INSTALLATION INSTRUCTIONS

Similar documents
INSTALLATION INSTRUCTIONS

Cased/Uncased Coils For Gas And Oil Furnaces

Cased/Uncased Coils For Gas And Oil Furnaces

CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INSTALLATION INSTRUCTIONS

AIR CONDITIONERS WA14**A SERIES

AIR CONDITIONERS WA16 SERIES

INSTALLATION INSTRUCTIONS

INSTALLATION GUIDE CR SERIES - DEDICATED HORIZONTAL COIL ! WARNING. 1. Safety Instruction. 2. Inspection. 3. Installation Preparation

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

ELITE SERIES R-410A Ready - Multi-Position

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION FEATURES MODELS: AHR18 THRU 60* WARRANTY

INSTALLATION INSTRUCTIONS

INDOOR COILS. RCFM- featuring New Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INSTALLATION MANUAL FOR LG AIR HANDLER UNIT (AHU) COMMUNICATIONS KIT. AHU Model Number: PRCKAM

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION FEATURE


EVAPORATOR COILS PRODUCT SPECIFICATIONS EAC4X EAC1P EAU1P EAH1P EVAPORATOR COILS FEATURES

Low Profile Unit Coolers

t EVAPORATOR PRESSURE REGULATING VALVES

13 SEER HEAT PUMPS Features Coils constructed with copper tubing and enhanced aluminum

R-22, 13 SEER 60 Hertz

Installation Instructions

High Profile Evaporator

13 SEER HEAT PUMPS Features Coils constructed with copper tubing and enhanced aluminum

Rheem Classic Series. Air Conditioners

Rheem Classic Series. Air Conditioners

Installation and Start-Up Instructions

DZ14S Commercial 3-5 TON, THREE-PHASE SPLIT SYSTEM HEAT PUMP 14 SEER / R-410A

MERIT Series R-410A - Upflow / Horizontal - Variable Speed

ASPT Multi-Position Air Handler

Rheem Classic Series. Air Conditioners

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: GHD, GFD, GFA, GNA, GUA & GHA CFM 2-5 TON COILS

Installation and Start Up Instructions

Cased/Uncased Coils For Gas And Oil Furnaces

FSH1BG Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Ultra High Efficiency Heat Pump, Up to 19 SEER Residential System 2-5 Ton Capacities

INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS

ARUF. 1½ to 5 Tons. O when tested in accordance with ASHRAE standard 193 Cabinet air leakage less than 1.4% at 0.5 inch H 2

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60

SYST0101ZP Ion Damper Control Installation and Start---Up Instructions

Rheem High Efficiency Air Handler

ARPT. Multi-Position 1½ to 5 Tons Construction

DAVE LENNOX SIGNATURE COLLECTION Multi Position Variable Speed Blower

ARUF Series Multi-Position

Installation instructions for KIT15017, KIT15018, KIT15019, and KIT15020

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

RCBA- MULTIFLEX INDOOR COILS

ARUF. Multi-Position Air Handler. 1½ to 5 Tons. Construction

High Profile Evaporator

Typical Applications. Horizontal Installation

ELITE Series R-410A - Upflow / Horizontal

Installation Instructions

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

HE Series Evaporator Coils

HE Series Evaporator Coils

TECHNICAL SUPPORT MANUAL Coils for Manufactured Housing EMA2X, EMA4X

AVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 1½ to 5 Tons. Contents.

Rheem Classic Series. Air Conditioners

Ruud Achiever Series Air Conditioners

COLD WEATHER START KIT Platinum Mini Split

R4H4. Product Specifications

File In/With: N/A. Equipment Affected: TXV Standard with ETRE (old) used as an option on some units. Brine units use TXV and SOL.

AIR HANDLERS AIR HANDLERS. UHKA- SERIES featuring R-22 Refrigerant UHKL- SERIES featuring Earth-Friendly R-410A Refrigerant.

