Installation, Operation and Maintenance Manual for Flame Check

Similar documents
Installation, Operation & Maintenance. Model 7678 End of Line Deflagration Flame Arrester ATEX Certified

Installation, Operation & Maintenance. Model 7688 In Line Deflagration Flame Arrester. ATEX Certified

Installation, Operation & Maintenance of the In-Line Flame Arrestor Model L76L-UF

Installation, Operation and Maintenance Manual for Model 7758A Deflagration and Detonation Flame Arrester

Installation, Operation and Maintenance Manual for Pressure/Vacuum Relief Valves

Installation, Operation and Maintenance Manual for Pressure/Vacuum Relief Valves (Spring Loaded)

Installation, Operation and Maintenance Manual for Spring Loaded Pressure/Vacuum Relief Valves

Installation and Maintenance Manual for the Lock Down Hatch for the Gauge Hatch Model L61T

Installation and Maintenance Manual for the Lock Down Hatch for the Gauge Hatch Model L61T

INSTALLATION AND MAINTENANCE

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

SERIES 670E End-of-Line Deflagration Flame Arrester

Installation, Operation and Maintenance Manual for Weight Loaded Fiberglass Valves

Full View Flow Indicator

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

EN-DFA Series Detonation Flame Arrestor (ATEX Approved)

Varec Series 5000/5010 Flame arresters Instruction, operation and maintenance manual

7 Series Flame Arrestor

94407 Horizontal Inline Deflagration Flame Arrester

MODELS 1400, 1420, 1430, 1460

D Instructions/Parts. Siphon Feed Detail Spray Gun D

MGFHVLP. Instructions/Parts. Mini Gravity Feed System E. Part No Includes MGFHVLP Mini Gravity Feed Spray Gun and MGC 125 Gravity Cup.

33 CENTERVILLE ROAD LANCASTER, PA

Installation, Operation and Maintenance Manual for Spring Loaded Thief Hatch Model L12-TH and L12-TL

Model DFA Detonation Flame Arrestor. Model DFA North America Only. Table of Contents. Introduction WARNING. Product Description

8 Series High Pressure Deflagration Flame Arrestor

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER INJECTION PUMP

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER AUTOMATIC INSERTION PROBE

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER SAMPLE / INJECTION PUMP

DFA Series Detonation Flame Arrestor (USCG/ATEX Approved)

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER RECYCLE TIMER

94406 Vertical Inline Deflagration Flame Arrester. Features

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

2001 SERIES CRYOGENIC BAR STOCK BODY VALVES

When installing the screwed end, socket weld & flanged end valves the following respective procedures shall be followed for better performance.

V-SEGMENT SERIES V-Port Segment Control Valves (VS/VV/VM) Installation & Maintenance Manual

H2O-C14 AAA FINE FINISH SERIES PUMP OUTFIT

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

2013 IMPCO Technologies, Inc. Page 1 of 20 EPR Repair Kit Instructions (PPI-122, Rev-B)

These installation and maintenance instructions must be read in full and completely understood before the installation!

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

IOM Manual. IOM Manual. Series 76/77.

GT-200 GATE VALVES PN16, Screwed end

INSTALLATION AND SERVICE INSTRUCTIONS FOR 2000 SERIES FLAMEPROOF XENON AND FLUORESCENT BEACONS

Installation & Operation Manual. IMPORTANT: This manual contains important information. READ AND KEEP FOR REFERENCE.

Polypropylene Piston Drum Pumps

Wastewater Combination Air Valve. Operation, Maintenance and Installation Manual

SM64052 Maintenance & Repair Manual Commercial 2" Unisex Coupling - Valved Model 64052

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

T1-Titanium Non-HVLP Spray Gun

Pressure Relief Valve Maintenance Manual

Installation Operation Maintenance

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER PROBE MOUNTED LIQUID ELIMINATOR

OPERATOR S MANUAL A

740G Double Disc Check. Valve. Operation / Maintenance Manual. General Information 2. Installation/Operation 3

B14 AAA FINE FINISH SERIES PUMP OUTFIT

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Guide

Installation, Operation, and Maintenance Manual

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) Model 6A00. Inline Deflagration Flame Arrestor SECTION I

OPERATOR S MANUAL SERVICE KITS PUMP DATA MODEL DESCRIPTION CHART INCLUDING: OPERATION, INSTALLATION & MAINTENANCE RELEASED:

DVG/AF Variable Geometry Desuperheater

Series 820 AWWA Butterfly Valves

FABER BURNER ROUTINE MAINTENANCE

Kimray reserves the right to modify or improve the designs or specifications of such products at any time without prior notice Kimray Inc.

