GE Industrial Solutions Retrofill Door Assemblies for AKD-5, AKD-6, AKD-8 and AKD-10

Similar documents
Programmer Disconnect Accessory Manual for Retrofil CB

Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers

Finger Cluster Replacement Parts Primary Disconnects for EntelliGuard* Retrofill Circuit Breakers

Operation and Maintenance Manual

EntelliGuard R Retrofill Application Guide

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

EntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

Power delivery for industrial facilities

GE Industrial Solutions. EntellEon * Low-Voltage Power Panel. Simple. Responsive. Revolutionary.

Distribution Cable Harness For Spectra RMS Molded-Case Circuit Breakers with microentelliguard TM, MicroVersaTrip PM or MicroVersaTrip Plus Trip Units

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

Installation, Operation, and Maintenance Manual Retain for Future Use. EntelliGuard G Circuit Breaker

Zone Selective Interlock Module. For GE Circuit Breakers

Power Break II Switchboard

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

DEF 005. WavePro Power Circuit Breakers A Frames, Vac. Renewal Parts

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

TIME REQUIREMENT GUIDE (TRG)

Introduction. Installation. A Series Lighting Control Panelboards. DEH41081 Installation Instructions

Factory Authorized Mechanism Enhancement (FAME)

ABB Power Products Medium Voltage MV SERVICE. Florence, SC Napa, CA Coral Springs, FL. ABB Inc. -1- March, 2007

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

www. ElectricalPartManuals. com

SecoVac * R Retrofill

SecoVac * Ground & Test Device

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits For GE Types AK-25 and AKU-25 Low Voltage Power Circuit Breakers

User s Manual. Automatic Switch-Mode Battery Charger

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

GEH-6259 Installation Instructions Voltage Conditioner Assembly

Record Plus. Molded Case Circuit Breaker Accessories. Plug In Base. DEH40915 Installation Instructions

Quick Connection Panel (QCP) Installation Guide

Company Switch Installation Instructions and User Manual

Effective November 2016 Supersedes September 1998 (S )

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

GEF Renewal Pans. low Vohage Power Circuit Breakers. Type AKR-30S and AKRU-30S. www. ElectricalPartManuals. com

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Power/Vac OEM Express Switchgear

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

GE Industrial Solutions Power Protection. LV Switchgear SEN Plus

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Frame Sizes: AKJ/ AKJT I AKJU-50 and AKR/ AKRU-30/ 50, AKRT-50

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Low Voltage Power Circuit Breakers

INSTALLATION MANUAL ELECTRIC DOUBLE OVEN RANGE

SecoVac * Vacuum Circuit Breaker

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Controlled Power HSN High Speed DC Circuit Breakers

Electric Range installation manual

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

SecoVac * R Retrofill Vacuum Circuit Breaker

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

www. ElectricalPartManuals. com Section 6 Low Voltage Power and DC Circuit Breakers

Installation Instructions For Motor Control Center (MCC) Units

University of Houston Master Construction Specifications Insert Project Name

Eilat, 11/2017. Cost Effective switchgear Modernization solutions

6900-( )-( ) HIGH SPEED SANDWICH PRESS

Power Break Circuit Breakers

Air Circuit Breaker Retrofitting

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

MEDIUM VOLTAGE PRODUCTS

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN

Automatic Burnout Furnaces 115 to 230-volt Models OPERATOR S MANUAL

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

Technical Specificaions. kwh Energy Meter

Florham Park, NJ USA Call (ASCO) for sales or service

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS

Operator Manual. This operator manual has. information for all models. of series M plus some. options and accessories. Some of the illustrations

Tenant Main Circuit Breakers. for GE Meter Mod * III Modular Metering

MOULDED CASE CIRCUIT BREAKERS 16A TO 630A

Operating instructions Actuator and Emergency exit AZ/AZM 200-B30 AZ/AZM 201-B About this document. Content

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Florham Park, NJ USA Call (ASCO) for sales or service

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

Vacuum Circuit Breakers (Vehicle)

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

Original. User Manual & Install Guide. Safe-T-Pull Inc. Page 1 of 15

Cradle Mounted Key Interlock Guide Frame Accessory

Quick Start Guide TS 910 & TS 920

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

Freedom egen System End-of- Line Functional Checklist

Transcription:

GE Industrial Solutions Retrofill Door Assemblies for AKD-5, AKD-6, AKD-8 and AKD-10 New doors can be ordered for GE Switchgear based on Switchgear type, Legacy Breaker type being replaced, and door size. Doors are available with & without cutouts for accommodating original lamps and ammeters.