Rheem High Efficiency Air Handler

611H Flo-Con Pressure Regulators & Valves

AIR HANDLERS RBHK- SERIES HEAT PUMP AIR HANDLERS AND FAN COIL UNIT

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL SUPPORT MANUAL Split System Heat Pump R2HM, R2H3, WCH3**2

Ruud Achiever Series Air Conditioners

Installation Instructions

INDOOR COILS RCBA-/RCHJ-/RCHL- MULTIFLEX CASED OR UNCASED INDOOR COILS. AIRFLOW CAPACITIES CFM [ L/s]

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS CX34. Upflow - Cased - R-410A PRODUCT SPECIFICATIONS. 1.5 to 5 Tons C X A - 6 F MODEL NUMBER IDENTIFICATION FEATURES

LG AHU Control Kit / EEV Kit

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION MODELS: AHP18 THRU 60 AND SHP48 THRU 60 FEATURES

Technical Information

DESCRIPTION FEATURES

TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION MODELS: MC, PC, FC, HD, UC CFM 1.

TECHNICAL GUIDE R-410A, 13 SEER LATITUDE SERIES 60 Hertz

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Q35 Series Automatic Vent Damper System

AIR HANDLERS AIR HANDLERS. RHPN- SERIES 18 SEER featuring Earth-Friendly R-410A Refrigerant. Features

BCE5E PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS WARRANTY

Low Profile Unit Cooler

MEDIUM PROFILE UNIT COOLERS Technical Guide. Models HMA Air Defrost HME/HML Electric Defrost HMG/HMF Hot Gas Defrost.

Why and how to adjust a TXV / TEV

INDOOR COILS RCBA-/RCHJ-/RCHL- MULTIFLEX CASED OR UNCASED INDOOR COILS. AIRFLOW CAPACITIES CFM [ L/s]

Installation Instructions

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS DESCRIPTION FEATURES YTG-A-0806

Pneumatic Isolation Module

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

TECHNICAL SPECIFICATIONS

Indoor Coils. CAUF, CAPF, CAPT, CHPF, and CSCF. Cased, Painted Upflow/Downflow, Uncased Upflow/Downflow, Horizontal A, and Horizontal Slab

INSTRUCTION MANUAL. Xfinity Enpro 12 Top Discharge Outdoor unit 31VA Series.

Technical Manual. DLM Module. This manual should remain with the unit.

Transcription:

INSTALLATION INSTRUCTIONS FOR REPLACEMENT COILS USED IN AIR HANDLERS (-)CH: featuring Industry-Standard R-410A (-)CH: Refrigerant efrigerant WARNING! WARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. ISO 9001:2008 92-100105-14-05 SUPERSEDES 92-100105-14-04

FIGURE 1 MODEL NUMBER EXPLANATION R C H 24 17 S T A V U A * OPTION CODE *TBD MINOR SERIES** A - 1 ST DESIGN CASING U - UNCASED ORIENTATION M - MULTIPOISE V - VERTICAL ONLY/ V - CONVERTIBLE** H - DED. HORIZONTAL ONLY MAJOR SERIES A - 1 ST DESIGN METERING DEVICE T - TXV P - PISTON E - EEV EFFICIENCY S - STANDARD EFF. H - HIGH EFF. M - MID EFF. WIDTH 14-14 21-21 17-17.5 24-24.5 CAPACITY 24-2 TON 48-4 TON 36-3 TON 60-5 TON TYPE F - FURN COIL H - AIR HANDLER COIL PRODUCT CATEGORY C - EVAP COIL BRAND R - RHEEM/RUUD All replacement coils for HM and AU air handler applications will be HU. **Convertible to horizontal using parts from original coil or using RXHH horizontal adapter kit. GENERAL (-)CH is a replacement only uncased coil. (-)CH replacement coils are used only in (- )HKL, (- )HLL, (- )HLP, (- )HML, (- )HPL, (- )HPN, ( -)HSL, (-)H1P, (- )H1T, (- )H2T, (- )H1V, and (- )H2V R 410A air handlers. For horizontal applications, a horizontal drip shield and water management parts (see Figure 2) must be installed to catch excess condensate drainage. COIL END SHIELDS All uncased replacement coils come equipped from the factory with sheet metal shields at the front and rear of the coil. The purpose of these shields is to isolate the aluminum tubing from copper residue left on the foil insulation by the original copper tube coil. Copper residue or copper oxide in FIGURE 2 PARTS TO BE REUSED ON HORIZONTAL COILS ONLY. ST-A1213 TABLE 1 R-410A UNCASED COILS: (-)CSL- ACCESSORY INFORMATION Replacement R-410A Uncased Coil Original Coil Horizontal Adapter Kit Model Number RCH2417STAVUA RCSL-HU2417CU RXHH-A02 RCH2421MTAVUA RCSL-HU2621CU RXHH-A03 RCH3617STAVUA RCSL-HU3617CU RXHH-A03 RCH3621STAVUA RCSL-HU3621CU RXHH-A03 RCH3621MTAVUA RCSL-HU3821CU RXHH-A04 RCH3624MTAVUA RCSL-HU3824CU RXHH-A04 RCH4821STAVUA RCSL-HU4821CU RXHH-A04 RCH4821MTAVUA RXHH-A04 RCH4824STAVUA RCSL-HU4824CU RXHH-A04 RCH6024STAVUA RCSL-HU6024CU RXHH-A05 RCH2421HTAVUA RCSN-HU2421CU RXHH-A03 RCH3624HTAVUA RCSN-HU3624CU RXHH-A05 RCH4824HTAVUA RCSN-HU4824CU RXHH-A05 RCH6021STAVUA RXHH-A06 RCH6024HTAVUA RCSN-HU6024CU RXHH-A05 RCH2417SPAVUA RCSP-HU2417CU RXHH-A02 RCH3617SPAVUA RCSP-HU3617CU RXHH-A03 RCH4821SPAVUA RCSP-HU4821CU RXHH-A04 RCH2417SPBMUA RXHH-A02 RCH3617SPBMUA RXHH-A03 RCH4821SPBMUA RXHH-A04 RCH2417SEAVUA RXHH-A02 RCH2421MEAVUA RXHH-A03 RCH3617SEAVUA RXHH-A03 RCH3621SEAVUA RXHH-A03 RCH3621MEAVUA RXHH-A04 RCH6021SEAVUA RXHH-A06 RCH6024MEAVUA RXHH-A05 2

