RD-2000 Round Control Dampers

Similar documents
RM-1200 Slim Round Control Damper

RA-2000 Airflow Measuring System

ID-141x 12-Gauge Hat Channel Industrial Damper

SD-1250 and SD-1600 Series Smoke Dampers

BD-1600 Balancing/Zone Control Damper

VD-1600 Series Volume Control Dampers

PC-125x Counter-Balanced Backdraft Damper

AD-1250 Airflow Measuring Station

Introduction to Johnson Controls Dampers

AD-1251 Probe with Differential Pressure Transducer

M x Series Cast Iron Flanged Valve Linkage Kit for M9000 Series Electric Actuators

M9210-xxx-3 Electric Spring Return Actuators

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Metasys Zoning Package Overview

VG7000 Series Bronze Control Valves

AV-8020 Series Floating Control Actuated Valve

M9220-xxx-3 Electric Spring Return Actuators

Installation Instructions

PP1 Series Piping Packages for VG1000 Series Ball Valves

V-9502 Series Pneumatic Valve Actuator Positioners

M Ball Valve Linkage Kit

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

D-4070 Two Stage Pneumatic Actuator

M9000-3xx Series Weather Shield Enclosures

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

DRUM LOUVERS DRUM LOUVERS 45DL SERIES. Models: 45DL1 Single Vanes 45DL2 Split Vanes G151 HIGH CAPACITY LONG THROW ALUMINUM CONSTRUCTION

HCD-230 Industrial Control Damper

M x Series Valve Linkage Kits

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

Flare Valves 1/2 inch 2-Way and 3-Way

AMD-33 Air Measuring Station with VCD-33 Control Damper

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

VF Series M9000 Electrically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves

VA-715x Electric Valve Actuator

Metasys Zoning Package

M9203-xxx-2(Z) Series Electric Spring Return Actuators

M x Cast Iron Flanged Valve Linkage Kit for Mounting a Single M9000 Series Electric Actuator

M x Series Valve Linkage Kits

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

VG7000 Female Threaded Cast Bronze Valve Series with Electric Actuators

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

M9109 Series Electric Non-spring Return Actuators

M9208-xxx-x Series Electric Spring Return Actuators

A25 Series Warm Air Control with Manual Reset

M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

VA-4233-GGx Series Electric Valve Actuators

M x Series Cast Iron Flanged Valve Linkage Kit for Tandem Mounting of M9000 Series Electric Actuators

VF Series Standard-Pressure, Standard-Temperature Butterfly Valves

M9300 Series Electric Non-Spring Return Actuators

VF Series Standard-Pressure, Standard-Temperature Butterfly Valves

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

P70, P72, and P170 Controls for Low Pressure Applications

P10 Series Low Range Pressure Controls

SafidDampers SPK Standard Construction SPK Description SPK ( Flange Type )

VA-8020 Floating Valve Actuator

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

M Remote Mounting Kit

R-317 Air Flow Controller

CONTROL DAMPERS. Models 1810 & Model Model Model 1370

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

SECTION CONTROL DAMPERS

M Valve Actuator Weather Shield Kit

LINEAR DIFFUSERS AND BAR GRILLES

TE-6300 Series Temperature Sensors

Series Y63, Y64, Y65, Y66, and Y69 Transformers

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators

VG9000 Flanged Valves

M Ball Valve Linkage Kit

Q35 Series Automatic Vent Damper System

Section Va: Valve Actuators

P70, P72 and P170 Series Controls for High Pressure Applications

Air Measuring Products AMD AMS IAQ

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

VA-7450 Series. Electric Valve Actuators

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

SP Standard Profile. In Duct or Flanged to Duct Install Types OPPOSED ACTION PARALLEL ACTION. Extended Rear Flange Install Type

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

ARROW INDUSTRIAL PRODUCTS

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper.

VF Series Standard-Pressure, Standard-Temperature Butterfly Valves

VT Series Terminal Unit Valves 1/2 inch, 2-Way and 3-Way ANSI Class 250 Body Rating

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations.

Thermal Isolation. Break

FADE SERIES. Typical Specifications for Model FADE Sidewall Propeller Fans Sidewall propeller fans shall be of the direct driven type.

Transcription:

RD-000 Round Control Dampers Product Bulletin Code No. LIT-8105 Issued February 5, 010 Supersedes July, 009 Johnson Controls provides top-quality, low-leakage RD-000 Round Control Dampers for use in Heating, Ventilating, and Air Conditioning (HVAC) systems that fit your size and application requirements. Round dampers are available with seals for low-leakage control dampers and are easily installed in round ducts. Round dampers are available with or without a factoryinstalled actuator. Figure 1: RD-000 Damper (Shown with Option B) Table 1: Features and Benefits Features Formed Shroud Available Factory-Installed One-Piece Construction Benefits Inserts easily into round ductwork. Reduces installation time. Increases rigidity and strength. RD-000 Round Control Dampers Product Bulletin 1