CV Control Valves Installation and Operation Manual

Installation, Operation, and Maintenance Manual

S E R V I C E B U L L E T I N

Instructions Parts List

Instruction Manual For DODGE. Airport Baggage Handling Systems Speed Reducers

Double Offset High Performance Butterfly Valve

DETONATION FLAME ARRESTER MODEL 7658A

Subject: Engine Oil Consumption on High Feature V6 Engines - Air Cleaner Housing Test, Repair Procedure (Install Piston Rings, Service PCV System)

SENSIT TKX INSTRUCTION MANUAL. Combustible Gas Leak Detector. Read and understand instructions before use.

INSTALLATION & MAINTENANCE MANUAL SERIES 90SV/93V SEGMENTED V FLOW VALVES

Inspection and Maintenance of Flame Arresters

Technical information for LFU20-Z07-3A-X2

Flame Arrester. ergil. ATEX approved. Storage Tank Protection Equipment. Model Number 300. Product Description. (Vertical, in-line, deflagration)

EC4 SERIES CRYOGENIC VALVES 1/4 2 Sizes

Rev. Apr. 2/02 !# " " $%# &&% #&% #&&% &% *!)

B14 AAA FINE FINISH SERIES PUMP OUTFIT

Installation, Operation, and Maintenance Manual

ATEX/IECEx Coil Manual Type 200 and 300 Series Coils for EH70 Series Solenoid Valves Issue , Released December 13, 2017

MOTORCYCLE DIVISION 4-STROKE BULLETIN NO. GS/GSX/GSX-R - 97 REVISED DATE: 9/2/98

Installation, Operation and Maintenance Manual

HIGH PERFORMANCE BUTTERFLY VALVE MODEL HP300 SERIES

for ½" thru 2" 800 lb. Piston Lift Check Valves with Resilient Seat Option

Voltmaster Centrifugal Trash Pumps

'C' Series Control Valves

PASSIVE OPERATION Completely self-contained with no reliance on power supplies, sensors, actuators or any external components.

HFB Steering Gear Service Manual

1-1/2 Inch Self-Priming Centrifugal Pumps Refer to pump manual for General Operating and Safety Instructions.

740G Double Disc Check Valve

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Triple Offset Valves

February 26, ch.12.notebook. Ch. 12. Preventative Maintenance and Troubleshooting. Feb 23 5:03 PM

NUMBER: S.M. REF.: Listed in Table ENGINE: EPA07 Series 60 DATE: October 2012 SUBJECT: REFERENCES TO THE TURBOCHARGER PURGE ROUTINE

Transcription:

Installation, Operation and Maintenance Manual for Flame Check Model 7622B 2014 Groth Corporation IOM-7622B Rev. C 12444 Ref. ID: 98172

Page 2 of 9 Table of Contents SECTION PAGE I. Introduction 3 II. Inspection and Installation 4 Table 1 - Application Guidelines 4 III. Maintenance 5 Figure 1 Typical Model 7622B Flame Element 5 IV. Spare Parts 7 V. Flame Bank Assembly Kits 8 Kit Identification (Graphic) 8 VI. Flame Check Assembly 8 Model Identification (Graphic) 8 Sample Gas Groups 8 Appendix A MODEL 7622B FLAME CHECK (1/2"- 2") 9

Page 3 of 9 I. INTRODUCTION Groth Corporation s flame checks are designed to inhibit flame propagation in gas piping systems and to protect low pressure tanks containing flammable liquids. They protect low flash point liquids from externally caused sources of heat and ignition, providing increased fire protection and safety. The flame check products consist of two main components, the arrester body and the flame element. The body serves as the connecting interface to the piping system. In the event that a flame front is traveling through the pipe, the flame element is instrumental in stopping the flame passage. The geometry of the flame element absorbs the heat from the vapor flow, cooling the vapor to prevent autoignition on the protected side. The flame element is comprised of small wafers of wire mesh and perforated plates aligned so that an approaching flame front is slowed down and then quenched before it can propagate to the protected side of the device. The small perforated wafers layered with wire mesh are used to promote heat absorption and turbulence and are constructed of corrosion resistant materials. The assembly as a whole, is also engineered for minimum pressure drop. A flame arrester should be treated as a safety device and maintained by a knowledgeable repair technician. Carefully read and understand this manual before installing or servicing this product. For information not contained in this manual, please contact: Groth Corporation 13650 N. Promenade Blvd. Stafford, TX, 77477 USA Phone: 281-295-6800 Fax: 281-295-6999 www.grothcorp.com

