CHALLENGER Propane to Natural Gas Instructions

Similar documents
GAS CONVERSION KIT INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR PCDE-36VA CONVERSION KIT

Note: An arrow ( ) found in the text signifies change in content.

INSTALLATION INSTRUCTIONS FOR PCBM-36C CONVERSION KIT From Natural Gas to Propane/LP Gas

Gas Conversion Kits and Instructions

Installation Instructions for. For Use When Converting Model (V)M42(B) Vented Decorative Fireplace. Fold Bi-Fold Door After Releasing

Applies to: Models F, B, FE, and BE with spark pilot

TC30 TRANQUILITY BURNER KIT INSTRUCTIONS

Installation Instructions

5270 Edison Ave., Chino, CA (Tel) (Fax)

Legacy Combustion Chamber Replacement Kit

INSTALLATION INSTRUCTIONS

Routine Burner Service

Specifications of MAXON VALUPAK burners for 50 Hz operation

DVM36/42 SERIES LOG SET/BURNER MODULES INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

Jandy FloPro (FHP) Series Pump Parts Replacement Kit Instructions

B21 Series BASOTROL Gas Valve

ONYX VALVE CO MODEL CER with JORDAN ACTUATOR Installation & Maintenance

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

INSTALLATION INSTRUCTIONS NATURAL TO PROPANE CONVERSION KIT

MODERUSTIC Battery Operated Remote Control Electronic Safety Pilot System IPI Intermittent Pilot Light For Fire Pits or Fireplaces

M-9603-CJ 123 mm Cold Air Kit for 5.4L 4V V8 Cobra Jet Mustang INSTALLATION INSTRUCTIONS

TECHNICAL SERVICE BULLETIN

Start-up Instructions

OWNER'S MANUAL WARNING DANGER. Propane cylinders sold separately. The propane cylinder must be disconnected when this firebowl is not use.

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

TECHNICAL INSTRUCTIONS

Models: AFVK-SP-SPLIT AFVK-SP-H/L-SPLIT AFVK-SP-MH/L-SPLIT INSTALLATION AND OPERATING INSTRUCTION

INSTALLATION INSTRUCTIONS

Propane torch. Model Assembly And Operation Instructions

SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE - NOTICE - ML ML ML RRG Shown

M-9603-GTB 85 mm Cold Air Kit w/premium Cal. for 4.6L 3V V8 Mustang INSTALLATION INSTRUCTIONS

TECHNICAL INSTRUCTIONS

G76x Direct Spark Ignition Controls

Installation Manual. English. French

CAUTION WARNING WARNING PROFLAME 2 UPGRADE KIT RX RX 300 NG/LP. Installation & Maintenance Manual

VE4000 & VE5000 SERIES

Installation Instructions

2018 Mustang Ecoboost Cold Air Intake P/N: ( ) Application: 2018 Ford Mustang 2.3L Manual or Automatic Transmission

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

ROBERT H. PETERSON CO. AUTOMATIC REMOTE LIGHTING SAFETY PILOT SYSTEM WITH VARIABLE FLAME-HEIGHT REMOTE FOR NATURAL OR PROPANE GAS. Model APK-17(M)(P)

ONYX VALVE CO MODEL CAR, CAP-PFO Installation & Maintenance

2013 IMPCO Technologies, Inc. Page 1 of 20 EPR Repair Kit Instructions (PPI-122, Rev-B)

Natural Gas Conversion Instructions for

2014 GM Truck Level 1 Performance Pack

Troubleshooting Guide

Installation Guide. Installing the FRK Hydraulic Compact Unit (HCU) on International School Buses TP-0913 Issued 1 Technical Bulletin

EDELBROCK THUNDER SERIES AVS CARBURETORS Part #1801, 1802, 1803, 1804, 1805, 1806, 1812, 1813, 1825, 1826 INSTALLATION INSTRUCTIONS

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Robert H. Peterson Co.

