TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

Similar documents
AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

SafeLink The Ultimate RMU. Rex de Bruyn PTMV New Zealand. ABB Ltd - Page 1 ABB

Gas Insulated Metal-clad Switchgear, HMGS!

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

33KV INDOOR SWITCHGEAR

NXPLUS C Single busbar. Maintenance-free for lifetime

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

PIX-H Metal-clad switchgear up to 17.5kV

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

MESG 12 / 17.5 / 24 / 36 KV

Extensible Unit - VCE2a

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

with Vacuum Circuit Breaker HAF

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

B kv T&D GAS INSULATED SWITCHGEAR

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

UniGear. Technical Guide

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

11 KV SF6 INSULATED RING MAIN UNIT WITH VACUUM CIRCUIT BREAKER. SYSTEM RATED VOLTAGE UP TO 12 kv

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

8DJ. Maintenance-free for lifetime

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

MEDIUM VOLTAGE SWITCHGEAR

SABRE VRN2a ENGINEERING BRILLIANT SOLUTIONS

Benefits, typical uses

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

Key features. DESIGNS: - Conservator type - Hermetically sealed

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Technical Specification of GECOL. Packaged Transformers

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

CBGS-0. Medium voltage distribution

Vacuum Circuit Breaker

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

B kv Gas-insulated Substations

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

EMPAC Metal enclosed capacitor bank for wind applications

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Air-insulated switchgear UniGear type ZS1

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR

Metal Clad VCBs ~ Mk1

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

ZX2.2 Gas-insulated medium voltage switchgear

Power IT Air Insulated Cubicle Uniswitch

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

045 : 2000 CEB STANDARD

the safe, reliable, and efficient choice for MV switchgear

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

Metal Clad Air Insulated Switchgear

CPG.0 Single busbar gas-insulated cubicles

Switchgear Type 8DJH 36 for Secondary

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus kv ABB

Typical Specification

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Unified requirements for systems with voltages above 1 kv up to 15 kv

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

Medium Voltage Metal-Enclosed Switches

Gas Insulated Switchgear

Metal Clad Switchgears

ZX-Family Gas-insulated medium voltage switchgear

FIXED VCB AIR INSULATED SWITCHGEAR

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

36kV Gas Insulated Medium Voltage Switchgear

SWITCHGEAR DIVISION PRODUCT PROFILES

Content. Uniswitch. 1. Design philosophy Applications Switchgear construction Cubicle types... 9

32-SDMS-02 SPECIFICATIONS FOR

32-SDMS-03 SPECIFICATIONS FOR

Transcription:

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop testing, inspection, packing, delivery to site, erection, testing and commissioning of 11 KV Metal Enclosed, panel type, extensible Indoor/ Outdoor SF6 RING MAIN UNIT (RMU) fully type tested according to IEC 60298 standards. This RMU should be complete with all components necessary for its effective and trouble free operation along with associated equipment etc. such components should be deemed to be within the scope of supplier s supply. The design of the switchgear should be exclusive and specific responsibility of supplier and should be comply with current good engineering practice, the relevant codes and recommendation, the project specific requirements. The RMU should be fixed type SF-6, insulated circuit breakers, with O/C & E/F relay for the protection of the transformer. It should be maintenance free equipment, having stainless steel robotically welded enclosure. 2 STANDARDS AND REFERENCE DOCUMENTS 2.1 Codes and Standards The RING MAIN UNIT (RMU) should be designed, manufactured and tested according to the latest version of: IEC 60694 Common specifications for high-voltage switchgear and control gear standards. IEC 60298: A.C metal-enclosed switchgear and control gear for rated voltages above 1KV and up to and including 72KV and the IEC Codes herein referred. IEC 60129: Alternating current Disconnector (isolators) and earthing switches IEC 60529: Classification of degrees of protection provided by enclosures IEC 60265: High-voltage switches-part 1: Switches for rated voltages above 1kV and less than 52 kv IEC 60056: Circuit breakers IEC 60420: High-voltage alternating current switch-fuse combinations IEC 60185: Current transformers IEC 60186: Voltage transformers IEC 60255: Electrical relays Page 1 of 14

