GETTING STARTED GUIDE NI DI, ±5 V to 24 V, Differential/Single-Ended, 500 ns

Similar documents
GETTING STARTED GUIDE NI AI, ±10 V, 12 Bit, 500 ks/s Aggregate

GETTING STARTED GUIDE NI AI, ±10 V, 16 Bit, 1 MS/s/ch Simultaneous

NI 9251 with mini XLR

GETTING STARTED GUIDE NI Channel Sinking Digital Input Module

GETTING STARTED GUIDE NI AO, ±10 V, 16 Bit, 25 ks/s/ch Simultaneous

GETTING STARTED GUIDE NI DO, 6 V to 30 V, Sourcing, 100 μs

GETTING STARTED GUIDE NI DO, 5 V to 30 V, Sourcing, 1 μs

GETTING STARTED GUIDE NI AI/1 Neutral, 400 Vrms L-N/690 Vrms L-L, 24 Bit, 50 ks/s/ch Simultaneous

GETTING STARTED GUIDE NI AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate

GETTING STARTED GUIDE NI AI, 51.2 ks/s/ch Simultaneous, Universal Measurements

SAFETY INFORMATION & INSTALLATION GUIDE RMX Programmable Power Supplies. About the RMX Safety Information & Installation Guide

CALIBRATION PROCEDURE NI Channel, ±0.5 V, 24-Bit Simultaneous, Channel-to-Channel Isolated Analog Input Module

Bracket and Assembly Dimensions

NI Pin DSUB to Screw-Terminal Connector Block

CALIBRATION PROCEDURE NI Channel, ±10 V, 16-Bit Analog Voltage Output Module

Industrial Rack Mount Kit for CompactRIO and CompactDAQ

Contents. Software. CALIBRATION PROCEDURE NI PXIe Ch, 24-bit, 25.6 ks/s Universal Bridge Input Module. ni.com/manuals

Shielded Connector Block for the NI PXI/PXIe-2532/2532B

INSTALLATION GUIDE NI WSN-3291 Outdoor IP Enclosure For NI WSN-32xx Series Devices

INSTALLATION GUIDE NI 9921/9922 Outdoor IP Enclosure For NI WLS-9000 Series Devices

NI PS-15/16/17 Side Mount Brackets

NI TB Introduction INSTALLATION INSTRUCTIONS. Terminal Block for the NI PXI/PXIe-2527

SCXI Power Supply/Float Charger Installation Guide

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS

F5 Platforms: FIPS Kit Installation MAN

362 Clamp Meter. Users Manual

Megohmmeter Test Probe

BroadBand PowerShield. 20 AHr Battery. User Manual

Solenoid coil for control in potentially explosive areas Type BZ

PF 3100 ION PILOT CARD PRO.FIRE

i3000s/i2000 Flex AC Current Probe

Solenoid Operator 0516 / 1216

323/324/325 Clamp Meter

Ø 68 mm to ø 115 mm. Material: Weight: Bearing Life: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating:

Type 2REX-A. Oil & Gas / Heavy Industry

2-Year Limited Warranty. See the Users Manual for the full warranty.

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

707Ex. Users Manual. ma Calibrator

1587 FC/1587/1577. Insulation Multimeter. Safety Information. Warnings

Installation Instructions

Ø 68 mm to ø 115 mm. Material: Weight: Shaft Loads: Enclosure Rating: Connection Options. Cable: Cable Glands:

Solenoid Operator 0513 / 1213

1100 Series Piston Type Differential Pressure Gauges

373 Clamp Meter. Users Manual

365 Detachable Jaw True-rms Clamp Meter


0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

650mA Phase Dimmable LED Driver

EStrong-series Emergency Stop

INTERNATIONAL METAL ENGINEERING

Safety Standards. Model Number:

Control Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

Leica GKL341 User Manual. Version 1.0 EN

CONTROL MICROSYSTEMS Power Supply. Hardware Manual

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

CPC DX (CPC Dual Transfer Skid) Redundant current to pressure converter assembly

- Wiring Brochure Mixing Expansion Module 440

DALI 650mA LED Driver

Material: Weight: Shaft Loads: Enclosure Rating: Cable: Cable Glands:

1000mA - 650mA Phase Dimmable LED Driver

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

Automatic Pressure Calibrator. 3-Year Limited Warranty. See the Users Manual for the full warranty.

ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c.

362 Clamp Meter. Users Manual

A419ABG-3C Electronic Temperature Control

INSTALLATION INSTRUCTIONS

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

Model Fixed Rack-Mount Kit

80 Series V Digital Multimeter Safety Information

Applications. Overview. Technical Specifications

Phase Sequence Tester

Electrical Installation

BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet

L(+) SV1 N(-) NC. Terminal Block Connections L (+) N (-) SV1 K2 K1. Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Temposonics. Magnetostrictive Linear Position Sensors. TH Analog Data Sheet

WF3132 User s Manual. AC rev D

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

HIGH VOLTAGE DIGITAL AMMETER

Technical Data. Dimensions

F261 Series Fluid Flow Switches

Powerware Vdc Extended Battery Cabinet User s Guide.

Temposonics. Magnetostrictive Linear Position Sensors. TH Analog SIL 2 capable Data Sheet

Mini Multimeter with Non-Contact Voltage Detector (NCV)

POWERWARE User s Guide VA.

1000 Series Piston Type Differential Pressure Gauges

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

Ex m Solenoid Operator Type 0519

Differential pressure gauge with output signal With integrated working pressure indication (DELTA-trans) Model DPGT40

Tina 4A Connection block

302+/303 Clamp Meter. Users Manual

EU RO Mutual Recognition Technical Requirements

VA-7450 Series. Electric Valve Actuators

Temposonics. Magnetostrictive Linear Position Sensors. TH CANbus Data Sheet

BMRX Series ROTARY LEVEL CONTROL

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Safety and General Information

MINI MCR-SL-UI-UI(-SP)(-NC)

Transcription:

GETTING STARTED GUIDE NI 9411 6 DI, ±5 V to 24 V, Differential/Single-Ended, 500 ns

This document explains how to connect to the NI 9411. Note Before you begin, complete the software and hardware installation procedures in your chassis documentation. Note The guidelines in this document are specific to the NI 9411. The other components in the system might not meet the same safety ratings. Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system. Safety Guidelines Operate the NI 9411 only as described in this document. Caution Do not operate the NI 9411 in a manner not specified in this document. Product misuse can result in a hazard. You can compromise the safety protection built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair. 2 ni.com NI 9411 Getting Started Guide

Safety Voltages Connect only voltages that are within the following limits. Channel-to- or Vsup-to- Isolation Channel-to-channel Channel-to-earth ground Continuous Withstand 30 V maximum, Measurement Category I None 30 Vrms, 42.4 Vpk, 60 VDC 400 Vrms, verified by a 5 s dielectric withstand test Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics. NI 9411 Getting Started Guide National Instruments 3

Caution Do not connect the NI 9411 to signals or use for measurements within Measurement Categories II, III, or IV. Note Measurement Categories CAT I and CAT O are equivalent. These test and measurement circuits are not intended for direct connection to the MAINS building installations of Measurement Categories CAT II, CAT III, or CAT IV. Safety Guidelines for Hazardous Locations The NI 9411 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx na IIC T4 and Ex na IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the NI 9411 in a potentially explosive environment. Not following these guidelines may result in serious injury or death. Caution Do not disconnect I/O-side wires or connectors unless power has been switched off or the area is known to be nonhazardous. 4 ni.com NI 9411 Getting Started Guide

Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous. Caution Substitution of components may impair suitability for Class I, Division 2. Caution For Division 2 and Zone 2 applications, install the system in an enclosure rated to at least IP54 as defined by IEC/EN 60079-15. Caution For Zone 2 applications, install a protection device between the Vsup and terminals on the NI 9411. The device must prevent the input Vsup-to- voltage from exceeding 42 V if a transient overvoltage condition occurs. Special Conditions for Hazardous Locations Use in Europe and Internationally The NI 9411 has been evaluated as Ex na IIC T4 Gc equipment under DEMKO Certificate No. 03 ATEX 0324020X and is IECEx UL 14.0089X certified. Each NI 9411 is marked II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 C Ta 70 C. If you are using the NI 9411 NI 9411 Getting Started Guide National Instruments 5