Table of Contents Related Publications... 2 Doors, Retrofit Ordering and Replacement... 3 Danger... 3 AKD-5, AK25 Retrofit Door... 4 20-Inch, 22-Inch, 27-Inch Door (AKD5, AK25)... 4,6 7, 8 AKD-5, AK50, AK-75, AK-100 Retrofit Door... 9,10,11 Replace AKD5 Door... 12 Modify Existing Door... 12,13, 14 AKD-6, AKR-75, AKR-100 Retrofit Door... 15, 16, 17 Replacing AKD6 Doors... 18 Modifying Existing Doors... 18 AKD-8 / 10, AKR30S, AKR30H, AKR 30/50, AKR-75, AKRH-75,AKRH-100, AKR-125 Retrofit Door Assemblies... 19,20,21 Replacing AKD8/10 Door Assembly... 22 Modifying Existing Door... 23 Retrofill Escutcheon Kit Spare... 25 Notes... 26 1 of 27

Related Publications Related Publications Brochure Snapshot Installation Manual AKD8 Installation Manual AKD10 Installation Manual AKD6 Installation Manual AKD5 Accessory: Door Interlock (Door Interlock Kit) Accessory Retrofill Doors Assembly Accessory: Position Switch Plate & Position Switch Assembly & Wiring (Position Switch Kit) Accessory: Neutral Rogowski CT Disconnect (Neutral Assemblies) Accessory: Programmer Disconnects Accessory: Finger Clusters (Cluster Assemblies) Accessory: Secondary Disconnects FAQ Application Guide Guideform Spec Spare/Renewal Parts Guide Publication Number DEA-532 DEE-543 DEH-41549 DEH-41550 DEH-41548 DEH-41547 DEH-41529 DEH-41530 DEH-41531 DEH-41532 DEH-41533 DEH-41534 DEQ-171 DET-753 DET-754 DET-755 2 of 27

Doors, Retrofit Ordering and Replacement Danger Turn off all power to switchgear. Tagout and lockout main source, up-stream or main breaker. Failure to comply with these instructions will result in death or serious injury from severe burns caused by arc flashing that has exceedingly high temperatures. Always wear personal protection equipment according to OSHA standards and appropriate to the severity of potential burns. Ensure only qualified personnel install, operate, service, and maintain all electrical equipment. It takes about 5 to 15 minutes to install the retrofill door(s) in the switchgear, but does not include the 20-minute timing claimed for the roll-in replacement. 3 of 27

AKD-5, AK25 Retrofit Door Retrofit doors for the can be ordered as required, depending on door size and if you want door cutouts for accommodating lamps and ammeters (Figure 1 and Figure 2). In this section, the particular wireframe figures feature different door sizes. Table 1 lets you specify a door type. It can be ordered by catalogue number by referring to the last column in the table. Some doors allow cutouts for lamps and/or ammeters; some do not. All the doors in Table 1 are right-hand doors. 20-Inch Door (AKD5, AK25) Figure 1. AK25 (20-inch door assembly) with and without Cutouts for Lights 4 of 27

Figure 2. AK25 (20-inch door assembly) with Cutouts for Lights and Accessories 22-Inch Door (AKD5, AK25) Figure 3 displays 22-inch door assemblies, with and without cutouts for lights. The next figure, Figure 4 displays cutouts for both lights and accessories. Figure 3. AK25 (22-inch door assembly) with and without Cutouts for Lights 5 of 27

Figure 4. AK25 (22-inch door assembly) with Cutouts for Lights and Accessories 27-Inch Door (AKD5, AK25) Figure 5 displays 27-inch door assemblies, with and without cutouts for lights. The next figure, Figure 6, displays cutouts for both lights and accessories. 6 of 27

Figure 5. AK25 (27-inch door assembly) with and without Cutouts for Lights Figure 6. AK25 (27-inch door assembly) with Cutouts for Lights and Accessories 7 of 27

