasket and neither separate under an angle nor stay together under force. The preconditions are that: (a) (b) (c) suction and discharge pipes connect easily; suction and discharge pipes are independently supported near the pump; flexible connections are used if the temperature of the pumping liquid is high. Flange gaskets should not protrude into the bore, which should be clean of weld splatter, burrs, rust and other impurities. 1.2 Suction Piping The suction line should: (a) be as short and straight as possible and made one or two sizes larger than the pump suction, so that the flow velocity does not exceed 1.5-2.0 m/sec; (b) (c) be equipped with eccentric reducers where the excess diameter is located on the lower side to avoid formation of an air pocket (Fig.1) be absolutely airtight and rise towards the pump or at least run horizontally;

(d) be equipped with a gate or foot valve. These valves must not be used to control the pump flow and must always remain fully open when the pump is running. 1.3 Discharge Piping The discharge line should: (a) (b) (c) have a diameter sufficiently large to limit the flow velocity to 2.5-3 m/sec; be fitted with a non-return valve between pump and discharge valve to prevent reverse flow while the pump is stopped. This is particularly important when pumps are operated in parallel. If reverse flow is allowed to occur, the pump will 'turbine' backwards and may be damaged when started under these conditions; be equipped with a discharge valve for start-up and flow regulation. 1.4. Piping in General All bends should have large radii and their number should be limited to a minimum. If a strainer is used in the suction line to prevent foreign matter from being drawn into the pump the screen should have sufficient openings to keep the flow velocity through it below 0.6 m/sec. 1.5 Shaft Sealing This pump is equipped with either a mechanical seal or a packed gland. Check if the pump shaft can be rotated easily by hand. Do not start or rotate the pump without liquid nor rotate in the wrong direction since this will seriously damage the mechanical seal. 1.6 Attention: Empty pump and piping if there is danger of frost!

2. OPERATION 2.1 Control before Start-up The pump is ready for start-up when: the motor-pump unit is firmly mounted; the direction of rotation of the motor is correct; the motor protection has been adjusted to maximum load as indicated on the motor identification plate; the pump and suction line are primed; If the pump operates under positive suction pressure, priming may be achieved by venting the pump through the vent plug (057 in cross section). If the pump operates in a suction mode with a foot valve, the pump may be primed by filling pump and suction line through the vent plug. If no foot valve is installed, the pump can be primed with a vacuum pump. the pump shaft rotates freely. the alignment of the pump and motor must be checked and re-aligned. Initial factory alignment can alter when the base plate is secured on site. 2.2 Start-up Start the unit with closed discharge valve until pressure has built up in the discharge line, then open discharge valve slowly. Do not operate unit for prolonged periods with closed discharge valve to avoid over-heating of liquid and pump. The pump set should be shut down at once and the trouble corrected if: little or no liquid is delivered; the pump does not build up enough pressure; the pump set vibrates or makes excessive noise (watch for cavitation 'crackle').

3. CONTROL DURING OPERATION The following items should be checked on a routine basis: shaft sealing A new mechanical seal can leak after start-up. After approx. 60 min. of run-in, leakage should not exceed 1-2 drops per minute. Packed glands must drip. leakage of entire installation the cleanliness of the suction strainer (a clogged strainer may cause cavitation!) the relative pressure in suction and discharge lines the power absorbed by the electric motor the speed of rotation noise and vibration level of the pump-motor unit the temperature of the motor bearings (max. 70 C)

4. TROUBLE SHOOTING DEFECTS No liquid delivered CAUSES 1 Pump not primed X Not enough liquid delivered 2 Speed too low X X X Not enough pressure Loss of liquid after starting 3 Speed too high X X 4 Air leak on suction X X X X X 5 Air leak in seal X X 6 Air or gas in liquid X X X X 7 Discharge head too high (above rating) X X X X 8 Suction head too high X 9 Not enough suction head for hot liquid X 10 Inlet pipe not submerged enough X X X X X 11 Viscosity of liquid greater than rating X X X 12 Liquid heavier that rating X 13 Insufficient nett inlet head X X X X X 14 Impeller plugged up X X X 15 Wrong direction of rotation X X X 16 Excessive wear ring clearance X X 17 Damaged impeller X X X 18 Rotor binding X 19 Defects in motor X 20 Voltage and/or frequency lower than rating X 21 Foundation not rigid X 22 Misalignment of pump and driver X X 23 Bearing worn X 24 Rotor out of balance X 25 Pump shaft bent or improperly aligned with motor shaft 26 Impeller too small X X Vibration X Motor runs hot X Cavitation (Noise)

