E J-Series Electric quarterturn / partturn actuators ASC Armaturen GmbH - D 97 Popelau phone.: +49/884/68-0 Fax: +49/884/68- e-mail: info@ascarmaturen.de www.ascarmaturen.de ISO-Interface Optical function indicator Emergency manual override and Optical position indication DIN electric connectors
E J-Series The consequent and further development of Best of Class EJ With the new EJ, the actual and very sucessful series of electric actuators from $6& $UPDWUHQ were now made even more powerful. A lot of additional technical features packed in a very attractive and modern designed housing make the ASC actuators quite more comfortable. As an clear example we point out the LED on the upper side of the case which indicates the function status at a glance: not only the initiation of the torque limiter but the actual function status of the actuator. The new models 5 and 85 complete the extended product range enabling a very exact selection of the correct torque and actuator for the torque range of the different valves up to 85 Nm, and thus optimizing the cost of automation. For higher torques up to 00 Nm we still offer the models 40 and 00 from Series EJ (see pages 4 and 5). Standard features and equipment from Series EJ were optimized and are integrated part of the Series EJ, which are the following: ETL : Electronic Torque Limiter this new electronic device prevents damagedamage to the valve and actuator when exceeding the maximum torque. AVS : Automatic Voltage Sensing With only two voltage series all possible voltages are covered fully automatically and without the need of complicated configurations! Operation torques and times are equal irrespective to the voltage modus. ATC : Automatic Temperature Control Ambient heater all inclusive! If no external energy supply cut occurs this thermostatically controlled heater prevents condesation. Mechanical Deblocking: In case of actuation of the torque limiter device or reaching the end positions the gear will be auto-relaxed (reverse movement) thus enabling the change from Automatic to Manual Operation, maintaining the self-locking function of the actuator. robust, corrosion and breaking-resistant polyamide housing. considerable stiffness (auto-stoppage) manual emergency override disconnecting the motor electronically limit switches for motor-control, limit switches for position indication
E J -Series Product Range Please refer to page 4 for the models 40 and 00 of E J -Series Model 0 5 55 85 Voltage range L 4V AC/DC 4V AC/DC 4V AC/DC 4V AC/DC [-0%/+5%] Voltage range H [+/-5%] Operating time ( s/90 ) [+/-0%] Break torque 85-40V AC/DC 85-40V AC/DC 85-40V AC/DC 85-40V AC/DC L : s / H : s L : s / H : s L : 7 s / H : s L : s / H : s 5 Nm 8 Nm 60 Nm 90 Nm Operational torque Duty rating [ED] 0 Nm 5 Nm 55 Nm 85 Nm 75% 75% 75% 75% Protection class IP65 IP65 IP65 IP65 Temperature range ISO-Flange F0/F04/F05 F0/F04/F05 F05/F07 F05/F07 Double square alternatives Connectors Torque limiter Heater Enclosure / housing 9 mm, mm 9 mm, mm or 4 mm or 4 mm DIN 4650 DIN 4650 DIN 4650 DIN 4650 ISO 4400 ISO 4400 ISO 4400 ISO 4400 C-9/C-9 C-9/C-9 C-9/C-9 C-9/C-9 Nylon (PA 6) 4 mm 4 mm or 7 mm or 7 mm Weight,4 kg,7 kg, kg,8 kg Optional equipment Turn angle 0-80, 0-90 -80 (other angles possible), Potentiometer (version K, 5K or 0K), Safety Battery Block/BSR, Digital positioning system/dps (either 0-0V or 4-0mA, input-output)
E J -Series Electric actuator Model EJ 0 Compact actuator for regulation and control of valves interface according ISO 5/DIN 7. (L=Low voltage range, H=High voltage range) Voltage ranges : L (-0%/+5%) (lower voltage range) H (+/-5%) (upper voltage range) Operating time s/90 (+/-0%): 4V AC/ DC 85-40 V AC/DC s Break torque : 5 Nm Operational torque : 0 Nm Duty rating [ED]: 75% Protection class : IP65 Temperature range : Flange: Double square alternatives Connectors: Enclosure/housing: Weight :,4 kg Multiflange F0/F04/F05 9, or 4 mm DIN 4650 ISO 4400 C-9/C-9 Nylon (PA 6) All advantages at glance: ETL (electronic torque limiter) AVS (automatic voltage sensing) ATC (automatic temperature control) integrated heater to prevent condensation mechanical deblocking manual override for emergency operation two addional pontential free contacts for remote position indication Additonal optional equipment Different operation angles 0º-80, 0º-90º-80º (other angles possible), potentiometer (alternatively K, 5K or 0K), Emergency-Batterypack/BSR, electronic positioning system DPS (either 0-0V or 4-0mA, input-output) 4
