Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Similar documents
B kv Gas-insulated Substations

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

3AP1 DTC for 145 and 245 kv

Gas-insulated switchgear from 72.5 to 550 kv. Excellent systems that create lasting value. siemens.com/energy-management

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

HIS Highly Integrated Switchgear up to 550 kv, 63 ka, 5000 A Type 8DQ1

B kv T&D GAS INSULATED SWITCHGEAR

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

SIMOBREAKER The New Substation with Rotary Disconnector Fully Assembled, Compact and with High Availability

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group April 17, 2009 Slide 1

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Gas-Insulated Switchgear up to 245 kv, 50 ka, 3150 A Type 8DN9. Power Transmission and Distribution

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group May 15, 2013 Slide 1

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

ZX2.2 Gas-insulated medium voltage switchgear

Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1. siemens.com/energy. Answers for energy.

Gas-Insulated Switchgear up to 145 kv, 40 ka, 3150 A Type 8DN8. Answers for energy.

3EK7 Distribution Class Surge Arresters. Answers for energy.

3EP6 porcelain surge arrester

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Gas Insulated Switchgear

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

Benefits, typical uses

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

HIS Highly Integrated Switchgear up to 145 kv

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

Surge Arresters. Supply Program. Answers for energy.

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

PASS M0. Innovative solutions for distribution substations up to 170 kv

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

NXPLUS C Single busbar. Maintenance-free for lifetime

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

New dimensions. Siemens Wind Turbine SWT Answers for energy.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

Product Brochure. Gas-insulated Switchgear ELK-14 The modular system for GIS, 245 kv

Air-insulated switchgear UniGear type ZS1

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

3AH37 and 3AH38 vacuum generator circuit-breakers for power stations and industry

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

GRAND RENEWABLE ENERGY PARK PROJECT DESCRIPTION REPORT. Attachment C. Turbine Specifications

MEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Power Transmission and Distribution. NXPLUS C double busbar. The economical solution when replacing old systems

Gas-Insulated Switchgear up to 145 kv, 40 ka, 3150 A Type 8DN8. Power Transmission and Distribution

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Raising the bar. UHV switchgear and components

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Outdoor vacuum breaker for railway applications - FSK II

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

Product brochure. Gas-insulated switchgear ELK-4, 800 kv Pioneering technology for extra-high voltage applications

Gas Insulated Metal-clad Switchgear, HMGS!

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

3TM Vacuum Contactors

123/145kV SF6 Gas-Insulated Switchgear incorporating VCB. 145kV-1250~2000A-31.5kA

High-Voltage Products. Reliable products for all customer requirements. siemens.com/energy-management

Stefano Cervidi - ABB S.p.A. PPHV Santiago de Chile J.T. ABB Chile de Abril 2015 PASS - Plug and Switch System Subestaciones con tecnologìa

Surge Arrester 3EL2 superior protection up to 550 kv

Power Transmission and Distribution. HIS Highly Integrated Switchgear up to 550 kv. Type 8DQ1

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids

XIRIA Green, Smart, Compact solution

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

High-Voltage Circuit Breakers

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

8DJ. Maintenance-free for lifetime

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

Independent Testing Laboratory for High Voltage Equipment

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

TECHNICAL DESCRIPTION

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

CPG.0 Single busbar gas-insulated cubicles

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

MEDIUM VOLTAGE SWITCHGEAR

Shoreside power supply. Intelligent solutions for berthed ships based on SIHARBOR / SIPLINK medium-voltage systems. Answers for Energy.

HD4. Gas insulated MV circuit-breakers kv A ka

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

Transcription:

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Table of Contents 1 Introduction... 4 2 Description of retrofit circuit-breaker 8DN8... 5 3 Technical data for retrofit circuit-breaker 8DN8... 6 4 Adapter - retrofitting circuit-breaker 8DN8 - existing switchgear... 7 5 Retrofitting steps... 12 6 Circuit-breaker maintenance comparison old vs. new... 19 7 Time schedule for retrofit solution... 21 8 Scope of delivery... 21 9 Life time expectation of existing GIS without new circuit-breaker... 21 10 Type tests... 21 11 Options... 22 Page 2 of 23