MGVCL/PP/4027/RMU/ Any other codes recognised in the country of origin of equipment might be considered provided that they fully comply with IEC standards. The design of the switchgear should be based on safety to personnel and equipment during operation and maintenance, reliability of service, ease of maintenance, mechanical protection of equipment, interchangeability of equipment and ready addition of future loads. Silent Technical feature of SF-6 RMU. Offered 11KV SF6 / VCB INDOOR/ OUTDOOR, EXTENSIBLE, Ring Main Unit (RMU), comprising of 2 Nos. 630A Load break Switches, 1No. 200 A SF6 / VCB T OFF Circuit Breaker with O/C & E/F Relays. (A)Load break switch (630A) Load break switch should have the following - Manually operated 12 KV, 630A Load Break switch and Earthing Switch with making capacity - Live Cable LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. - Mechanical ON/OFF/EARTH Indication - Anti-reflex operating handle - Cable Testing facility without disconnecting the cable terminations, cable joints and terminal protectors on the bushings. Cable terminations - Cable boxes suitable for 1 X 3C x 300 sq mm XLPE Cable with right angle Cable Termination Protectors. (B) Circuit Breaker. (200A / 630A) Circuit Breaker should have the following: - Manually operated 200 A / 630A SF6 / Vacuum circuit breaker and Ear thing Switch with making capacity - Mechanical tripped on fault indicator - Auxiliary contacts 1NO and 1NC - Anti-reflex operating handle - Live Cable LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. - O/C + E/F self powered relay - Shunt Trip circuit for external trip signal - Mechanical ON/OFF/EARTH Indication - Cable boxes suitable for 1 X 3C x 300 sq mm XLPE Cable with right angle Cable Termination / protectors / boots Page 2 of 14

INDOOR RMU MGVCL/PP/4027/RMU/ 1. MODULAR DESIGN, PANEL TYPE WITH FRONT CABLE ACCESS. 2. RMU MUST BE MADE OF ROBOTICALLY WELDED STAINLESS STEEL. 3. Offered RMU must be extensible. OUT DOOR RMU 1. Hermetically sealed metallic Epoxy / Stainless steel enclosure for OUT DOOR RMU application. The manufacturers shall conform the normal current ratings mentioned in GTP at 45/50 deg. Ambient without derating or as per IEC Standard 2. Enclosure with I.P.54 standard protection. 3. Offered RMU must be extensible. 4. Cable boxes shall be on Front / side/rear sides. 5. Three way type, with two nos. of 630 Amp isolators and 200 Amp. T - off circuit breaker. 6 RMU ENCLOSURE MUST BE SHIELDED AGAINST SOLAR IRRADIATION AND TESTED FOR AMBIENT OF 45 / 50 DEGREE C. The manufacturers shall conform the normal current ratings mentioned in GTP at 50 deg. Ambient without derating. 2.1 DIELECTRIC MEDIUM SF6 / VCB GAS shall be used for the dielectric medium for 11KV/22KV RMUS in accordance with IEC376. It is preferable to fit an absorption material in the tank to absorb the moisture from the SF6 / VCB gas and to regenerate the SF6 / VCB gas following arc interruption. The SF6 / VCB insulating medium shall be constantly monitored via a temperature compensating gas pressure indicator offering a simple go, no-go indication. Page 3 of 14