5. MAINTENANCE This pump does not need any special maintenance. However, it should be examined at regular intervals for vibration-free running, power absorption and leakages. Do not 'service' a well-operating mechanical seal since the seal faces have run in together in a given position. If the seal is disassembled and reassembled the faces will not touch in exactly the same position and as a consequence, the seal may leak. 5.1 Change of mechanical seal If the seal leaks more than 1-2 drops per minute and if this amount of leakage cannot be tolerated in the respective installation, the seal will have to be replaced by a new one since an adjustment is not possible. The pump casing can stay in the piping. Remove the nuts from the casing studs, and remove the bearing housing support foot. Withdraw the complete rotating element. Remove impeller nut, impeller and impeller key. Remove shaft sleeve, if fitted, and mechanical seal. Disengage casing cover. Before and after disassembly determine the cause of the seal failure. Frequently the cause does not lie in the mechanical seal itself but in the condition of the pump or its surrounding (i.e. dirt, temperature, excessive axial play, etc.). Examine the shaft sleeve and shaft (seat of sleeve gasket) for damage and replace if necessary. Check proper running of shaft with dial gauge. Check if the axial and radial play of the motor bearings are within the specified limits. Permissible axial play of the standard IEC motors depends on the location of the fixed bearing - shaft side or ventilator side. Most of the manufacturers locate the fixed bearing on the ventilator side and as a consequence the axial play on the shaft side can vary between 0.9-1.2 mm when the motor is cold. If motors of this design are used care has to be taken that the movable ring will slide easily on the sleeve (moisten shaft sleeve with vegetable oil or liquid soap). Complete units which are assembled at the factory are preferentially equipped

with motors whose fixed bearing is located on the shaft side, thereby reducing the axial play when cold to 0-0.2 mm Carefully clean seal chamber, sleeve and shaft before reassembly. Do not damage contact surfaces of seal faces. If PTFE O-rings are used, heat these rings in water bath to 80 o before assembling. Lubricate shaft sleeve slightly with vegetable oil or liquid soap. Mount seal cover, which supports the stationary ring of standardised seals, perpendicular to shaft. It is recommended that casing gasket (005)) be exchanged together with the mechanical seal Attention: When in doubt about the replacement seal or the elimination of the cause of the defect, consult with a specialist. 5.2 Change of Gland Packing The pump casing can stay in the piping. Remove gland (Ref. No. 20) from the rear of the casing cover. Remove all rings of old packing without damaging shaft or stuffing box bore. New Packing can now be installed in the stuffing box. Insert the first ring and tap it to the bottom of the stuffing box. Each following ring should be installed in the same manner and positioned in the stuffing box so that the split is advanced 90 0. When the correct number of packing rings have been inserted, the last ring should not protrude past the stuffing box face, so that the Gland may be properly started in the stuffing box bore. Install Gland and tighten finger tight only. When the pump has been running for 10 minutes at full pressure, adjust nuts so that there is only a small leakage. A small leakage is essential to ensure that the packing is lubricated. Excessive Gland pressure will cause damage by cutting off lubrication to the packing and will burn and damage the shaft. 5.3 Leakage Test After assembly, fill pump with water and connect to pressure network (max. 10 bar) to check for leakage.