List of Figures Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker... 4 Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8... 5 Fig. 3: 8D2 bay with old blast piston circuit-breaker... 7 Fig. 4: 8D2 bay with 8DN8 circuit-breaker... 8 Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS section... 9 Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters... 9 Fig. 7: Top view of 8DN8-circuit-breaker with two adapters... 10 Fig. 8: Top view of contact arrangement... 11 Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker... 12 Fig. 10: Electrical view... 12 Fig. 11: SF6 pressure view... 13 Fig. 12: Third retrofitting step (a)... 14 Fig. 13: Third retrofitting step (b)... 14 Fig. 14: Fourth retrofitting step (a)... 15 Fig. 15: Fourth retrofitting step (b)... 15 Fig. 16: Fifth retrofitting step (a)... 16 Fig. 17: Fifth retrofitting step (b)... 17 Fig. 18: Sixth retrofitting step: Bay after retrofitting... 18 Fig. 19: Standardized maintenance costs... 20 List of Tables Tab. 1: Technical data for circuit-breaker 8DN8... 6 Tab. 2: Technical data of the adapter... 7 Tab. 3: Comparison SF6 content old/new... 8 Tab. 4: Comparison of the maintenance intervals of the different circuit-breakers... 19 Page 3 of 23

1 Introduction The first SF6-gas insulated switchgear of type 8D1 and 8D2 delivered by Siemens are now 40 years and older. These substations have proved outstanding in operation. They are rugged, reliable, and virtually leak-free (SF6 or oil) and still fulfill their function perfectly. Today, stricter and more economically focused standards apply with respect to the maintenance of gas-insulated switchgear. Especially the SF6 double -pressure circuit-breakers used since GIS systems were first introduced on the market are highly maintenance-intensive. However, since the other GIS components (excluding the original circuit-breaker) require very little maintenance and have an expected life span of over 50 years provided the Siemens maintenance recommendations described in the operating manual are followed, Siemens offers a retrofit solution. This is in the form of a state-of-the-art SF6-circuit-breaker with spring mechanism based on more than 40 years of accumulated experience and intensive research. Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker Page 4 of 23

2 Description of retrofit circuit-breaker 8DN8 The circuit-breaker employed in this retrofit solution is used in the current GIS and HIS substations 8DN8 up to 145 kv and also in 123 kv and 145 kv outdoor circuit-breakers. This type-tested breaker has proven itself in service over the years in thousands of applications. The most important advantages of this self-compression circuit-breaker of the latest generation are: Significantly lower maintenance costs (see chapter 6) Type-tested to the latest IEC standard (at the time of the development) State-of the-art spring mechanism with extremely low maintenance Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8 Page 5 of 23

3 Technical data for retrofit circuit-breaker 8DN8 Standard IEC, latest edition (at the time of the development) Rated voltage 123 145 kv Rated frequency 50/60 Hz Rated short-time power-frequency withstand voltage 230 275 kv Rated lightning impulse withstand voltage 550 650 kv Rated normal current 3150 A Rated short-circuit-breaking current 40 ka Rated short-time withstand current 40 ka Rated duration of short-circuit </= 3 s Rated peak withstand current 100 ka First-pole-to-clear-factor 1.5 SF6 filling pressure at 20 C 0.56 MPa Loss of SF6 0.52 MPa General lockout SF6 0.50 MPa Volume of SF6 gas: 35kg Break time 60 ms Opening time 32 +/- 3 ms Arcing time (50 Hz) 24 ms Closing time 55 +/- 6 ms Operating sequence (IEC) CO-15s-CO or O-0.3s-CO-3min-CO Motor spring operating mechanism 220 V DC / 3.0 A / 10 A 230 V AC / 8.0 A / 20 A Auto reclosing 3-pole Closing coil 225 W at 220 V DC Tripping coil 225 W at 220 V DC Auxiliary switch 8 NO/8 NC/1 WI; 250 V / 2.5 A Weight of circuit-breaker without SF6 gas: 900 kg Tab. 1: Technical data for circuit-breaker 8DN8 Replaces: Circuit- breaker for 8D1 and 8D2 up to 145 kv, double-pressure type and blast piston type Page 6 of 23

