Proceptor Owner s Manual

Similar documents
INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS

Installation & Operation Instructions For EZ Klear Systems Model EZK-25

1BGrease Traps and. Frequently Asked Questions About Grease:

OWS OPERATIONS & MAINTENANCE

Grease Inspection Program

Excerpt from Chapter 3 of the City Code that address Fats, Oils and Grease (FOG) control program that was adopted by the City Council on May 9, 2016.

Installation and Operating Procedures

City of Tega Cay, South Carolina

OVERVIEW OPERATION. 2 Stormceptor EF Technical Manual

Hampton Roads Planning District Commission

AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual

Rapid Digestor Fume Removal System

Installation, Operation & Maintenance Manual. TotlSep (TS) Series. FRP Oil/Water Separator

AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual

Typical Machine Tool Coolant Purification Unit Installation and Operating Manual Note: MSR provides a custom manual for every application

SaniTEE Wastewater Screens Installation & Service Manual FOR USE WITH SNT416, SNT418, SNT818, SNT 838, SNT1618, and SNT1638

Fats, Oils & Grease Ordinance and Program. Presented by Lance McAvoy Deputy Director of Operations

BECKLEY. General: Page 1

(a) Administrator means Clearwater's Public Works Administrator or his or her designee.

QUICK START GUIDE OWNER S MANUAL AL50 SERIES SAND FILTRATION TECHNOLOGY PLEASE CALL DO NOT RETURN TO STORE

Operation and Maintenance

OWNER S MANUAL GREAT BASIN GREASE INTERCEPTORS

Operator's Manual. Models (¾") (1") (1½ ) (2 ) (3") (4") (6") (8")

CHATSWORTH WATER WORKS COMMISSION GREASE AND OIL CONTROL ORDINANCE

INSTALLATION GUIDE. Model #GB2 35/50 GPM Grease Interceptor For Indoor Use. Contents

INSTALLATION GUIDE. Model #GB1 20/25 GPM Grease Interceptor For Indoor Use. Contents

HOW TO INSTALL YOUR BOV

ORDINANCE NO BE ORDAINED BY THE CITY COUNCIL OF THE CITY OF TALLADEGA, ALABAMA, AS FOLLOWS:

Air-Operated Waste Oil Drainer

Fats, Oil, and Grease (FOG) Best Management Practices (BMP) For Food Service Facilities Information, Pollution Prevention, and Compliance Information

INSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket

GREASE INTERCEPTOR REQUIREMENTS Lakeway Municipal Utility District

Bottom Loading Water Dispenser

OPW Installation and Maintenance Instructions OPW Series Primary and Secondary Bucket Replacement Instructions

1000-lb Hydraulic Truck Crane

Cone Skimmers. Instructions. for Models 75G, 150G and 300G. Please read these instructions in their entirety before attempting to use this product.

Installation Manual DIAPHRAGM WELL TANK

OWNER S MANUAL WARNING

2-in-1 Air Operated Waste Oil Drainer

HOW TO INSTALL YOUR BOV

INSTRUCTIONS AND SERVICE MANUAL WITH PARTS LIST

Pretreatment Programs Fats, Oils and Grease FRWA Daytona 2015

SEPTIC TANK PUMP VAULT FILTER SYSTEM PUMP VAULT INSTALLATION AND SERVICE MANUAL

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.

Underground Storage Tank Guidance for Commercial Building Inspectors

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Fats, Rags, Oils, and Grease Program. Bedford Regional Water Authority

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

MASTER COALESCER JR & PORTABLE MASTER COALESCER JR AIR PUMP MODEL INSTALLATION MANUAL

Condensate Pump. Installation and Safety Instructions CP-22 CP CP-22LP CP-22LP-230

Laboratory Series. Ultraviolet Ozone Destruct System Installation, Operation and Maintenance Manual. One Source for All Your UV Needs!

RECYCOIL Used Oil Tank

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY

CHAPTER 20.1 WASTEWATER HAULING. Section Definitions. For the purposes of this article, the following definitions shall apply:

Model GP Triplex Ceramic Plunger Pump Operating Instructions/ Manual

City of Derby Water Pollution Control Authority Fats, Oils, and Grease Pretreatment Regulations Adopted March 15, 2017

Crispin Valves Operating Guide. Crispin

12V Oil Extractor Pump

KESSEL-Grease Separator Under sink

HALLMARK INDUSTRIES INC

Commercial Fats, Oils & Grease Stephen Sealey

182-LED Solar-Powered Motion Security Light. Owner s Manual

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

WSB clean: Installation Manual

Nilfisk-CFM SS Vapor Vacuum Instructions for Use and Spare Parts Manual

2000-LB. ENGINE STAND

AEROMOTIVE Part # Ford 5.0 Liter INSTALLATION INSTRUCTIONS

1000-LB. ENGINE STAND

AEROMOTIVE Part # Ford 5.4L Shelby GT500 Mustang INSTALLATION INSTRUCTIONS

StormPro BA Series Sump Pump

IMPORTANT OPERATING CONDITIONS. Failure to comply with any of these conditions invalidates the warranty. STANDARD CONFIGURATIONS