in Gas Group IIC hazardous locations, you must use the device in an NI chassis that has been evaluated as Ex nc IIC T4, Ex IIC T4, Ex na IIC T4, or Ex nl IIC T4 equipment. Caution You must make sure that transient disturbances do not exceed 140% of the rated voltage. Caution The system shall only be used in an area of not more than Pollution Degree 2, as defined in IEC 60664-1. Caution The system shall be mounted in an ATEX/IECEx-certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15. Caution The enclosure must have a door or cover accessible only by the use of a tool. Electromagnetic Compatibility Guidelines This product was tested and complies with the regulatory requirements and limits for electromagnetic compatibility (EMC) stated in the product specifications. These requirements and limits provide reasonable protection against harmful interference 6 ni.com NI 9411 Getting Started Guide

when the product is operated in the intended operational electromagnetic environment. This product is intended for use in industrial locations. However, harmful interference may occur in some installations, when the product is connected to a peripheral device or test object, or if the product is used in residential or commercial areas. To minimize interference with radio and television reception and prevent unacceptable performance degradation, install and use this product in strict accordance with the instructions in the product documentation. Furthermore, any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory rules. Special Conditions for Marine Applications Some products are Lloyd s Register (LR) Type Approved for marine (shipboard) applications. To verify Lloyd s Register certification for a product, visit ni.com/certification and search for the LR certificate, or look for the Lloyd s Register mark on the product. NI 9411 Getting Started Guide National Instruments 7

Caution In order to meet the EMC requirements for marine applications, install the product in a shielded enclosure with shielded and/or filtered power and input/output ports. In addition, take precautions when designing, selecting, and installing measurement probes and cables to ensure that the desired EMC performance is attained. Preparing the Environment Ensure that the environment in which you are using the NI 9411 meets the following specifications. Operating temperature -40 C to 70 C (IEC 60068-2-1, IEC 60068-2-2) Operating humidity (IEC 60068-2-78) Pollution Degree 2 Maximum altitude Indoor use only. 10% RH to 90% RH, noncondensing 2,000 m Note Refer to the device datasheet on ni.com/manuals for complete specifications. 8 ni.com NI 9411 Getting Started Guide

Connecting the NI 9411 The NI 9411 provides connections for 6 digital input channels. NI 9411 Getting Started Guide National Instruments 9

Figure 1. NI 9411 Pinout DI0b DI1b DI2b DI3b DI4b DI5b 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 DI0a DI1a DI2a Supply (+5 Vout) Supply (+5 Vout) DI3a DI4a DI5a Vsup 0 1 10 ni.com NI 9411 Getting Started Guide

Note You must use 2-wire ferrules to create a secure connection when connecting more than one wire to a single terminal on the NI 9411 screw-terminal connector. NI 9411 Signals Table 1. DSUB Connector Signal Descriptions Signal Description DIa and DIb Supply (+5 Vout) Common reference connection to isolated ground Digital input signal connections 5 V power output connection for external devices Table 2. Screw-Terminal Connector Signal Descriptions Signal Vsup Description Common reference connection to isolated ground Voltage supply connection NI 9411 Getting Started Guide National Instruments 11

Connecting an External Power Supply to the NI 9411 You can connect an external power supply to the NI 9411. The external power supply provides power for external devices through the NI 9411 +5 Vout terminal. Connecting an external power supply to the NI 9411 is optional, depending on your application. Figure 2. Connecting an External Power Supply External Power Supply + Vsup +5 Vout DIa DIb +5 V Reg Receiver Circuitry NI 9411 12 ni.com NI 9411 Getting Started Guide

Connecting a Differential Device to the NI 9411 You can connect differential devices to the NI 9411. Figure 3. Connecting a Differential Device to the NI 9411 External Power Supply + Vsup Differential Device +5 V + GND +5 Vout DIa DIb +5 V Reg Receiver Circuitry NI 9411 The NI 9411 compares the difference between DIa and DIb to the digital logic levels to determine if the signal is in the high range or low range. Tip Refer to the device datasheet at ni.com/manuals for the digital logic levels. NI 9411 Getting Started Guide National Instruments 13