FIGURE 3 BULB LOCATION FIGURE 4 BULB LOCATION 10 O CLOCK 2 O CLOCK BULB VAPOR LINE BULB contact with the aluminum tubing in the presence of moisture will result in galvanice corrosion and leaks in the aluminum tube at the contact point. The shields must be in place on the coil when replacing a copper tube coil to prevent the galvanic corrosion. REFRIGERANT CONNECTIONS Keep the coil connections sealed until refrigerant connections are to be made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information. Coil is shipped with a low (5-10 PSIG) pressure charge of dry nitrogen. Evacuate the system before charging with refrigerant. Install refrigerant tubing so that it does not block service access to the front of the unit. Nitrogen should flow through the refrigerant lines while brazing. Use a brazing shield to protect the cabinet s paint from being damaged by torch flames. After the refrigerant connections are made, seal the gap around the connections with pressure sensitive gasket. If necessary, cut the gasket into two pieces for a better seal. TEV SENSING BULB IMPORTANT: DO NOT perform any soldering with the TEV bulb attached to any line. After soldering operations have been completed, clamp the TEV bulb securely on the suction line at the 10 to 2 o clock position with the strap provided in the parts bag. Insulate the TEV sensing bulb and suction line with the provided pressure sensitive insulation (size 4 x 7 ) and secure with provided wire ties. IMPORTANT: TEV sensing bulb should be located on a horizontal section of copper suction line, just outside of coil box. The copper sensing bulb must never be placed on any aluminum tube as this will result in galvanic corrosion and eventual failure of the aluminum tube. ELECTRONIC EXPANSION The RCF EXV equipped coils, cased and uncased, are the first Rheem indoor products to be produced with the noncommunicating, stand-alone EXV control. One of the biggest advantages of an EXV is the control can intelligently change the EXV position based on system demands other than just suction line temperature. By the measurement of the suction pressure via the vapor line pressure transducer (factory installed) and the vapor line thermistor (field connected to the vapor line, but factory provided within the air handler) the EcoNet enabled air handler control calculates the suction superheat at the indoor coil. This calculation permits the air handler control to make decisions for when to open and close the electronic expansion valve for the purpose of maintaining a predetermined suction superheat. The electronic valve is equipped with a 4-pole removable external stator, and inlet and outlet Chatleff fittings for optimal serviceability. These valves also have an internal check valve to provide heat pump compatibility. When operating in heating mode, the air handler control will open the electronic valve completely to permit the check valve to operate and maximize reverse refrigerant flow. EXV VAPOR LINE THERMISTOR! NOTICE THE VAPOR LINE THERMISTOR DOES NOT COME WITH THE REPLACEMENT COILS. REMOVE THE THERMISTOR FROM THE ORIGINAL COIL AND INSTALL ON THE NEW COIL. IMPORTANT: DO NOT perform any brazing with the vapor line thermistor attached to any line. After brazing operations have been completed, clamp the vapor line thermistor securely on the vapor line at the 10 to 2 o clock position with the clip provided on the thermistor. Insulate the vapor line thermistor and vapor line with the provided pressure sensitive insulation (size 4 x 7 ) and secure with provided wire ties. Make sure to protect the EXV pressure transducer, vapor thermistor, copper to aluminum joint, and service valves from overheating by use of wet rag or some type of shielding. Double tip torches are not recommended. IMPORTANT: Vapor line thermistor should be located on a horizontal section of vapor line, just outside of coil box. The copper thermistor must never be placed on any aluminum tube as this will result in galvanic corrosion and eventual failure of the aluminum tube. IMPORTANT: Never place the thermistor on the heat effected zone near the braze connection, but it should be located within 6 of the indoor unit. 3