4 Adapter retrofitting circuit-breaker 8DN8 existing switchgear The adapter, two of which are needed for connecting the new circuit-breaker to the existing switchgear, is type-tested with 650 kv rated lightning impulse withstand voltage and connects the three-phase encapsulated circuit-breaker with the single-phase encapsulated switchgear. The adapter forms a single SF6-gas compartment with joint gas monitoring together with the circuit-breaker. It is connected to the existing GIS switchgear through gas-tight bushings. Rated lightning impulse withstand voltage: Weight of an adapter: SF6 filling pressure at 20 C: Volume of SF6 gas/adapter: Tab. 2: Technical data of the adapter 650 kv approx. 200 kg 0.56 MPa 18.75 kg Fig. 3: 8D2 bay with old blast piston circuit-breaker Page 7 of 23

Retrofit 8DN8 selfcompression circuitbreaker 123 kv 35 kg 2 x 18.75 kg 8D1/2 double pressure circuit-breaker 123 kv Circuit-breaker Adapter Total volume SF6 gas 72.5 kg 105 kg 87 kg Tab. 3: Comparison SF6 content old/new 8D2 blast piston circuitbreaker 123/145 kv Fig. 4: 8D2 bay with 8DN8 circuit-breaker Page 8 of 23

Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS section Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters Page 9 of 23

Fig. 3 shows the original system with 8D2 blast piston circuit-breaker. In Fig. 4, the circuit-breaker is replaced by an 8DN8 circuit-breaker. The connection between the 3-phase encapsulated 8DN8 circuit-breaker and the remaining single-phase 8D2 encapsulated GIS section is implemented via two adapters as shown in perspective in Fig. 5. Fig. 6 shows a side view from left to right: Upper and lower adapter - transition from single-phase encapsulation to 3-phase encapsulation 3-phase encapsulated 8DN8 circuit-breaker Fig. 7: Top view of 8DN8-circuit-breaker with two adapters Fig. 7 shows the top view of the three-pole encapsulated 8DN8 circuit-breaker with indicated contact arrangement connected to the single-pole encapsulated adapters. Page 10 of 23

Fig. 8: Top view of contact arrangement Fig. 8 shows the contact arrangement of the adapter. Page 11 of 23

5 Retrofitting steps Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker Fig. 9 shows the typical design of a 8D bay with doublel-pressure circuit-breaker Fig. 10: Electrical view Legend: red= voltage, green: no voltage Page 12 of 23

Fig. 11: SF6 pressure view Legend: blue= air at atmospheric pressure; yellow= SF6 at rated pressure Views 10 and 11 show the second step of the retrofit 1) Switch off circuit -breaker -Q0 2) Switch off disconnectors -Q1, -Q2 and -Q8 3) Switch on and secure earthing switches -Q51 and -Q52 4) Switch off and earth the cable from the remote end 5) Switch off the auxiliary and tripping circuits 6) Perform gas work in accordance with diagram 7) Disassemble old circuit-breaker -Q0 with accessories 8) Check the existing 8D2 bushings and contacts 9) Install the new circuit-breaker with preassembled adapters 10) Install the new circuit-breaker module 11) Evacuate the new circuit-breaker module 12) Modify or replace the VOS (local control cubicle) 13) Top up SF6 to rated pressure 14) Commission the new circuit-breaker 15) Switch on the auxiliary and tripping circuits 16) Switch off the earthing switches -Q51, -Q52 and -Q8 and the earthing switch at the remote end of the cable. 17) Switch on disconnectors -Q1, -Q2 and -Q8 18) Switch on circuit-breaker -Q0 19) Bay is energized Figs. 12-18 show the individual steps of the retrofit graphically Page 13 of 23

Fig. 12: Third retrofitting step (a) Fig. 13: Third retrofitting step (b) Page 14 of 23

1,5 to SF6-Gas Scheme -Q52 -T5 -Q8 -Q0 -Q51 -Q9 -Q2 -Q1 -Z1 BB II BB I Fig. 14: Fourth retrofitting step (a) Fig. 15: Fourth retrofitting step (b) Page 15 of 23