Connecting a Single-Ended Device to the NI 9411 You can connect single-ended (TTL) devices to the NI 9411. Figure 4. Connecting a Single-Ended Device to the NI 9411 External Power Supply + Vsup Single-Ended Device +5 V out GND +5 Vout DIa DIb +5 V Reg Receiver Circuitry NI 9411 The NI 9411 compares the difference between DIa and to the digital logic levels to determine if the signal is in the high range or low range. 14 ni.com NI 9411 Getting Started Guide

Tip Refer to the device datasheet at ni.com/manuals for the digital logic levels. Connecting an Encoder to the NI 9411 An encoder has phase A, phase B, and index signals. Use the phase A signals to measure rotational speed. Use the phase B signals to measure direction. Use the index signals to measure the number of rotations. You can connect differential and singleended encoders to the NI 9411. NI 9411 Getting Started Guide National Instruments 15

Figure 5. Connecting a Differential Encoder to the NI 9411 External Power Supply + Differential Encoder +5 V A+ A B+ B Index+ Index GND DI0a DI0b DI1a DI1b DI2a DI2b Vsup +5 Vout +5 V Reg Receiver Circuitry Receiver Circuitry Receiver Circuitry NI 9411 16 ni.com NI 9411 Getting Started Guide

Figure 6. Connecting a Single-Ended Encoder to the NI 9411 External Power Supply + Vsup Single-Ended Encoder +5 V A B Index GND +5 Vout DI0a DI0b DI1a DI1b DI2a DI2b +5 V Reg Receiver Circuitry Receiver Circuitry Receiver Circuitry NI 9411 I/O Protection The NI 9411 provides I/O protection for each channel. NI 9411 Getting Started Guide National Instruments 17

Note Refer to the device datasheet on ni.com/manuals for more information about I/O protection. High-Vibration Application Connections If your application is subject to high vibration, NI recommends that you follow these guidelines to protect connections to the NI 9411: Use ferrules to terminate wires to the detachable connector. Use the NI 9948 backshell kit. 18 ni.com NI 9411 Getting Started Guide

Where to Go Next CompactRIO NI CompactDAQ NI 9411 Datasheet NI 9411 Datasheet NI-RIO Help NI-DAQmx Help LabVIEW FPGA Help LabVIEW Help RELATED INFORMATION C Series Documentation & Resources ni.com/info cseriesdoc Located at ni.com/manuals NI 9411 Getting Started Guide Services ni.com/services Installs with the software National Instruments 19

Worldwide Support and Services The NI website is your complete resource for technical support. At ni.com/support, you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers. Visit ni.com/services for NI Factory Installation Services, repairs, extended warranty, and other services. Visit ni.com/register to register your NI product. Product registration facilitates technical support and ensures that you receive important information updates from NI. A Declaration of Conformity (DoC) is our claim of compliance with the Council of the European Communities using the manufacturer s declaration of conformity. This system affords the user protection for electromagnetic compatibility (EMC) and product safety. You can obtain the DoC for your product by visiting ni.com/certification. If your product supports calibration, you can obtain the calibration certificate for your product at ni.com/calibration. 20 ni.com NI 9411 Getting Started Guide

NI corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504. NI also has offices located around the world. For telephone support in the United States, create your service request at ni.com/support or dial 1 866 ASK MYNI (275 6964). For telephone support outside the United States, visit the Worldwide Offices section of ni.com/niglobal to access the branch office websites, which provide up-to-date contact information, support phone numbers, email addresses, and current events. NI 9411 Getting Started Guide National Instruments 21

Refer to the NI Trademarks and Logo Guidelines at ni.com/trademarks for information on NI trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering NI products/technology, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your media, or the National Instruments Patent Notice at ni.com/patents. You can find information about end-user license agreements (EULAs) and third-party legal notices in the readme file for your NI product. Refer to the Export Compliance Information at ni.com/legal/export-compliance for the NI global trade compliance policy and how to obtain relevant HTS codes, ECCNs, and other import/ export data. NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ERRORS. U.S. Government Customers: The data contained in this manual was developed at private expense and is subject to the applicable limited rights and restricted data rights as set forth in FAR 52.227-14, DFAR 252.227-7014, and DFAR 252.227-7015. 2003 2015 National Instruments. All rights reserved. 373506F-01 Dec15