Page 4 of 9 II. INSPECTION AND INSTALLATION All Groth Corporation's flame checks are bi-directional and the installation on a tank or piping system depends to a great extent on the design of the system. Groth model 7622B flame check may be installed in any orientation (horizontal, vertical, etc.). This product is used in gas lines where flow can be easily shut off. They are normally supplied with either threaded or flanged connections. As with any new equipment, prior to installation, an inspection should be made to ensure all thread protectors and packing materials are removed. Also inspect the unit to ensure the unit is not damaged due to rough handling during shipment or job site accident. All connections should be tight. Note: This series of flame arresters has ANSI FNPT threaded connections or can be coupled with ANSI 150#, PN 10 OR PN 16 flanges. Each unit is pneumatically leak tested to 15 PSIG at the factory. The following application guidelines should be observed at installation: Table 1 FNPT Size Gas Type(IEC) Gas Group(NEC) Max Run Up Length (Pipe diameters =L/D) ½ IIA or IIB3 D or C 50 23.2 ¾ IIA or IIB3 D or C 50 23.2 1 IIA or IIB3 D or C 50 23.2 1 ½ IIA or IIB3 D or C 50 23.2 2 IIA or IIB3 D or C 50 23.2 Note: Groth Corporation's flame arresters have been tested by a 3 rd party ATEX approved test facility. This device is considered an integral part of a Shut Down Operation system and is therefore not designed for stabilized burn. Max Pre-ignition Pressure (PSIA) 1. Remove any flange protectors and discard all packing material. Inspect flange faces and flame element for damage or contamination. 2. If flange option is used, Inspect the gasket seating surface of the tank nozzle or piping. It must be clean, flat, free of scratches, corrosion and tool marks. 4. Teflon tape is recommended for installation due to the possible clogging of the flame element when pipe sealant or paste is used. 5. Set the arrester between the mating pipe or flanges and ensure there will not be too much stress on the flame check body. 6. Make up the final torque and check that all connections are tight and that the body of the flame check is secure as well. WARNING: After installation, all connections should be inspected for vapor leakage. This may be accomplished by static pressure test, gas detector, or "bubble" test using a liquid leak detector.

Page 5 of 9 III. MAINTENANCE For maximum operating efficiency, the element of a flame arrester must be inspected for clogging at regular intervals. Frequency of inspection and maintenance should be based on the experience gained in each application. For servicing this unit, the flame check should be removed from the line. It is recommended that the arrester be removed for inspection of the element at least once per year or any time that one of the following conditions occurs: Excessive pressure drop is encountered at a known flow rate. A flame front is detected. 1. Purge the line or tank with an inert gas before attempting to remove the arrester for maintenance. CAUTION: The connecting pipeline must be free of all hazardous or flammable vapors before inspection procedures begin. Before disassembling consult Material Safety Data Sheets (MSDS) for all products that were exposed to in service. The components should be cleaned according to MSDS procedures. Take appropriate safety precautions regarding eye protection, skin contact & respiration. 2. Refer to Fig. 1 which illustrates a typical flame check element assembly. FIGURE 1 - TYPICAL MODEL 7622B FLAME CHECK ELEMENT 3. Loosen the piping connections and withdraw the FULL housing. WARNING: Failure to replace a damaged or clogged flame element can render the flame arrester ineffective WARNING: The full housing must be removed from the line because the wafers will tend to come out of alignment and cause the unit to lose its seal and become ineffective if the housing is separated in the horizontal position.

Page 6 of 9 4. Verify that the element openings are not clogged by viewing a light source through the element passages. If the flame element is dirty or clogged it can be cleaned by one of the following methods: Compressed air High pressure steam or water purge Solvent wash followed by compressed air WARNING: Never try to clean the element by inserting a sharp tool or probe into the orifices. Any damage to the integrity of these passages can render the flame arrester ineffective. CAUTION: If compressed air, steam, or high pressure water jet is used to clean clogged element passageways, restrict access to the area to prevent injury from blown debris exiting the element. Use appropriate personal safety equipment for the cleaning method used. TIP: The best method of cleaning and frequency should be based on the experience gained in each application. 5. Inspect the sealing gasket for damage and replace if necessary.(see Table 2 for replacement kit part numbers.) 6. Install a gasket in the counter bore of the coupling. Position the element housing to align with the counter bore. Make sure the flame elements are centered while the coupling halves are screwed together. Improper alignment of the element wafers during the reassembly process may render the unit ineffective at stopping the flame and could cause a leak path. 7. If the arrester is in high temperature service or stainless steel mating components are used, apply an anti-seize compound such as moly-disulfide to the threaded connections. Use this anti-seize sparingly and do not allow excess compound to clog the flame bank. 8. Make up the final torque and check that all connections are tight and that the flame check body is secure.