FIGURE 5 THERMISTOR LOCATION 10 O CLOCK 2 O CLOCK VAPOR LINE THERMISTOR VAPOR LINE THERMISTOR VAPOR LINE FIGURE 6 THERMISTOR LOCATION 4

FACTORY PROGRAMMED SUPERHEAT The stand alone EXV control is pre-programmed for 10 F superheat. The following dip switch settings must be set at the time of coil installation. Air Handler Outdoor Unit Superheat Dipswitch Settings ( F) 1 2 RCF2417SE RP1724 6 ON OFF RCF2421ME RA1724, RA2024, RP2024 6 ON OFF RCF3617SE RP1736 6 ON OFF RCF3621ME RA1736 8 OFF ON RA1748 RCF6021SE RA2036, RA2048, RA2060 6 ON OFF RP2036, RP2048, RP2060 RCF6024ME RA1660 6 ON OFF SUPERHEAT OFFSET DIP SWITCH SETTINGS Although the above superheat set point is considered to be the most efficient set point for each air handler, installation conditions can drastically effect the measurement of superheat by the air handler control. For this reason the following dip switch settings have been provided to enable flexibility for various installation conditions. Superheat Offset Selection Profile Superheat Setting ( F) A 10 B 6 C 8 D 12 EXV STEP DIP SWITCH The EXV dip switch has an optional 500 or 1600 steps setting. This dipswitch should currently be in the 500 step position only. Rheem does not currently supply 1600 step EXV s. The dipswitch makes the control forward compatible with a 1600 step EXV for possible future use. 1 2 1 2 1 2 1 2 O N O N O N O N A B C D DIAGNOSTICS There are 2 LEDs (green/yellow) on the standalone EXV control which indicate valve movement. When the green LED is illuminated, the control is moving the valve in the open direction. When the yellow LED is illuminated, the control is moving the valve in the closed direction. When neither LED is illuminated, the valve is not being moved by the control. In addition to the diagnostic lights on the control, it is possible to feel the coil on the EXV pulse when the control is attempting to change the EXV position. Status LED Board Fault Only suction temperature valid suction pressure nor coil 1 temperature are valid 2 No Valid Suction Temperature 3 Valve near open position 4 Suction pressure out of range 5

EXV STANDALONE CONTROL PHYSICAL INTERFACE FIGURE 7 EXV ENABLED COIL WIRING DIAGRAM 2 3 4 5 1 8 1. Thermostat Connection 2. Yellow LED (close) 3. Green LED (open) 4. Red LED (status) 5. Dip Switch (EXV steps, 2 & 3 SH adjustment dip switch) 7 6 6. Electronic Expansion Valve Connection 7. Suction and Coil Thermistor Connection 8. Suction Pressure Transducer Connection EXV STANDALONE CONTROL OPTIONAL MOUNTING LOCATIONS! NOTICE THE STANDALONE EXV CONTROL, VAPOR LINE THERMISTOR, PRESSURE TRANSDUCER, AND WIRING HARNESSES DO NOT COME WITH THE UNCASED REPLACEMENT COILS. REMOVE THESE COMPONENTS FROM THE ORIGINAL COIL AND INSTALL ON THE NEW COIL. FIGURE 8 OPTIONAL CONTROL INSTALLATION LOCATION ST-A1246-01_S2 6