AUTOMATIC REMOTE CAPABLE SAFETY PILOT SYSTEM

1100W PORTABLE GENERATOR

Mustang 5.0L Cold Air Intake Installation Instructions P/N:

EDELBROCK THUNDER SERIES AVS CARBURETORS Part #1801, 1802, 1803, 1804, 1805, 1806, 1812, 1813, 1825, 1826 INSTALLATION INSTRUCTIONS

ONYX VALVE CO MODEL CER and CEP Installation & Maintenance

Installation Instructions

AUTOMATIC REMOTE CAPABLE SAFETY PILOT SYSTEM

Installation Instructions

OWNER S MANUAL: Model # JGSBSEAR Searing Burner Station

Replacement Parts List. Knight Fire Tube Boilers KHB 055 thru 285 Series 100 & _ _Rev B

f i r e - p a r t s. c o m

M-9603-SVT mm Cold Air Kit w/premium Calibration INSTALLATION INSTRUCTIONS

G600 Series Replacement Intermittent Pilot Ignition Controls

TECHNICAL MANUAL WENDY'S RANGE MODEL: C0300HT AND C0301 HT

Replacing the Carburetor

ONYX VALVE CO MODEL DAO-ADA Installation & Maintenance

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors

Manual Revision F Publication Date: 11/20/17 NOTE: Dimensions in () are informational only. English values take priority.

Replacement Parts List. Knight Fire Tube Boilers. KH 55 thru _ _Rev D

ONYX VALVE CO MODEL DAC-PFO Installation & Maintenance

E Series CE Approved Intermittent Pilot Ignition Control

G72x Series Direct Spark Ignition Controls

ONYX VALVE CO MODEL DAO-PFC Installation & Maintenance

Mustang V-6 Cold Air Intake P/N: ( A600) Application: Ford Mustang 3.7L Manual or Automatic Transmission

Safety Pilot System For Vented Gas Logs

289 Series Relief Valves

Installing FRK and FRK Hydraulic Compact Unit (HCU) on Navistar Straight Trucks

Info 110 4/98. RatioMatic Burners. RM Series version through 600 Sizes. 750 through 2000 Sizes

1080 CF Valve Replacement Instructions

Installation Guide. Installing the FRK Hydraulic Compact Unit (HCU) with Parking Brake Valve on International School Buses

PROPANE TORCH WITH TURBO BURNER

V5197A Firing Rate Gas Valve

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

ONYX VALVE CO MODEL DAO-PFO Installation & Maintenance

Installation, Operation and Maintenance Manual

MODEL 11A REGULATOR

Installation & Service Instructions

2018 F L Cold Air Intake Installation Instructions P/N: ( )

2018 Mustang 5.0L Cold Air Intake Installation Instructions P/N: ( )

Troubleshooting Guide

ECLIPSE AIR HEAT BURNERS Series AH, DAH, TAH & CAH

POCKET GUIDE for TROUBLESHOOTING Gas Products To be used by F.P.I. trained service technicians only.

INSTRUCTION FOR EFI FUEL PRESSURE GAUGE TOOL

AEROMOTIVE Part # & Stealth Fuel Tank Sump INSTALLATION INSTRUCTIONS

401B/1KDB CoolRite/FreezeRite Installation Manual I003

Transcription:

Kit Part Number: CCRKIT02 Kit Includes: - Rating Label - (3) Natural Gas Orifices - T-15 Torx Wrench Recommended Tools: - Phillips-Head Screwdriver - Standard Adjustable Wrenches - Calibrated Combustion Analyzer Indicates a potentially hazardous situation which, if ignored, can result in serious injury or substantial property damage. Indicates special instructions on installation, operation or maintenance, which are important to equipment but not related to personal injury hazards. This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. This installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit. Failure to follow instructions below can result in severe personal injury or damage if ignored: - Instructions are for a qualified installer / service technician. - Read all instructions before proceeding. - Follow instructions in the proper order. CAUTION The gas supply shall be shut off prior to disconnecting the electrical power, before proceeding with the conversion. For your safety, turn off electrical power supply at service panel and allow appliance to cool before proceeding. Failure to do so can cause severe personal injury or death. Upon completion of the conversion from Propane to Natural Gas, affix the new rating label included in the kit to the appliance just below the existing rating label on the right side jacket panel. DO NOT affix the new label over the existing rating label. Remove propane conversion labeling from the gas valve. Complete the Installation Record by recording the combustion reading in the CHALLENGER Installation and Maintenance Manual. 1