2.2 GENERAL TECHNICAL REQUIREMENTS 2.2.1 Fixed type SF-6 gas insulated / Vacuum circuit breakers. It should be maintenance free, having stainless steel robotically welded enclosure for IN DOOR RMU & hermetically sealed metallic Epoxy / Stainless steel enclosure for OUT DOOR RMU application. However, offer with high quality of the welding which has necessary extensive leakage test with leak rate of 0.1% per annum can be accepted. The RMU use is only outdoor type. 2.2.2 Low gas pressure devices- 1.2 Bar pressure. RMU should have full rating with 0.0 Bar gas pressure. 2.2.3 Live cable indicators- High operator safety. 2.2.4 Fully Rated integral ear thing switch on each device. 2.2.5 Self powered Microprocessor Based relay- Does not require any external source of power. 2.2.6 Units fully SCADA Compatible. Retrofitting at site possible at a later date. Line switches (Load break switches) as well as T- OFF circuit Breaker can be operated by remote. 2.2.7 For indoor Cable boxes should be front access and interlocked with earth switch. No rear access required. For outdoor RMUs cable boxes shall be on sides/rear/front. 2.2.8 Cable testing possible without disconnection of cables. 2.2.9 Compact in dimension. 2.2.10 Circuit Breaker with self powered O/C & E/F RELAY. 2.2.11 Low pressure, sealed for life equipment, can operate at 0 bar pressure. 2.2.12 Cable ear thing switch on all switching device-standard, for operator safety. 2.2.13 Enclosure with IP 54 standard protection for OUTDOOR RMUs and IP2X for INDOOR RMUs 2.2.14 All live parts should be inside a hermetically sealed metalised Epoxy enclosure / stainless steel enclosure for out door type RMU & 3mm stainless steel robotically welded enclosure for indoor RMU. Page 4 of 14

2.3 TECHNICAL AND GUARANTEED PARTICULARS. The bidders shall furnish all guaranteed technical particulars as called for in Schedule A of this specification. Particulars which are subject to guarantee shall be clearly marked. Bids lacking information in G.T.P are liable to be rejected. 3 DESIGN CRITERIA 3.1 Service conditions The offered switchgear and control gear should be suitable for continuous operation under the basic service conditions indicated below. Installation should be in normal indoor conditions in accordance with IEC 60694. Ambient temperature -1 o C to +45 o C Relative humidity up to 95% Altitude of installation up to 1000m, IEC 60120 3.2 General structural and mechanical construction The offered RMU should be of the fully arc proof metal enclosed, free standing, floor mounting, flush fronted type, consisting of modules assembled into one or more units. Each unit is made of a cubicle sealed-for life with SF6 / VCB and contains all high voltage components sealed off from the environment. The overall design of the indoor switchgear should be such that front access only is required. It should be possible to erect the switchboard against a substation wall, with HV and LV cables being terminated and accessible from the front. The units should be constructed from 3 mm thick stainless steel sheets. However, Offer with type test report of pressure withstand test for gas filled compartment with pressure relief device test as per cl. no. 6-103-1 of IEC 62271-200-2003 can be accepted for 2mm stainless steel tank thickness. The design of the units should be such that no permanent or harmful distortion occurs either when being lifted by eyebolts or when moved into position by rollers. For outdoor RMUs a weather proofing process shall be carried out. SHEET METAL MUST BE GRIT BLASED / THERMALLY SPRAYED AND POLYURETHANE PAINTED WITH ABOUT 70 MICRON THICKNESSES, TO ACHIVE OUTDOOR WORTHINESS AND CORROSION PROOF NESS. - RMU ENCLOSURE MUST BE SHIELDED AGAINST SOLAR IRRADIATION AND TESTED FOR A AMBIENT OF 45 / 50 DEGREE C WITHOUT DERATING OF THE EQUIPMENT. The cubicle should be have a pressure relief device. In the rare case of an internal arc, the high pressure caused by the arc will release it, and the hot gases is allowed to be Page 5 of 14

exhausted out at the bottom / top / rear of the cubicle. A controlled direction of flow of the hot gas should be achieved. The switchgear should have the minimum degree of protection (in accordance with IEC 60529) - IP 67 for the tank with high voltage components - IP 2X for the front covers of the mechanism - IP 3X for the cable connection covers - IP 54 for the outdoor enclosure. 4.0 TECHNICAL DATA 4.1 Ring Main Unit, Electrical data Electrical data and service conditions No Rated voltage KV 12/15.5KV 1 Power frequency withstand voltage KV 28 / 35 2 Impulse withstand voltage KV 75 / 95 3 Rated frequency Hz 50/ 4 Rated current busbars A 630 5 Rated current (cable switch) A 630 6 Rated current (T-off) A 200 / 630 Breaking capacities: 7 active load A 630 8 closed loop (cable switch) A 630 9 off load cable charging (cable switch) A 135 10 earth fault (cable switch) A 200 11 earth fault cable charging (cable switch) 115 12 short circuit breaking current (T-off circuit breaker) ka 20 / 21 13 Rated making capacity ka 52 14 Rated short time current 3 sec. ka 20 / 21 Ambient temperature: 15 Maximum value C + 50 16 Maximum value of 24 hour mean C + 35 17 Minimum value C 0 18 Altitude for erection above sea level4 m...1000 19 Relative humidity Max 95% Page 6 of 14