Table 1. Replacement Door Categories (TOP LEVEL) Description Breaker Type LVS Fascia Cutout Only Cutout Options Plus Lamps Plus Lamps & Ammeter Available Stack Width (in inches) 20 22 27 30 38 Type Door Width (in inches) Door Bumpout (in inches) CAT # AK25 DOOR AK25 DOOR AK25 DOOR AK25 DOOR AK25 DOOR AK25 DOOR AK25 DOOR AK25 DOOR AK25 AKD5 YES YES YES YES RH 27 YES 3.7 10106255G1 AK25 AKD5 YES YES RH 20 YES 3.7 10107429G1 AK25 AKD5 YES YES RH 22 YES 3.7 10108047G1 AK25 AKD5 YES YES RH 20 YES 3.7 10108345G1 AK25 AKD5 YES YES RH 22 YES 3.7 10108347G1 AK25 AKD5 YES YES RH 22 YES 3.7 10108376G1 AK25 AKD5 YES YES YES YES RH 27 YES 3.7 10108380G1 AK25 AKD5 YES YES YES YES RH 27 YES 3.7 10108383G1 8 of 27

27-Inch Door, 30-Inch Door, 38-Inch Door (AKD5, AK50 / AKT50 AK-75, AK-100) Retrofit doors for the can be ordered as required, depending on door size and if you want door cutouts for accommodating lamps and ammeters (Figure 7 and Figure 8). In this section, the particular wireframe figures feature different door sizes. Table 2 lets you select a specific door type. It can be ordered by catalogue number by referring to the last column in the table. Two doors allow cutouts for lamps and/or ammeters; one does not allow any cutouts. All the doors in Table 2 are right-hand doors. Figure 7. SHOWN (AK50 (27-inch door assembly) with and without Cutouts for Lights 9 of 27

Figure 8. AK50 / AKT50 (27-inch door assembly) with Cutouts for Lights and Accessories 10 of 27

Table 2. Replacement Door Categories (TOP LEVEL) Description Breaker Type LVS Fascia Cutout Only Cutout Options Plus Lamps Plus Lamps & Ammeter Available Stack Width (in inches) 20 22 27 30 38 Type Door Width (in inches) Door Bumpout (in inches) CAT # AK50 DOOR AK50 AKT50 AKD 5 YES YES YES YES RH 27 No 10106248G1 AK50 DOOR AK50 AKT50 AKD 5 YES YES YES YES RH 27 No 10108355G1 AK50 DOOR AK50 AKT50 AKD 5 YES YES YES YES RH 27 No 10108363G1 AK75 DOOR AK75 AKD 5 YES YES RH 30 No 10108355G2 AK75 DOOR AK75 AKD 5 YES YES RH 30 No 10108355G4 AK75 DOOR AK75 AKD 5 YES YES RH 30 No 10108355G6 AK100 DOOR AK100 AKD 5 YES YES RH 38 No 10108355G3 AK100 DOOR AK100 AKD 5 YES YES RH 38 No 10108355G4 AK100 DOOR AK100 AKD 5 YES YES RH 38 No 10108355G7 11 of 27

Replace AKD5 Door Sequence of replacement of door assemblies will remain the same for all AKD5 type doors. 1. De-energize/switch off the LVS section that is to be retrofitted. 2. Open the compartment door that is to be retrofitted. 3. Rack out the existing legacy AK/AKR breaker from the LVS. 4. Keep the door open for accessing the door mounting hinges. These are placed on the right side wall of the moving frame in the LVS compartment. 5. The door hinge is mounted via 2/3-mounting pins that hold the door in place. 6. Lift the pin out of the hinge joint. This allows access for removing the old door from the LVS compartment. 7. Unpack the new door assembly and mount it on the door mounting hinges. These are located at the right side of the moving frame. 8. Replace the hinge pins and secure the joints. 9. Insert the new retrofitted EntelliGuard R Retrofill circuit breaker into the compartment and slide the breaker into the disconnected condition. 10. Close the new door and secure it to the compartment. 11. Rack-in the new retrofitted EntelliGuard R Retrofill in. Modify Existing Door If customer doesn t want to buy a new door, the customer can modify the existing door: 1. Remove the legacy door assembly from the LVS section. 2. Modify the door cut out as per the new door cutout template. 3. Check the through-door racking with the new door assembly. AKD-6, AKR, AKR-75, AKR-100 Retrofit Door Retrofit doors for the can be ordered as required, depending on door size and if you want door cutouts for accommodating lamps and ammeters. Table 3 lets you select a specific door type (Figure 9 and Figure 10). In this section, the particular wireframe figures different door 12 of 27

sizes. It can be ordered by catalogue number by referring to the last column in the table. Some doors allow cutouts for lamps and/or ammeters; some do not. All the doors in Table 3 are right-hand doors. 22-Inch, 30-Inch Door (AKD6) Figure 9. AKD6 SHOWN (22-inch door assembly) with and without Cutouts for Lights 13 of 27