The EXV standalone control and housing is factory installed inside the case on the tube sheet. This location has been tested and approved for long term operation inside the highly humid environment. In the event servicing the EXV control without opening the coil door or to see the operational lights while the system is in operation the following alternate control and housing location is approved. The mounting location will require the wiring harnesses to be disconnected from the control, the control removed from the housing and the housing mounting screws removed. The wires will need to be routed through the knockout (there is one knockout per side) and then the assembly reassembled externally to the coil case. IMPORTANT: It is recommended to place aluminum tape over the screw holes in the tube sheet to prevent bypass air. FIGURE 9 FACTORY CONTROL INSTALLATION LOCATION ST-A1246-01_S1 EXV STANDALONE WIRING! NOTICE THE STANDALONE EXV CONTROL, VAPOR LINE THERMISTOR, PRESSURE TRANSDUCER, AND WIRING HARNESSES DO NOT COME WITH THE UNCASED REPLACEMENT COILS. REMOVE THESE COMPONENTS FROM THE ORIGINAL COIL AND INSTALL ON THE NEW COIL. For proper operation the standalone EXV control requires 24VAC power and staged operation thermostat signals. The following diagram should be used to connect the flying leads provided with the cased coil to the thermostat wiring. When employed with the Econet Communicating System attach the flying leads provided with the cased coil to the legacy thermostat outputs on the Econet compatible IFC. 7

GND WIRING DIAGRAM NOTES WIRING INFORMATION SUCTION PRESSURE COIL TEMP. SUCTION TEMP. EXV MOTOR SS SH1 SH2 R BR Y Y/BL R C Y1Y2 STATUS OPEN CLOSE 1... CONNECTORS SUITABLE FOR USE WITH COPPER CONDUCTORS ONLY. 2... LOW VOLTAGE CIRCUIT TO BE N.E.C. CLASS 2 WITH A CLASS 2 TRANSFORMAER 24 VOLT, 50 OR 60 HZ. MIN 18 AWG. 3... TO THERMOSTAT, REFER TO SYSTEM SCHEMATICS OR SCHEMATICS ON FURNACE FOR LOW VOLTAGE CONTROL WIRING. LINE VOLTAGE -FACTORY STANDARD -FACTORY OPTION -FIELD INSTALLED LOW VOLTAGE -FACTORY STANDARD -FIELD INSTALLED REPLACEMENT WIRE -MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (105C. MIN.) WARNING -CABINET MUST BE PERMANENTLY GROUNDED AND CONFORM TO I.E.C., N.E.C., C.E.C., NATIONAL WIRING REGULATIONS, AND LOCAL CODES AS APPLICABLE. SCHEMATIC DIAGRAM T M SUCTION PRESSURE COIL TEMP. SUCTION TEMP. EXV MOTOR SS SH1 SH2 R BR Y Y/BL R C Y1Y2 STATUS OPEN CLOSE COMPONENT CODES CLOSE...YELLOW LED COIL TEMP...COIL INLET THERMISTER CONNECTION COMP...COMPRESSOR EXV (5 PIN)...ELEC. TX VALVE ODF...OUTDOOR FAN CONNECTION OPEN...GREEN LED SH1...SUPERHEAT OFFSET SWITCH 1 SH2...SUPERHEAT OFFSET SWITCH 2 SS...EXV STEP SELECTION (MUST REMAIN OFF) STATUS...RED LED SUCTION PRESSURE...SUCTION PRESS. TRANSDUCER CONN. SUCTION TEMP....VAPOR LINE THERMISTOR CONN. TM...THERMISTOR RVS...REVERSING VALVE CONN. WIRE COLOR CODE BK...BLACK G...GREEN PR...PURPLE BR...BROWN G Y...GRAY R...RED BL...BLUE O...ORANGE W...WHITE Y...YELLOW ELECTRICAL WIRING DIAGRAM NON-COMMUNICATING STANDALONE EXV CONTROL W/ PRESSURE TRANSDUCER PART NO.: 90-101897-09 REV: 00 FLOW CHECK PISTON! NOTICE FOR PROPER SYSTEM OPERATION, IT MAY BE NECESSARY TO REPLACE THE PISTON INSTALLED IN THE INDOOR COIL. CHECK THE SERVICE VALVES ON THIS UNIT TO SEE IF A NOTICE TAG ALONG WITH A PLASTIC BAG CONTAINING A PISTON IS ATTACHED. IF ONE IS PRESENT A CHANGE OF THE PISTON IS REQUIRED. FAILURE TO CHANGE THE PISTON CAN RESULT IN IMPROPER PERFORMANCE OF THE SYSTEM. The flow check piston is a multi-purpose device. With flow into the compression nut end from the liquid line, the piston is in a check position and acts as the expansion device with flow through the metering orifice in the center of the piston. The O ring on the end of the piston prevents refrigerant from bypassing the metering orifice. Flow from the metering orifice is centered into a distributor which serves to evenly distribute refrigerant to the evaporator circuits. With flow in the reverse direction (direction of arrows on the distributor body), the piston is forced off the seat and liquid from the condenser is allowed to free flow around the piston. It is essential that the heat pump indoor and outdoor sections be properly matched. Use only matched components as shown in sales specification sheets. A piston size that is too small will cause starving and one that is too large will cause flooding. In either case, system performance, reliability and charge balance (heating and cooling) will be unacceptable. Change the piston in the distributor on the indoor coil before installing the coil and charging the system following the procedure below: Using a back-up wrench on the distributor body, loosen the compression nut to gain access to the piston. Using the wire provided with replacement pistons, run (hooked end) through hole in piston. Hook nose end of piston and lift gently from distributor body. Replace piston with one of proper size (see Table 4), install piston with gasket end of piston in distributor. Do not force piston into distributor. NOTE: With piston in distributor, seal end should be down and should not be seen looking in end of distributor. Piston must be free to rotate and move up and down. Make sure piston is free to move in distributor body. Insure distributor gasket is located properly in the distributor body. 8