Installation of the Natural Gas Orifice 1. Close the manual gas shut off valve to the appliance. 2. Turn off the electrical power supply to the appliance. 3. Remove the front panel by flipping down the control panel and loosening the two Phillips head mounting screw(s) at the control panel. Pull bottom of front panel forward to remove. CHALLENGER 4. Disconnect the gas piping inside the CHALLENGER enclosure at the brass union located above the gas valve, and rotate piping towards the back of appliance, see Fig. 1. Gas Piping Union Nut O-Ring Gasket Gas Orifice Gas Valve The gas orifice is installed in a O-ring gasket. This O-ring gasket must be reinstalled when ever the gas orifice is changed. Use care not to damage the O-ring gasket. 5. Separate the O-ring gasket from the propane gas orifice and insert the appropriate brass natural orifice from Table 1 into the O-ring gasket. The CHALLENGER appliances contain a propane gas orifice. This orifice must be removed prior to the installation of the natural gas orifice. Table 1: Natural Gas Orifice CHALLENGER MODEL Propane Gas Orifice Size Orifice Marking CC50s 0.217 [5.50 mm] 550 CC85 or CC85s CC105 or CC105s CC125, CC125c or CC125s CC125H or CC125Hs 0.256 [6.50 mm] 650 0.256 [6.50 mm] 650 0.285 [7.25 mm] 725 0.217 [5.50 mm] 550 Fig. 1: CHALLENGER Gas Valve/Orifice Assembly Failure to retain the O-ring gasket on the gas orifice will cause an improper seal between the gas valve and the union resulting in a potential risk of a gas leak. Ensure unions at top and bottom of gas valve are tight. Any potential gas leakage may result in death, serious injury or substantial property damage. Ensure the proper orifice for natural gas is installed as given in Table 1. Failure to comply will affect input rate and combustion efficiency of the appliance which may result in death, serious injury or substantial property damage. 6. Install proper natural gas orifice/o-ring gasket assembly on the top of the gas valve. 7. Reconnect the gas piping on top of gas valve and tighten the brass union connections at the gas valve. CC150s 0.285 [7.25 mm] 725 2

8. Open the manual gas shut off valve. Before placing the CHALLENGER back into operation check and test all gas connections for leaks. Repair leaks if found. 0.12 [ 3 mm] Do not check for gas leaks with an open flame. Use a bubble test. Failure to check for gas leaks can cause severe personal injury, death or substantial property damage. Inspect Ignition Electrode (45.00) 0.43 [11 mm] Prior to inspecting the ignition electrode, ensure all electrical power supply to the appliance is turned off to avoid electrical shock. 1. Remove the ignition electrode using the T-15 Torx wrench. Spark gap approximately. 0.18 1.75 [44 mm] 1.18 [30 mm] 0.12 [3 mm] 2. Remove any white oxides accumulated on the electrode using fine grit sandpaper or steel wool. If the electrode does not clean to a satisfactory condition, replace the ignitor. 3. Check ignitor to Fig. 2 4. When replacing the ignition electrode, ensure the gasket is in good condition and correctly positioned, replace gasket if necessary. Check Inlet Gas Supply Pressure 1. Turn on the electrical power supply to the CHAL- LENGER. 2. Check the inlet gas supply pressure to the CHAL- LENGER at the gas valve (see Figs. 3 and 4 on page 5). Ensure a minimum pressure of 5 w.c [13 mbar] during flow conditions with all gas appliances firing including the CHALLENGER and a maximum pressure of 13 w.c [32 mbar] during non-flow conditions with all gas appliances off including the CHAL- LENGER. [5 mm] 1.06-1.12 [27 mm - 29 mm] Fig. 2: Igniter Dimensions Combustion Test and Adjustments 1. The installer must perform a complete combustion check to ensure the following combustion levels are met at high and low input firing rates and the burner is operating at optimum conditions for propane gas. The combustion testing and adjustments must be performed only by a qualified installer, service agency or the gas supplier. All combustion measurements must be performed with calibrated equipment to ensure proper readings and accuracy. 3