Figure 10. AKD6 SHOWN (22-inch door assembly) with Cutouts for Lights and Accessories 14 of 27

27-Inch, 30-Inch Door Sizes (AKD6) For the AKD6, Figure 11 displays the 27-inch door assembly with and without cutouts for lights. Figure 12 shows cutouts or punch-outs for the same door assembly. Figure 11. AKD6 SHOWN (27-inch door assembly) with and without Cutouts for Lights 15 of 27

Figure 12. AKD6 SHOWN (27-inch door assembly with Cutouts for Lights and Accessories 16 of 27

Table 3. Replacement Door Categories (TOP LEVEL) Description Legacy Breaker Type LV Swgr Fascia Cutout Only Cutout Options Plus Lamps Plus Lamps & Ammeter Available Stack Width (in inches) 20 22 27 30 38 Type Door Width (in inches) Door Bumpout (in inches) CAT # AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKD6 DOOR AKR- 30/50/T50 AKR- 30/50/T50 AKR- 30/50/T50 AKR- 30/50/T50 AKR- 30/50/T50 AKR- 30/50/T50 AKR75 AKR100 AKR75 AKR100 AKR75 AKR100 AKD6 YES YES RH 22 No 10107469G1 AKD6 YES YES RH 22 No 10108074G1 AKD6 YES YES RH 22 No 10108439G1 AKD6 YES YES YES YES RH 27 No 10108447G1 AKD6 YES YES YES YES RH 27 No 10108462G1 AKD6 YES YES YES YES RH 27 No 10108469G1 AKD6 YES YES RH 30 No 10108355G2 AKD6 YES YES RH 30 No 10108355G4 AKD6 YES YES RH 30 No 10108355G6 17 of 27

Replacing AKD6 Door Assembly Sequence of replacement of door assemblies will remain the same for all AKD6 type doors. 1. De-energize/switch off the LVS section that is to be retrofitted. 2. Open the compartment door that is to be retrofitted. 3. Rack out the existing legacy AK/AKR breaker from the LVS. 4. Keep the door open for accessing the door mounting hinges. These are placed on the right side wall of the moving frame in the LVS compartment. 5. The door hinge is mounted via 2/3-mounting pins that hold the door in place. [What does the 2/3 mean: size, inches, type, etc.?] [How many pins are there per door?] 6. Lift the pin out of the hinge joint. This will provide access for removing the old door from the LVS compartment. 7. Unpack the new door assembly and mount it on the door mounting hinges. These are placed [found?] [or are they already installed there?] at the right side of the moving frame. 8. Replace the hinge pins and secure the joints. 9. Insert the new retrofitted EntelliGuard R Retrofill circuit breaker into the compartment and slide the breaker into the disconnected condition. 10. Close the new door and secure it to the compartment. 11. Rack-in the new retrofitted EntelliGuard R Retrofill in. [OK, what do I do with the old door? Discard it salvage it for something else?] Modifying Existing Door If customer doesn t want to buy a new door, the customer can modify the existing door: 1. Remove the legacy door assembly from the LVS section. 2. Modify the door cut out as per the new door cutout template. 3. Check the through-door racking with the new door assembly. 18 of 27

AKD-8 / 10, AKR30S, AKR30H, AKR 30/50/, AKR-75, AKRH-75, AKRH-100, AKR-125 Retrofit Door Assemblies Retrofit doors can be ordered as required, depending on door size and if you want door cutouts for accommodating lamps and ammeters (Figure 13, Figure 14, and Figure 15). Table 4 lets you select a specific door type. It can be ordered by catalogue number by referring to the last column in the table. Some doors allow cutouts for lamps and/or ammeters; some do not. All the doors in Table 4 are right-hand doors. 22-Inch, 30-Inch, 38-Inch RH AKD8/10 Figure 13. AKD8/10 SHOWN (22-inch door assembly) see 10106239G2 for BOM Figure 14. AKD8/10 SHOWN (30-inch door assembly) See 10108088G1 for BOM 19 of 27