Sample Specifications Furnish and install round control dampers manufactured by Johnson Controls. Damper shrouds are to be constructed of formed 0-gauge galvanized steel, mechanically joined. Blade rotation shall not exceed 80 degrees. Damper blades are to be constructed with 1-piece or -piece 1-gauge or 0-gauge galvanized steel, determined by size. Damper performance shall be designed for tight shutoff. Leakage rating at in. Water Gauge (w.g.) differential pressure with 5 lb in./sq ft closing torque shall not exceed 10 cfm per square foot. Dampers without actuators must be rated to operate over a temperature range of -0 to 00 F (-9 to 93 C). Damper sizing shall be by the designer in accordance with accepted industry practices to ensure proper system performance. Factory-installed electric and pneumatic actuators are available. Construction All dimensions are the same for the 0-gauge (1 mm) galvanized, 03-T5 aluminum (Class I only) and 30 stainless steel products. The shroud is made of -inch (15 mm) long, 0-gauge (1 mm) material. Blades are made of single-piece 1-gauge or two layers of 1-gauge material matching the shroud. Blade arm is 1/ in. (13 mm) diameter material matching the shroud. The length of the blade arm is the full width of the diameter of the damper with an additional in (15 mm) extending beyond the shroud. Balancing dampers have no seals. Class II leakage control dampers have an Ethylene Propylene Diene M-class (EPDM) rubber seal adhered to the shroud. Class I leakage dampers have an EPDM seal sandwiched between the two sides of the blades. The seal fully encompasses the blade edge. Damper Shroud FIG:dmpr_cmpnnts Blade Arm Damper Blade Damper Seal Blade Arm Figure : Damper Components RD-000 Round Control Dampers Product Bulletin

Dimensions Top View in. (15 mm) 3-13/1 in. (97 mm) 5-7/8 in. 19 mm Reference FIG:elec_act Face View Side View Figure 3: Damper with Electric Dimensions, in. (mm) Top View 1-1/ in. (318 mm) 5-7/8 in. 19 mm Reference -3/ in. (171 mm) 1-7/1 in. (37 mm) Face View Side View FIG:pneu_act Figure : Damper with Pneumatic Dimensions, in. (mm) RD-000 Round Control Dampers Product Bulletin 3

Table : Approximate Weight, lb (kg) Damper Diameter Without Selection Information With M910 Not all combinations are available, check the selector tool software application for valid combinations. With M90 With M910 or M90 With D-30 in. 1.1 (0.5) 3.5 (1.) 7.5 (3.) 8.7 (3.3) 3.5 (1.) 8 in..9 (1.3) 5.3 (.) 9.3 (.) 10.5 (.1) 5.5 (.5) 1 in. 8.0 (3.) 10. (.7) 1. (.5) 15. (.) 10.5 (.8) 1 in. 1.0 (.3) 1. (7.) 0. (9.) 1. (9.1) 1.5 (7.5) 0 in..5 (10.).9 (11.3) 8.9 (13.1) 30.1 (13.0) 5.0 (11.3) in..5 (1.0) 8.9 (13.1) 3.9 (1.9) 3.1 (1.8) 9.0 (13.) Table 3: Damper Selector Code Number R C G d d N Product R = Round dampers Family Application B = Balancing (no seals) C = Control (Class II) L = Low Leakage Control (Class I) Shroud Type A = Aluminum (Class I only) G = Galvanized steel S = Stainless steel (30) Diameter to in., 1 in. increments 1 Control Signal Operation B = Bracket with no actuator E = Electric non-spring return M = Manual locking quadrant N = None P = Pneumatic, D-30 S = Spring return electric B = Floating with two Single-Pole Double-Throw (SPDT) auxiliary switches E = Proportional with two SPDT auxiliary switches R = 8-13 lb spring range NC = Normally Closed NO = Normally Open 1. Based on torque requirements, RCG construction dampers use M910 or M90 actuators on all sizes, and RLG construction dampers use M910 and M90 actuators on all sizes. RD-000 Round Control Dampers Product Bulletin

Pressure Drop To determine static pressure drop through an open damper, enter the Damper Pressure Drop chart (Figure 5) on the left side. Given the CFM airflow through the damper, follow that CFM line to the diagonal line for the damper size required, then down to the static pressure drop of that damper size. For example, the pressure drop of an 8-inch diameter damper with 700 CFM airflow is 0.0 inches w.g. 100,000 9 8 7 Airflow in CFM 5 3 10,000 9 8 7 5 3 in. diameter damper 0 in. diameter damper 1 in. diameter damper 1 in. diameter damper 8 in. diameter damper FIG:stat_prssr_drp 1,000 9 8 7 5 3 100.01.0.03.0.05.0.07.08.09.1..3..5..7.8.9 1.0 Static Pressure Drop (Inches W.G.) Figure 5: Damper Pressure Drop RD-000 Round Control Dampers Product Bulletin 5

Repair Information If the RD-000 Round Control Damper fails to operate within its specifications, replace the unit. For a replacement RD-000 Damper, contact the nearest Johnson Controls representative. Technical Specifications RD-000 Round Control Dampers 1 RCG Construction RLA, RLG, and RLS Construction Leakage per in. diameter 1 in. static pressure.1.079 in. static pressure.55.1 in. static pressure.8.15 Pressure Drop (in. w.g. at 8 in. diameter damper.1 1,000 fpm) 1 in. diameter damper.01 1 in. diameter damper.001 0 in. diameter damper.001 Torque Required to 8 in. diameter damper 5 lb in maximum for Closing at 1,500 fpm Velocity 9 to 1 in. diameter damper 8 lb in maximum 17 to in. diameter damper 11 lb in maximum Leakage Class I RLG Construction Class II RCG Construction Not Rated RBG Construction Electric M910 and M90: Running and breakaway torque 53 lb in ( N m) M911 and M90: Running and breakaway torque 10 lb in (1 N m) Pneumatic control pressure: 5 psig (17 kpa) Temperature Limits without actuator -0 to 00 F (-9 to 93 C) with electric actuator 35 to 15 F ( to 5 C) with pneumatic actuator -0 to 150 F (-9 to C) 1. Dampers are tested using instrumentation and procedures in accordance with AMCA Standard No. 500, Test Methods for Louvers, Dampers, and Shutters. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 530 Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 010 Johnson Controls, Inc. RD-000 Round Control Dampers Product Bulletin Published in U.S.A. www.johnsoncontrols.com