4.2 Ring Main Unit Technical data (11KV/22KV) No. General data, enclosure and dimensions 1 Standard to which Switchgear complies IEC 2 Type of Ring Main Unit Metal Enclosed, Panel type, Compact Module. 3 Number of phases 3 4 Whether RMU is type tested Yes 5 Whether facility is provided with pressure relief Yes 6 Insulating gas SF6 7 Nominal operating gas pressure 1.4 bar @ 20 C. However offer with Nominal operating gas pressure shall be as per manufacturer standard and suitable to satisfy the rated dielectric strength can be accepted 8 Gas leakage rate / annum % 0,075 9 Expected operating lifetime 30 years 10 Whether facilities are provided for gas Yes, temperature monitoring compensated manometer can be delivered 11 Material used in tank construction Stainless steel sheet, 3 mm / metallised cast resin No Operations, degree of protection and colours 1 Means of switch operation separate handle 2 Means circuit breaker operation separate handle and push buttons 3 Rated operating sequence of Circuit Breaker O 3min-CO-3min- CO 4 Total opening time of Circuit Breaker approx. 45ms 5 Closing time of Circuit Breaker approx. 40ms 6 Mechanical operations of switch CO 1000 Page 7 of 14

7 Mechanical operations of CO earthing switch 1000 8 Mechanical operations of circuit breaker CO 2000 9 Principle switch / earth switch 3position combined switch / earth switch Degree of protection: 10 High Voltage live parts, SF6 / VCB tank IP 67 11 Front cover mechanism IP 2X 12 Cable covers IP 3X 13 Outdoor Enclosure IP 54 Colours: 14 Front cover 15 Side and cable cover 5.0 PANEL (MODULE) DESCRIPTION 5.1.1 Incoming cable module It should be consist of an SF6 cubicle housing a switch disconnector and an ear thing switch. Bus bars and all electrical connections are located inside the tank. The operating shafts for the switches should be have rotary seals where they enter the SF6 cubicle. The operating mechanisms should be located outside on the front of the SF6 tank. Cable bushings should be located on the front of the SF6 cubicle in a separate cable compartment. Front covers containing the mimic diagram and having a degree of protection IP2XC close the fronts. 5.1.2 The T-off circuit breaker module (200 A) The T-off circuit breaker module should be consist of an SF6 cubicle housing a circuit breaker unit and a disconnector- ear thing switch. An integrated relay and related CTs is used for tripping of the circuit breaker. Bus bars and all electrical connections should be located inside the tank. The operating shafts for the switches should be have rotary seals where they enter the SF6 cubicle. The operating mechanisms are located outside on the front of the SF6 B tank. Cable bushings should be located on the front of the SF6 cubicle in a separate cable compartment. Front covers containing the mimic diagram having a degree of protection IP2XC seal off the fronts. 6 CIRCUIT BREAKERS SF-6 / Vacuum bottles should be use as interrupters of the currents. The circuit breaker main circuit should be connected in series with a three-position disconnector ear thing Page 8 of 14

switch. The operation between circuit breaker and disconnector earthing must be interlocked. 1. SF6 / VCB BREAKER must SELF -TRIPPING AND HAS A SELF POWERED RELAY Switch on to fault condition relay does not specify operation of O/C or Fault, so it should be visible indication. 2. THE RMU MUST BE EXTENSIBLE TYPE 7 OTHER MAIN FEATURES 7.1 Bus bars Comprising the 3 single phases copper bus bars and the connections to the switch or circuit breaker. The bus bar should be integrated in the cubicle Bus bars should be rated to withstand all dynamic and thermal stresses for the full length of the switchgear. 7.2 The cable switch It should be a switch-disconnector and ear thing switch using SF6 / VCB gas as an arcquenching medium. The switch positions are closed open earthed. In the open position the switch satisfies the disconnector requirements. 7.3 Earthing Switch Ear thing switches should be rated equal to the switchgear rating. Ear thing switches should be quick make type capable of making Rated Fault Current. Ear thing switch should be operated from the front of the cubicle by means of a removable handle. 7.4 The mechanisms All mechanisms should be situated in the mechanism compartment behind the front covers outside the SF6 / VCB-tank. The mechanism for the switch and the ear thing switch is operating both switches via one common shaft. The mechanism provide independent manual operation for closing and opening of the switch, independent closing of the ear thing switch and dependent opening of the ear thing switch. The mechanism for the T-off switch and ear thing switch is operating both switches via one common shaft. The mechanism has stored spring energy and provide independent manual Page 9 of 14