Figure 15. AKD8 AKR30S (30-inch door assembly) 20 of 27

Table 4. Replacement Door Categories (TOP LEVEL) Description Legacy Breaker Type LV Swgr. Cutout Options Fascia Cutout Only (includes door interlock bracket) Available Stack Width (in inches) 22 30 38 Type Door Width (inches) Door Bump-out (inches) CAT # 22 DOOR AKR30S AKR-30S AKD-8 YES YES RH 22 YES 2.95 10108089G1 30 DOOR AKR30S AKR-30S AKD-8 YES YES RH 30 YES 2.95 10108090G1 22 DOOR, AKD-8 & AKD-10 AKR-30/50/T50 WP-08/16/20 AKD-8 & AKD-10 YES YES RH 22 G1-YES 1 G2-NO 10106239G1/2* 30 DOOR, AKD-8 & AKD-10 AKR-30/50/T50 WP-08/16/20 AKD-8 & AKD-10 YES YES RH 30 NO 10108088G1 30 DOOR, AKD-8 ONLY 38 DOOR, AKD-8 ONLY 30 DOOR, AKD-10 ONLY 38 DOOR, AKD-10 ONLY AKR-75/100 AKD-8 YES YES RH 30 NO 10108088G2 AKR-125 AKD-8 YES YES RH 38 NO 10108088G4 WP-32 & WP-40 AKD-10 YES YES RH 30 NO 10108088G3 WP-50 AKD-10 YES YES RH 38 NO 10108088G5 +Bump-out doors for AKR-30S Retrofills only *G1 -angled bump-out for early Model 1 Retrofills and G2 - later Model 1 s & Model 2 Retrofills for AKR-30/50/T50, and all small frame WavePro. 21 of 27

Replacing AKD-8/10 Door Assembly Figure 16A & B are examples of new retrofill doors for the newly installed retrofill breakers. (Note that the figure16a shows that a motor can power the racking-in of the retrofill breaker.) Figure 16A. Remote Racker Assembled to Retrofill in AKD-8 Figure 17B. New Door Assembled on AKD-10 38"-Door, 5000A Sequence of replacement of door assemblies will remain the same for all AKD8 /10 type doors. 1. De-energize/switch off the LVS section that is to be retrofitted. 2. Open the compartment door that is to be retrofitted. 3. Rack out the existing legacy AK/AKR breaker from the LVS 4. Keep the door open for accessing the door mounting pads placed on the right side wall in the LVS compartment. 22 of 27

5. Loosen the screws holding the mounting pads to the compartment frame. 6. Note that this will provide access for removing the old door from the LVS compartment. 7. Unpack the new door assembly and mount it on the compartment and secure via placing the pads and tightening the screws. 8. Insert the new retrofitted EntelliGuard R Retrofill circuit breaker into the compartment and slide the breaker into the disconnected condition. 9. Close the new door and secure it to the compartment. 10. Rack-in the new retrofitted EntelliGuard R Retrofill circuit breaker in. Modifying Existing Door If customer doesn t want to buy a new door, the customer can modify the existing door: 1. Remove the legacy door assembly from the LVS section. 2. Modify the door cut out as per the new door cutout template. 3. Check the through-door racking with the new door assembly. 23 of 27

Figure 18 shows a legacy breaker in the cabinet with the old doors still attached. Figure 19 shows the retrofill breaker, racked in a compartment, waiting for a retrofill door to be installed. The other three compartment doors have the retrofill doors already, but no retrofill breakers yet. Figure 18. Legacy AK with Old Door Figure 19. AKR with New Door 24 of 27

Retrofill Escutcheon Kit Spare Table 5 displays some kit options. Table 5. Escutcheon Options Kit Description Breaker Type LV Swgr No Cutouts Fascia Cutout Only Plus Lamps Plus Lamps & Ammeter Available Stack Width (in inches) 20 22 27 30 38 CAT # AK-25 AKD-5 YES YES YES YES YES Retrofill Escutcheon Kit Spare AKR AKD-6 N/A YES YES YES YES AKR AKD-8 / 10 AKR- 30S N/A YES YES YES YES 10109607G1 AKR AKD-8 / 10 Regular N/A YES YES YES YES Escutcheon Kit AK-50 AKD-5 N/A N/A YES YES YES 10102167G1 Escutcheon Kit AK & AKR- 75/100 Only AKD-5 & AKD-6 N/A N/A N/A YES YES 10102167G2 25 of 27

Notes 26 of 27

GE Industrial Solutions 41 Woodford Avenue Plainville, CT 06062 www.geindustrial.com 2015 General Electric Company Rev. 3 (10/16) 27 of 27