Table 2: Recommended Combustion Levels Combustion Levels Natural Gas Propane Gas High Fire DOOR OFF* Low Fire CO 2 Range 9% to 10.1% 10.5% to 11.1% CO 2 Target 9.0% 10.8% O 2 Range 3.0% - 5.0% 4.1% - 5.0% O 2 Target 5.0% 4.5% CO 2 Range O 2 Range Failure to perform a complete combustion test at both high and low input rates may result in incomplete combustion and the production of carbon monoxide, which can cause severe personal injury, death or substantial property damage. 2. Manually place the appliance into high fire mode by pressing both the service button with + button simultaneously on the control panel display two times. The control panel will display a H followed by the current appliance temperature when placed into high fire test 0% - 0.4% < H.F 9.0% min. 0% - 0.6% > H.F 5.0% max. 0% - 0.4% < H.F 10.5% min. 0% - 0.6% > H.F 5.0% max. CO Max. 100 ppm 150 ppm * Door On can raise the maximum allowable CO 2 by 0.4 or lower the minimum allowable 0 2 by 0.6. The THROTTLE SCREW on the CHALLENGER s gas valve works opposite than the PRESTIGE. If you turn the CHALLENGER s THROTTLE SCREW clockwise you increase the input, CO 2 and CO of the appliance. EXERCISE CARE! 3. If the combustion levels during high fire are outside the recommended combustion settings, adjust the THROTTLE SCREW (see Figs. 3 and 4 on page 5) using a T15 Torx wrench as follows: Counter-clockwise adjustment of the THROTTLE SCREW at High Fire: O2 increases and CO2 decreases Clockwise adjustment of the THROTTLE SCREW at High Fire: O2 decreases and CO2 increases 4. Once the combustion level is set and recorded at high fire, manually place the appliance into low fire mode by pressing the service button with - button simultaneously on the control display once. The control panel will display a L followed by the current appliance temperature when placed into low fire test 5. If the combustion levels during low fire are not within 0.0 to 0.4% CO2 lower than the combustion level measured at high fire, remove the offset pressure cover screw and adjust the OFFSET SCREW (see Figs. 3 and 4 on page 5) using a T15 Torx wrench as follows: The OFFSET SCREW adjustment on the CHALLENGER S gas valve is very sensitive. A small adjustment will have a significant effect. Counter-clockwise adjustment of the OFFSET SCREW at Low Fire: O 2 increases and CO2 decreases Clockwise adjustment of the OFFSET SCREW at Low Fire: O 2 decreases and CO2 increases 4

6. Confirm the combustion levels at both high fire and low fire meet the requirements listed in Table 2 on page 4. 7. Press the + and - button simultaneously to cancel high or low fire Test mode will time out in approximately 10 minutes. Throttle Screw Offset Pressure Cover Screw 8. Replace offset cover screw. 9. Check the flame pattern through the inspection port on the left side of the heat exchanger. The flame should be blue and stable and should be the length of the burner. 10. Replace the front jacket panel and secure with the two Phillips head mounting screws at the control panel. Measure Input 1. Ensure the appliance is firing at maximum firing rate. To manually place the appliance into high fire mode, press both the service button with + button simultaneously on the control panel display two times. Flow direction Fig. 3: Original Gas Valve Offset Pressure Port Inlet Gas Supply Pressure Port The control panel will display a H followed by the current appliance temperature when placed into high fire test 2. Operate the appliance for approximately 5 minutes. 3. Turn off all gas appliances within the building, except the CHALLENGER. 4. At the gas meter, record the time required to use one cubic foot of gas. 5. Calculate Natural gas input using the following equation: 3600 x 1000/number of second recorded for one cubic foot of gas = BTU/H. Fig. 4: Updated Gas Valve 6. The BTU/H calculated should approximate the input rating listed on the appliance. 7. Press the + and - button simultaneously to cancel high or low fire Test mode will time out in approximately 10 minutes. 8. Return appliance back to service. Date: 10/6/2016 2010-42 CHALLENGER Propane to Natural Inst.