operation for closing and opening of the switch, independent closing of the ear thing switch and dependent opening of the ear thing switch. The mechanism has fuse- tripping device. The mechanism for the vacuum circuit breaker (VCB) and disconnector- earthing switch is operating the VCB and the disconnector earthing switch via to separate shafts. The mechanism for the VCB has stored spring energy and provides independent manual operation for closing and opening of the VCB. The mechanism has a relay with related CT s and/or remote tripping device. The mechanism for the disconnector earthing switch provide independent manual operation for closing and opening of the disconnector, independent closing of the earthing switch and dependent opening of the earthing switch. 7.5 Front covers The front cover contains the mimic diagram of the main circuit with the position indicators for the switching devices. The voltage indicators are situated on the front panels. Access to the cable bushings is in the lower part of each module. 7.6 Position indicators The position indicators are visible through the front cover and are directly linked to the operating shaft of the switching devices. 7.7 Voltage indicator The voltage indicators are situated on the front cover, one for each module, and indicate the voltage condition of each incoming cable. Identification of the phases is achieved with labels L1, L2 and L3 on the front of the voltage indicators. The voltage indicator satisfies the requirements of IEC61243. 7.8 Cable compartment It should be possible to terminate up to a maximum of two single core HV cables per phase. The access to the compartment will be possible by removing the cable cover, bolted to the main frame. Removable steel covers close the cable compartments. Arc proof cable covers should be available as option. Each module has a separate cable compartment that is segregated from each other by means of a partition wall. A partition wall should be fitted to divide the cable compartment from the rear side of the switchgear. In case of an arc inside the tank, followed by the opening of the pressure relief, the partition wall prevents the hot gases flowing out from the pressure relief to enter the cable compartments. All covers are removable. The ground continuity is achieved when the covers are in place by means of bolted connections. Page 10 of 14

7.9. Power connection. MGVCL/PP/4027/RMU/ The cables are installed in the dedicated compartment below the mimic front cover. At the bottom of the cable compartment, an earthing bar system made of copper with a minimum cross section of 120 mm2 should be fitted. In each compartment the earthing bar should be fitted with 4 screws M10. The earthing system is connected to the tank by a copper bar, which rises up to the connecting point of the tank behind the rear partition wall on the middle of the switchgear. However offer for manufacture to ensure the continuity of earthing switch up to the earth connecting points through suitable copper earthing bus can be accepted. 7.10 INTERLOCKING. The mechanism for the cable switch should be provide a built in interlocking system to prevent operation of the switch when the earthing switch is closed, and to prevent operation of the earthing switch when the switch is in the closed position. The mechanism for the T-off switch should be provide a built in interlocking system to prevent operation of the switch when the earthing switch is closed, and to prevent operation of the earthing switch when the switch is in the closed position. In addition an interlocking device allows access to the fuses only when the earthing switch is in the earthed position and opening of the earthing switch is only possible when the fuse cover is closed and secured. The mechanism for the VCB and the disconnector-earthing switch should be have a built in interlocking system to prevent operation of the disconnector-earthing switch when the VCB is in the closed position. 7.11 Optional equipment. 7.11.1 Current Transformers All current transformers should be comply with IEC 60185. Current transformers should be of dry type, with ratings and ratios as required. Cable current transformers used in circuit breaker modules should be maximum 100mm wide. Current transformers used for metering should be having dimensions according to DIN 42600, Narrow type. 7.12.2 Auxiliaries. The switchgear should be prepared for options like motor operation, auxiliary contacts and short-circuit indicators. Necessary terminal blocks and wiring etc. should be placed behind the front cover of each module. Page 11 of 14