5.4 Pedestal bearings Sealed for life bearings require no lubrication and no provision is provided for this purpose. Greasable bearings will require regular greasing via the two ball-type grease nipples. Lubrication data for the following R.P.M.: 1500 R.P.M. : Approximately every 5,000 operating hours. 3000 R.P.M. : Approximately every 2,500 operating hours. After approximately 10,000 operating hours, but not later than two years, the ball bearings need to be dismantled, washed, re-greased and can then be refitted. Under unfavourable operating conditions ( dusty, wet or high ambient temperatures) The period for re-greasing must be must be far shorter. The amount of grease required for each bearing depends entirely on the size of the ball bearing. SHAFT UNIT AMOUNT OF GREASE (gr.) 25 5 35, 35/1 8 35H 14 45, 45/1 12 If the bearings are over greased ( too much grease in the bearings) there is a danger of hot running. We recommend the following grease: (or their equivalent) ESSO SHELL B.P. BEACON EP3. SHELL ALNANIA R.2. B.P. ENERGREASE L.S.3. OIL LUBRICATED bearings have normal clearances. The quantity of oil used depends on bearing pedestal Shaft Unit size. SHAFT UNIT PUMP END BEARING COUPLING END BEARING APPROX. HOUSING OIL CONTENT 25 6305 6305 Approx. 0.2 litre. 35, 35/1 6307 6307 Approx. 0.55 Litre. 35H 3307 3307 Approx. 0.55 Litre. 45, 45/1 6309 6309 Approx. 0.9 Litre.

5.4 Pedestal bearings, continued. Lubricating oil must meet the following requirements: Extreme cleanliness, resistance to ageing, good viscosity and temperature behaviour, good water separating properties and corrosion protection. We recommend, depending on the operating temperature of the bearings and the speed Of the pump, to use lubricating oils according to DIN 51517. Operating Temperatures up to 80 0 Up to 1500 RPM More than 1500 RPM Bearing operating Temperatures Ambient Temperature < above 80 0 C 0 0 C Type of lubricating oil to DIN 51517 C49 C36 C68 C25 Kinematics viscosity at 50 0 C 10-6 m 2 /s 49~5 36~4 68~6 25~4 Suitable motor oil SAE 20 AND 20W SAE 30 SAE 10W

Regent Dinflow 14.3 PARTS LIST No. 2. PARTS LIST SECTION 14 PAGE 36 MARCH 1998 ITEM NUMBER DESCRIPTION QTY. PER UNIT ITEM NUMBER DESCRIPTION QTY. PER UNIT 001 CASING 1 049 IMPELLER LOCK WASHER 1 002 IMPELLER 1 050 IMPELLER KEY 1 003 CASING COVER 1 051 COUPLING KEY 1 005 GASKET, CASING 1 054 CASING WEAR RING 1 013 SLINGER 1 055 DRAIN PLUG 1 014 BEARING HOUSING 1 056 GASKET, DRAIN PLUG 1 015 SHAFT 1 057 GAUGE PLUG 1 033 SUPPORT FOOT 1 058 GASKET, GAUGE PLUG 1 036 GLAND 1 100-0 STUD, CASING 8/12 037 LANTERN RING 1 100-1 STUD, CASING COVER 6/8 038 GLAND PACKING 4 100-2 STUD, GLAND 2 039 BEARING CAP 2 102-0 SET SCREW, SUPPORT FOOT 1 040 GASKET, BEARING CAP 2 102-1 SET SCREW, BEARING CAP 6 041 BEARING 2 110-0 HEXAGON NUT, CASING 8/12 042 FELT SEAL 2 110-1 HEXAGON NUT, CASING COVER 6/8 046 SHAFT SLEEVE 1 110-2 HEXAGON NUT, GLAND 2 047 GASKET, SHAFT SLEEVE 1 115-0 FLAT WASHER, GLAND 2 048 IMPELLER NUT 1 115-1 FLAT WASHER, SUPPORT FOOT 1

REGENT 'A' STYLE MECHANICAL SEAL ARRANGEMENT MECHANICAL SEAL ITEM DESCRIPTION 35 MECHANICAL SEAL 36 SHAFT SLEEVE 37 SEAL PLATE 41 O-RING