AEROMOTIVE Part # /2 4.6L SOHC Ford Fuel Rail Kit INSTALLATION INSTRUCTIONS

MODELS 108 and 138 CRAWL SPACE PUMPING SYSTEM PREINSTALLATION CHECKLIST

C.I.Agent HFF Oil Stop Valve

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-126 REV A 12/09

Dual/Triple Manifold Water Filtration Systems Instruction Manual

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

Motorized Stainless 2-Way Valves

Battery Backup Sump Pump System Instruction Manual

007 Tank Monitor. WARNING Never use with gasoline or highly flammable liquids.

Installation Instructions / Warranty

VANGUARD A EZ INSTALL OPERATOR S MANUAL

INSTALLATION INSTRUCTION & OWNER S MANUAL

MGFHVLP. Instructions/Parts. Mini Gravity Feed System E. Part No Includes MGFHVLP Mini Gravity Feed Spray Gun and MGC 125 Gravity Cup.

Smith & Hawken Propane Tank Cover dpci # stock # ZAZ15200T

Troubleshooting. This section outlines procedures for troubleshooting problems with the operation of the system:

Inst all a ti o n and Oper a tin g Instru c ti o n s

Wastewater Air Release Valve Models 48A, 49A

CRD600 Automatic Fitting Inserter

Tissue Master. User Manual

Mechanical Filter Pump Kit Up to 500 gallons

Owner s Manual GLASSLINED PUMP TANK

Mechanical Filter Box Kit

FOG Hog Grease Interceptor System Installation & Service Manual FOR USE WITH FOGHog FH-20, FH0-35, FH-50, FH-75, and FH-100

Stormwater Treatment System

Fuel and Oil Separators

Operations and Parts Manual

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1

Complete Pond Kit REMINDER CALL BEFORE RETURNING TO STORE. PLEASE CALL BEFORE RETURNING TO THE STORE.

Professional. Owner s Manual. Heavier Use Bottled Water Dispenser #601177

Transcription:

1 Proceptor

1 Proceptor Overview Congratulations on purchasing a Proceptor separator! Proceptor oil, grease and solids separators are a cost-effective solution allowing you to focus on your business, not your wastewater. 1.1 Benefits Drainage and wastewater contaminated with oils, fuels, grease and suspended solids are common in many commercial, institutional and industrial businesses due to the products produced, used, distributed and/or stored. Increasingly, stringent environmental regulations require that oil, grease and suspended solids be restricted to certain levels prior to being discharged into receiving sewer systems. Proceptor oil, grease and solids separators effectively remove floatables (i.e., free oil, grease) and allow solids to settle resulting in reduced and/or eliminated sewer-use surcharges and penalties to end users. Developed by Zurn Green Turtle (GT), Proceptor separators achieve maximum removal treatment efficiency of free oil, grease and suspended solids from wastewater flows because of its unique hydraulic flow patterns. The controlled hydraulic flow patterns further ensure captured contaminants will not scour or re-suspend. The elliptical design of the unit allows for enhanced treatment efficiency and ease of cleaning. Proceptor is useful as a point-source spill control device. Its fiberglass construction eliminates corrosion that can lead to soil and/or ground water contamination and costly remediation. 1.2 Design Tough reinforced fiberglass construction eliminates corrosion Elliptical separation chamber optimizes separation conditions Internal piping design eliminates scouring of stored oil, grease and solids Sized based on site-specific water flow and usage to ensure superior performance Multiple system configurations available for flexibility of installation If sized properly, eliminates or reduces sewer use surcharges The curved bottom design promotes easy maintenance including removal of contaminants by vacuum or pump truck 30-year warranty against cracks and leaks 2

1.3 Construction The Proceptor tank is equipped with two 3 diameter PVC vent connections (per tank) for venting gases to the outside, inspection ports and an access way for regular inspection and maintenance. The contractor installing a Proceptor is required to provide piping from the vent connections to the venting system. An extension collar located at the center and/or at both ends of the separator provides access for maintenance. A frame and cover, supported by a concrete slab or similar support structure, is placed above the extension collar to provide access to the separator. The standard, single tank separator design includes a baffle that creates two chambers in the unit. Note: for designs such as the Uniform Plumbing Code (UPC) oil separator tanks, the unit consists of three chambers separated by two baffles. Figure 1: illustrates the components of a standard, single tank Proceptor separator Figure 1: Single tank Proceptor design 3