Fig. 16: Fifth retrofitting step (a) Page 16 of 23

Fig. 17: Fifth retrofitting step (b) Page 17 of 23

1,5 to 4000 -Q52 -T5 -Q8 4050 5335 -Q0 -Q51 -Q9 -Q2 -Q1 -Z1 3000 1335 BB II BB I 1792 1115 1245 940 Fig. 18: Sixth retrofitting step: Bay after retrofitting Page 18 of 23

6 Circuit-breaker maintenance comparison old vs. new 8D1/2 Double -pressure circuitbreaker 8D2 Blast piston circuit-breaker 8DN8 Self compression circuit-breaker Minor inspection (or enhanced visual inspection) 1000 x CO in rated nominal current range or after 5 years 3000 x CO in rated nominal current range or after 10 years 3000 x CO in rated nominal current range or after 17 years Taking out of service necessary Replacement of blast valve Taking out of service necessary Taking out of service not necessary Major Inspection (or standard inspection) 5000 x CO in rated nominal current range or after 10 years Taking out of service necessary 6000 x CO in rated nominal current range or after 20 years Taking out of service necessary Replacement of blast valve Tab. 4 Comparison of the maintenance intervals of the different circuit-breakers 6000 x CO in rated nominal current range or after 25 years Taking out of service necessary Table 4 compares the maintenance intervals of the individual circuit-breaker types over a period of 25 years. It can be plainly seen that the maintenance expenditure as well as the short maintenance intervals for double-pressure circuit-breaker are no longer economical compared with the new 8DN8-circuit-breaker and no longer in keeping with today s needs. Fig. 19 shows the standardized maintenance costs (at today s costs) of the different circuit-breaker types over a 25-year operating period which naturally does not represent the whole life span of the new 8DN8 circuit-breaker. Compared to the new 8DN8-circuit-breaker the maintenance costs for the 8D1 double-pressure circuit-breaker are about 15 times higher, and the costs for the 8D2- blast piston circuit-breaker still 3 times as high. Page 19 of 23

Fig. 19: Standardized maintenance costs - blue: Double-pressure circuit-breaker 8D1/8D2 - red: Blast piston circuit-breaker 8D2 - yellow: Self compression circuit-breaker 8DN8 Page 20 of 23

7 Time schedule for retrofit solution The total duration from the receipt of the order to the provisional acceptance test is approximately 9 months referred to 1 bay. The actual retrofit, for example the dismantling of the existing circuitbreaker, installation of the new circuit-breaker, start-up and high voltage testing takes approximately 4 weeks. 8 Scope of delivery The scope of delivery comprises: Circuit-breaker 8DN8, 3-phase encapsulated, including supporting structure SF6 gas (2 x 40 kg bottles to ensure problem-free conversion); SF6 gas from the old 8D1/2 breaker is reused) 2 adapters from 3-phase encapsulated circuit-breaker to single-phase switchgear Small parts such as sealing material, filter material, etc. Control cubicle adaptation components or complete new control cubicle 9 Life time expectation of existing GIS without new circuit-breaker A life expectancy > 50 years is predicted for the remaining GIS components, provided that the Siemens maintenance recommendations have been followed as described in the operating manual. Tests on the gastight insulators of an over 40-year old 8D2 GIS did not show any discrepancies. The insulators did not produce any partial discharges. Naturally, if desired, a retrofit can be carried out on the existing disconnector and earthing switches. These devices can then be equipped with the latest motor drives. 10 Type tests Type tests are available for the retrofit 8DN8-circuit-breaker. Page 21 of 23

11 Options Local control cubicle, including control cable Service measures on the bays in conjunction with the planned retrofit Retrofitting of the disconnector / earthing switch drives with the latest generation of drives Overhaul of the dismantled 8D1/8D2 circuit-breaker Decentralized SF6 gas monitoring Replacement of old cast-resin voltage transformer with SF6-insulated transformer UHF antennas Page 22 of 23

Published by and copyright 2011: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Transmission and Distribution Services Humboldtstrasse 59 90459 Nuremberg, Germany For more information, please contact our Customer Support Center. Phone: +49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com Power Distribution Division Transmission and Distribution Services Order No. SE_AS_1010e_W3233-8D1D2Retrofit Printed in Germany Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. Page 23 of 23