Page 7 of 9 IV. SPARE PARTS Flame Bank Kits are available upon request. Kits include the flame arrester element assembly and one non-asbestos gasket. Kits are based on Model Number, Size, Material and Gas Group. To procure the appropriate kit, please contact Groth Corporation with the Serial Number, Model Number, Size, Material and Gas Group. V. TABLE 2 FLAME BANK ASSEMBLY KITS Size Element Material Gas Group(NEC/ATEX) Kit P/N 1/2" 304 SS D Gas / IIA KFB76220541 3/4" 304 SS D Gas / IIA KFB76227541 1" 304 SS D Gas / IIA KFB76220141 1 ½ 304 SS D Gas / IIA KFB76221541 2" 304 SS D Gas / IIA KFB76220241 1/2" 316 SS D Gas / IIA KFB76220551 3/4" 316 SS D Gas / IIA KFB76227551 1" 316 SS D Gas / IIA KFB76220151 1 ½ 316 SS D Gas / IIA KFB76221551 2" 316 SS D Gas / IIA KFB76220251 1/2" 304 SS C Gas / IIB3 KFB76220542 3/4" 304 SS C Gas / IIB3 KFB76227542 1" 304 SS C Gas / IIB3 KFB76220142 1 ½ 304 SS C Gas / IIB3 KFB76221542 2" 304 SS C Gas / IIB3 KFB76220242 1/2" 316 SS C Gas / IIB3 KFB76220552 3/4" 316 SS C Gas / IIB3 KFB76227552 1" 316 SS C Gas / IIB3 KFB76220152 1 ½ 316 SS C Gas / IIB3 KFB76221552 2" 316 SS C Gas / IIB3 KFB76220252 Kit Number Identification ----- ------ ---------- KFB7622 Size Element Gas Type 05=1/2 4=304 SS 1 - D / IIA 75=3/4 5=316 SS 2 - C / IIB3 01=1 Z=Special 15=1.5 02=2

Page 8 of 9 VI. MODEL NUMBER IDENTIFICATION The nameplate on the Flame Arrester contains the Model Number, Serial Number, operational, temperature, operational pressure, and Run up (L/D) distance. The Model Number contains additional information about materials of construction, soft goods and options. The following chart will assist in relating the Model Number to the characteristics of your valve: 7 6 2 2 B ----- ------ ------------ Model 7622B Size Element Gas Type 1 D / IIA 2 C / IIB3 05=1/2 4=304 SS O = No Specials 75=3/4 Body 5=316 SS Z = Special Option 01=1 3=CS Z=Special 15=1.5 5=316 SS 02=2 Z=Special N= Standard FNPT` F= Flanged Outlet EXAMPLE: Model 7622B-01-35-1NO indicates a 1" Model 7622B with a CS Body and 316 SS flame element, D gas group, Standard FNPT inlet/outlet connections, and no special options. Sample Explosion Groups IEC NEC/CEC Inflammable material Zone Group Class Division Group Gas and Vapors Cyclopropane Ethyl Ether Ethylene Tetrafluoroethylene Acetone Benzene Butane Hexane Propane Paint solvents Gasoline Vapors Natural gas(methane) 0,1 or 2 II B I 1 or 2 C 0,1 or 2 II A I 1 or 2 D * For a more extensive list of gases and group ratings, refer to appropriate standard.

Page 9 of 9 APPENDIX A: Model 7622B Flame Check (1/2"- 2") ITEM DESCRIPTION STD MATERIALS OF CONSTRUCTION 1 COUPLING HOUSING CS (WCB) 316 SS (CF-8M) 2 *FLAME ELEMENT ASSEMBLY 304 SS 304 SS 4 GASKET NON-ASB NON-ASB * Recommended Spare Parts Notice: Please specify model number, size and serial number as shown on the equipment tag when ordering replacement parts.