E J -Series Electric actuator Model EJ 0 4 0 9 x 9 x 4 x 4 6 50 4 49 6 5 77 55 55 Please consider our wide range of optional equipment. N/ L/ EJ Standard AC/DC Wire connection diagram EJ Standard alternativ Plug Plug 5
E J -Series Electric actuator Model EJ 5 Compact actuator for regulation and control of valves interface according ISO 5/DIN 7. (L=Low voltage range, H=High voltage range) Voltage ranges : L (-0%/+5%) (lower voltage range) H (+/-5%) (upper voltage range) Operating time s/90 (+/-0%): Break torque : 8 Nm Operational torque : 5 Nm Duty rating [ED]: 75% Protection class : IP65 Temperature range: Flange: Double square alternatives Connectors: Enclosure/housing: Weight :,7 kg 4V AC/ DC 85-40 V AC/DC L : s / H : s Multiflange F0/F04/F05 9, or 4 mm DIN 4650 ISO 4400 C-9/C-9 Nylon (PA 6) All advantages at glance: ETL (electronic torque limiter) AVS (automatic voltage sensing) ATC (automatic temperature control) integrated heater to prevent condensation mechanical deblocking manual override for emergency operation two addional pontential free contacts for remote position indication Additonal optional equipment Different operation angles 0º-80, 0º-90º-80º (other angles possible), potentiometer (alternatively K, 5K or 0K), Emergency-Batterypack/BSR, electronic positioning system DPS (either 0-0V or 4-0mA, input-output) 6
E J -Series Electric actuator Model EJ 5 4 0 9 x 9 x 4 x 4 6 50 4 7 6 5 77 55 55 Please consider our wide range of optional equipment. N/ L/ EJ Standard AC/DC Wire connection diagram EJ Standard alternativ Plug Plug 7
E J -Series Electric actuator Model EJ 55 Compact actuator for regulation and control of valves interface according ISO 5/DIN 7. (L=Low voltage range, H=High voltage range) Voltage ranges : L (-0%/+5%) (lower voltage range) H (+/-5%) (upper voltage range) Operating time s/90 (+/-0%): Break torque : Operational torque : Duty rating [ED]: Protection class : Temperature range : Flange: Double square alternatives Connectors: Enclosure/housing: Weight : 4V AC/ DC 85-40 V AC/DC L : 7 s / H : s 60 Nm 55 Nm 75% IP65 F05/F07 4 or 7 mm DIN 4650 ISO 4400 C-9/C-9 Nylon (PA 6), kg All advantages at glance: ETL (electronic torque limiter) AVS (automatic voltage sensing) ATC (automatic temperature control) integrated heater to prevent condensation mechanical deblocking manual override for emergency operation two addional pontential free contacts for remote position indication Additonal optional equipment Different operation angles 0º-80, 0º-90º-80º (other angles possible), potentiometer (alternatively K, 5K or 0K), Emergency-Batterypack/BSR, electronic positioning system DPS (either 0-0V or 4-0mA, input-output)
Electric actuator Model EJ 55 E J -Series 4xM8 0 4/7 4xM6 50 70 4 96 6/9 6 5 77 55 55 Please consider our wide range of optional equipment. EJ Standard AC/DC Wire connection diagram EJ Standard alternativ N/ L/ Plug Plug 9
E J -Series Electric actuator Model EJ 85 Compact actuator for regulation and control of valves interface according ISO 5/DIN 7. (L=Low voltage range, H=High voltage range) Voltage ranges : L (-0%/+5%) (lower voltage range) H (+/-5%) (upper voltage range) Operating time s/90 (+/-0%): Break torque : Operational torque : Duty rating [ED]: Protection class : Temperature range : Flange: Double square alternatives Connectors: Enclosure/housing: Weight : 4V AC/ DC 85-40 V AC/DC L : s / H : s 90 Nm 85 Nm 75% IP65 F05/F07 4 or 7 mm DIN 4650 ISO 4400 C-9/C-9 Nylon (PA 6),8 kg All advantages at glance: ETL (electronic torque limiter) AVS (automatic voltage sensing) ATC (automatic temperature control) integrated heater to prevent condensation mechanical deblocking manual override for emergency operation two addional pontential free contacts for remote position indication Additonal optional equipment Different operation angles 0º-80, 0º-90º-80º (other angles possible), potentiometer (alternatively K, 5K or 0K), Emergency-Batterypack/BSR, electronic positioning system DPS (either 0-0V or 4-0mA, input-output)