7.12.3 Fault Passage Indicators. Each RMU shall be equipped to display the phase currents on feeder circuit. Each RMU shall be provided with one no. fault passage indicator on the isolator to indicate the earth fault. This shall facilitate quick detection of faulty section of line. The unit should be self-contained requiring no auxiliary power supply and shall be an integral part of the RMU to avoid any thefts. The fault shall be displayed by means of LED indication / flag which can be reset with three options viz. manual / on restoration of supply / settable time. 8 TESTING AND CERTIFICATION. 8.1 TYPE TESTS. Units should be type tested in accordance with IEC standards 60056, 60129, 60265, 60298,60420,60529 and 60694. The following type tests have been performed and available if required - Short time and peak withstand current test - Temperature rise tests. - Dielectric tests. - Test of apparatus i.e. circuit breaker and earthing switch - Arc fault test - Measurement of resistance of main circuit. - Mechanical endurance test. - Duty cycle test. - Internal arc test for HT chamber. - Degree of protection for IP 54 for OUT DOOR and IP2X for INDOOR RMU. Type test reports for above type shall be submitted with the offer. 8.2 ROUTINE TESTS. Routine tests should be carried out in accordance with IEC 60298 standards. These tests should be ensure the reliability of the unit. Below listed test should be performed as routine tests before the delivery of units; - Withstand voltage at power frequency - Measurement of the resistance of the main circuit - Gas leakage test - Withstand voltage on the auxiliary circuits - Operation of functional locks, interlocks, signalling devices and auxiliary devices - Suitability and correct operation of protections, control instruments and electrical connections of the circuit breaker operating mechanism - Verification of wiring - Visual inspection Page 12 of 14

9.0 Guarantee Period. MGVCL/PP/4027/RMU/ Guarantee period of RMU shall be 60 months from the date of success fully installation / commission of both type of RMU. If RMU fails during this guarantee period, the supplier shall have to repair/replaced the same at the cost of supplier at site / their works within 48 hours. 10.0 DOCUMENTATION. An instruction manual should be provided with necessary information for receiving, handling, storage, installation, operation and maintenance. Routine test certificate should be follow each unit, and standard schematic drawings should be delivered for Ring Main Units. Compact Switchgear should be have drawings that consist of system single line drawings, general arrangement and schematic drawings for order specific units. All drawings shall confirm to International Standards Organization (ISO) A series of drawing sheets/indian Standards Specification IS : 11065. All dimensions and data shall be in ink and suitable for microfilming. All dimensions and data shall be in S.I. Units. 11.0 List of drawings and Documents. The bidder shall furnish four sets of relevant descriptive and illustrartive published literature, pamphlets and the following drawings for preliminary study along with offer. General outline drawings showing dimensions and shipping weights, quantity of insulating media. Sectional views showing the general constructional features of the circuit breaker including operating mechanism, arcing chambers, contacts with lifting dimensions for maintenance. Drawings showing control cabinets and circuit diagrams for operating mechanism. Schematic diagrams of breaker offered for control, supervision and auto reclosing. Structural drawings and loading data for support structures. Foundation plan and loading data and foundation design. Drawings showing the complete operation cycle of the RING MAIN UNIT with description. NAME PLATE: Each RMU and its associated equipment s shall be provided with following information. a) Name of manufacturer. b) Type, design and serial number c) Rated voltage and current d) Rated frequency e) Rated symmetrical breaking capacity f) Rated making capacity Page 13 of 14

Note: MGVCL/PP/4027/RMU/ g) Rated short time current and its duration h) Purchase Order number and date i) Month and year of supply j) Rated lighting impulse withstand voltage i) The word rated need not appear on the name plate. Recognized abbreviations may be used to express the above particulars. ii) Whether the circuit breaker is fitted with closing/tripping devices necessitating an auxiliary supply shall be stated either on the circuit breaker name plate or any other acceptable position. 12.0 TRAINING: Installation of the switchgear should be required no special tools. Optional product training should be available at the manufactures facility. Page 14 of 14