Figure 2: The following figures depict other common unit configurations. Dual tank with one access way per tank Triple tank with one access way per tank Single tank with dual access way Dual tank with dual access way Single tank with triple access way 4

1.4 Operation Wastewater enters the unit through an inlet drop pipe, typically a 4 or 6 PVC sewer pipe, which discharges the wastewater below the normal liquid surface in the tank (see Figure 3). The inlet drop pipe is configured to discharge wastewater horizontally along the tank walls. Upon entering the tank, oil, grease and other liquids with a specific gravity less than water rise to the surface in the first chamber, while suspended solids settle to the bottom by gravity. The wastewater then flows into the second chamber by a means of a flow distributor on the baffle wall (or riser pipe into the second tank), ensuring a smooth flow path, where further separation occurs. Cleaner water from the middle elevation of the tank is displaced through the riser pipe into the downstream sewer system. Maintenance is performed by a licensed liquid disposal company using a vacuum or pump truck. Figure 3: Proceptor operation: process flow dynamic 2 Protecting the Wastewater Collection System 1. Inspect and maintain your Proceptor separator regularly. 2. Be familiar with local regulations that govern the acceptable limits for wastewater from your operation and any other required practices. 3. Be proactive. Source a local plumber, drain cleaning service and licensed separator pumping and disposal operator before you have a plumbing emergency. With attentive maintenance, you can avoid emergency situations. 4. Witness all Proceptor separator maintenance to ensure that the device is being properly cleaned and is operating efficiently. Keep an inspection and service maintenance log. All inspection and maintenance records should be retained on file for a period of at least two years. 5

2.1 Essential Best Management Practices (BMPs) The practice of preventing or reducing the amount of oils, grease and solids discharged into the drainage system can prove to be very beneficial to your company. The reduction of oils, grease and solids going down the drain will result in less frequent maintenance of your Proceptor, and greater assurance of being compliant with local regulatory bylaws. The reduced chance of drain line blockages and a reduced maintenance frequency will result in lower costs for your company. Check to see if your government has published BMPs. They may be available on a web site or from your municipal office. The following are brief outlines of major points found in typical BMPs. Your industry s BMPs will likely have additional items and useful tips. 2.2 Kitchen BMPs 1. Keep grease out of the drains. Prevent pouring excess oil or grease down the drain. The thick yellow grease should be collected and rendered. The more yellow grease collected and rendered, the less grease that ends up in the drains or in your Proceptor separator. Yellow grease can be used as raw material for biofuels. Grease that goes down the drain and mixes with water becomes brown grease that is more difficult to recover. 2. Scrape grease and food from plates and cookware before washing. Using gloves or rubber spatulas, grease and food scraps should be scraped off plates and cookware before washing. This material should be added to the trash, recycled or composted as part of a food waste recycling program. 3. Use drain screens. Using drain screens, particularly on sink drains, will prevent much of the grease and greasy food particles from ending up in the drains. 4. Wipe up grease spills before using water. Grease spills or drippings should be wiped up with a paper or cloth towel before using water to minimize the amount of grease ending up in the drains. 5. Limit garbage disposal use to non-greasy food materials. Restaurants with garbage disposals should be limited to processing non-greasy food materials like fruits or vegetables in food preparation areas to minimize the amount of grease ending up in the drains. 6. Employee training. Employees must be trained to implement the kitchen BMPs and/or properly inspect and maintain your Proceptor separator. Also, a NO GREASE sign above sinks or on the front of dishwashers acts as a constant reminder of employee training and the kitchen BMPs. 6

2.3 Garage BMPs A detailed BMP can be obtained from Petroleum Products Institutes, or your Provincial/State or Municipal Government. Most of these items are geared to keeping oil and other chemicals from going down the drain. 1. Use spill containment protection for acid batteries, solvents, oils, fuels, antifreeze, transmission fluid, brake fluid and any other substances whose discharge into the sewer system is regulated. 2. Have a spill response plan and personnel trained to carry it out. 3. Do not dump oil or other chemicals down the drain or into the separator. Store and dispose according to regulations. 4. Any accumulation of volatile liquids must be removed immediately by a licensed pumping company. 5. Clean up oil spills with rags and store in closed containers for cleaning or disposal. 6. Use drip pans to contain leaks under vehicles. 7. Do not wash service bays with hot water and soap as these emulsify oils. Dry sweep floors as much as possible. 8. Where soaps are used, quick-break types are recommended. These emulsify oils for a shorter period of time, giving them more chance to be unbonded from soap within the separator instead of further downstream. 3 Inspection Regular inspection is important to ensure the drainage system is working properly. When the unit is first commissioned, it is recommended that the levels of solids and oil or grease be checked at weekly intervals for food applications to determine how much material is accumulating. Oil separators in garages should be checked monthly to start. These observations will help establish the best maintenance interval based on site specific conditions. Normal inspection and maintenance of a Proceptor separator does not require entrance into the separator. The separator may contain noxious, toxic or explosive gases, even if empty, that could be harmful or fatal to workers inside the tank. Entrance to the tank may only be made by workers trained to work in confined spaces having obtained confined space certification from a recognized certifying authority. Proceptor separators must be examined annually for damage to both the interior surface and internal components. Damage must be repaired immediately upon discovery. 3.1 Water Level and Tank Depth For any inspection and maintenance work, it is important to have a benchmark measurement of two reference points: 1. Static water level to top of grade (floor level) 2. Clean bottom of the tank to top of grade (floor level) (see Figure 4). 7