Replace compression nut using back-up wrench on distributor body. Torque compression nut end with 8 to 10 ft. lbs. Original piston size is stamped on outside of distributor body. Remove new piston size label from poly bag new piston came in and install new size label on outside of distributor tube. Check fittings for leaks after installation, evacuation and charging is complete. IMPORTANT: Do not attempt to drill pistons to size in the field. Metering holes have a special chamfered inlet and cannot be modified. IMPORTANT: Do not replace the neoprene O ring on the piston with any type of seal. Contact the parts department for the exactly replacement of O ring. FIGURE 10 PISTON AND DISTRIBUTOR ASSEMBLY TABLE 2 R-22 TXV CONVERSION KITS (TO BE USED TO CONVERT R-410A COIL TO OPERATE WITH R-22) AIR HANDLER CROSS REFERENCE CHART RECOMMENDED ORIGINAL AIR ORIGINAL AIR ALUMINUM TUBE R-22 TXV HANDLER HANDLER COIL REPLACEMENT COIL CONVERSION KIT (R-410A) MODEL NO. RHSA-**1817 RCSA-**2417 RCH2417STA RXCT-HBA RHSA-**2417 RCSA-**2417 RCH2417STA RXCT-HBA RHLA-**2417 RCSA-**2417 RCH2417STA RXCT-HBA RHSA-**3017 RCSA-**3617 RCH3617STA RXCT-HBB RHSA-**3617 RCSA-**3617 RCH3617STA RXCT-HBB RHLA-**3617 RCSA-**3617 RCH3617STA RXCT-HBB RCH3621STA, RHSA-**3621 RCSA-**3621 RCH2421MTA, or RXCT-HBB RHSA-**4221 RCSA-**4821 RCH2421HTA RCH4821STA or RCH3621MTA RXCT-HBC RHSA-**4821 RCSA-**4821 RCH4821STA or RCH3621MTA RXCT-HBC RHLA-**4821 RCSA-**4821 RCH4821STA or RCH3621MTA RXCT-HBC RHSA-**4824 RCSA-**4824 RCH4824STA or RCH4824MTA RXCT-HBC RHLA-**4824 RCSA-**4824 RCH4824STA or RCH4824MTA RXCT-HBC RHSA-**6024 RCSA-**6024 RCH6024STA, RCH6024HTA, RCH4824HTA, or RXCT-HBD RHLA-**6024 RCSA-**6024 RCH3624HTA RCH6024STA, RCH6024HTA, RCH4824HTA, or RXCT-HBD RCH3624HTA **= AU, HM, OR HU 9

10

11

12 CM 0516