E J -Serie Electric actuator Model EJ 85 4xM8 0 4/7 4xM6 50 70 4 6/9 96 6 77 5 7 55 Please consider our wide range of optional equipment. EJ Standard AC/DC Wire connection diagram EJ Standard alternativ N/ L/ Plug Plug
E J -Series Electric actuators E J -Serie Compact actuator for regulation and control of valves interface according ISO 5/DIN 7. (L=Low voltage range, H=High voltage range) Model EJ40 EJ00 Voltage ranges : L (-0%/+5%) (lower voltage range) H (+/-5%) (upper voltage range) 5-4V AC/ 4 85-40 V AC/DC Operating time s/90 (+/-0%): L : s / H: 0 s L : 66 s / H: 60 s Break torque : 70 Nm 50 Nm Operational torque : 40 Nm 00 Nm Duty rating [ED]: Protection class : Temperature range : Flange: 75% IP65 F07/F0 Double square alternatives mm Connectors: DIN 4650 ISO 4400 C-9 Enclosure/housing: Nylon (PA 6) Weight : 5, kg All advantages at glance: ETL (electronic torque limiter) AVS (automatic voltage sensing) ATC (automatic temperature control) integrated heater to prevent condensation mechanical deblocking manual override for emergency operation two addional pontential free contacts for remote position indication Additonal optional equipment Different operation angles 0º-80, 0º-90º-80º (other angles possible), potentiometer (alternatively K, 5K or 0K), Emergency-Batterypack/BSR, electronic positioning system DPS (either 0-0V or 4-0mA, input-output)
POWER POS. E.L.S E J -Series Electric actuators E J Model 40/00 0 4xM0 4xM8 4 7/ 70 mpm 4 54 AUTO MAN 8 5 07 0/4/6 N/ L/ EJ Standard AC/DC Wire connection diagram EJ Standard alternativ Plug Plug
E J -Series Additional equipments Models with Emergency Battery Pack (BSR) The special feature of the J Series: The Battery Pack for emergency operation is integrated in the housing. In order to guarantee the proper function of the installed actuators in case of loss of the energy supply the actuators of the J Series can be equiped with the emergency battery pack (BSR). This device enables the customer to operate into the desired position without external power supply. Beeing an emergency operation device it is not design as continious power supply for standard operation. All advantajes at a glance: automatic re-positioning at power-blackout free selection of the security position: NC / NO short charging time enables immediate response long endurance and lifespan due to modern accumulator technology N E W EJ With internal integrated Emergency Battery Pack Charging current: 00 ma Weight of Emergency Battery Pack (BSR): Standard-actuator + 0, Kg of BSR. Charging time after an emergency operation Model 0 and 5: 8 min. Charging time after an emergency operation Model 55 and 85: 0 min. EJ Comparision with external Emergency Battery Pack N/ L/ EJ with Emergency Battery Pack AC/DC Wire connection diagram EJ with Emergency Battery Pack alternativ Plug Plug
E J -Series Models with Potentiometer The potentiometer in the actuator indicates the position of it as linear value of the resistance which is beeing evaluated by an internal device controlling the operation accordingly. The following three executions of potentiometers are available: KOhm, 5KOhm or 0KOhm. If other values are required please contact your nearest ASC Armaturen distributor. Because of the fact that later changes are not possible any more, the exact value of the potentiometer has to be given at the time of order. EJ with Potentiometer AC/DC Wire connection diagram EJ with Potentiometer alternativ N / L / Plug Plug Plug Plug Models with Positioner DPS 005 Alternatively 0-0V or 4-0mA (input and output signal) The DPS005 electronic positioner converts the actuators into servo-controlled control device for valves. Through the input signal of the DPS 005 it is possible to position the actuator at any angle of desplacement. The output-signal is completely proportional to the actual position of the valve. The DPS 005 Module controls trough an integrated internal micro-processor (CPU) the analog input-and output signal (4-0mA or 0-0V) and compares it with the position of the actuator. The sensivity and repetiveness are guaranteed by means of a continous comparision of the analog input signals executed by the CPU. Class B+C according E DIN EN 574 Inching+Modulation EJ with DPS 005 AC/DC Wire connection diagram EJ with DPS 005 alternativ N / L / + output + output Plug + input Plug - Plug + input Plug -