The distance from top of grade to the tank bottom will be your reference for measuring solids depth. Make sure you record which units (inches or centimeters) that you are using. A. Static Water level to Floor Level = Make sure the tank is full of water and not backed up. Record this measurement after it is pumped out and refilled with clean water. With no flow running into the separator, open the cover and put the zero end of a measuring tape or rod on top of the liquid surface, and measure to the top of the floor level. Enter this into your records. If during a routine inspection the water level is unusually high there may be a blockage downstream. The water level should not rise as high as the tank neck and extension collar through the access way. B. Bottom of Tank to Floor Level = Measure from the tank bottom to the floor level and record the height in your separator maintenance records. Record this measurement after the tank is pumped out and before it is refilled with clean water. Shine a flashlight into the dark tank to visually check that the measuring tape is contacting the bottom of the tank. Figure 4: Measurements of materials in unit A = Benchmark No Flow Level H = Benchmark High Flow Level (see Oil Draw off option) B S = Solids Depth G A = Grease or Oil Layer Depth 3.2 Grease/Oil and Solids Levels Solids generally settle to the bottom, and grease or oil will float on the top. Solids can block the inlet or outlet if the layer becomes too deep. Also, if the grease or oil layer becomes too deep, concentrated grease or oil will exit the separator and go down the sewer pipe, causing problems in the pipe downstream, which may cause sewer backups into your facility. 8

In a single tank system, be sure to measure within the inlet side of the access way. To determine the inlet side of the access way, look at your facility layout to figure out which direction the inlet would be coming in. If this is not clear, try running water down the drain and watch the liquid in the tank to see if you can observe the direction of flow. In a double or triple tank system, it is recommended to measure in all tanks. Compare these measured amounts to the limits in Table 1 (page 11) to determine if a pump out is required. Solids Layer The solids layer depth can be determined two ways; either by probing with a graduated rod or weighted measuring tape or by using a specially designed sampling/measuring tube (See section 3.3). To measure with a rod or tape, slowly lower the rod or tape into the fluid on the inlet side of the access way until increased resistance is felt. Depending on your operation, this might be a soft layer (more typical of restaurants), or a harder layer (i.e. sand in an oil separator). When resistance is met, hold the rod or tape steady and measure to the floor (top of cover). Subtract this measurement from the previously measured tank depth to find inches or centimeters of solids. Oil or Grease Layer The oil or grease layer depth can be determined two ways; either with a dipstick rod and water finding paste, or by using a specially designed sampling/measuring tube. (See section 3.3). Spread a thin coating of water level indicator paste (i.e. Kolor Kut) on the bottom six inches or so of the dipstick, measuring tape or gauge rod. Slowly lower the measuring device into the liquid, coated end down, to where the oil-water interface is anticipated. Mark the floor level against the rod. Slowly pull the rod back up without stirring the oil. A change in color by the water paste indicates where the oil-water interface occurs. The distance between the color change on the rod and the floor level is the G dimension in Figure 4. The absence of color change indicates that the measuring device did not reach far enough down to the oil-water interface, therefore remeasurement is necessary. 3.3 Total Waste Column Measurement The sludge/solids, water and oil/grease level can be measured collectively in a sampling tube equipped with a built-in ball check valve to hold the material. The tube should be graduated (marked in inches or centimeters with zero at the bottom) to indicate the depth of the sludge, water level and oil or grease layer in the Proceptor separator. Follow the manufacturer s usage instructions. Slowly lower the dipstick tube to the bottom of the tank. Do not plunge the device to the bottom as it will result in an inaccurate reading and possibly damage the ball check valve. Keep the dipstick tube as vertical as possible when raising it up, without allowing it to bend or bounce while it is full of wastewater. A water core sample should be visible within the tube showing the solids depth and oil/grease depth. Release the sample back into the inlet side of the separator or dispose of according to acceptable practice. 9

3.4 Treated Wastewater Sampling The inspection/sample port at the outlet pipe is designed to allow sampling of the discharge to determine compliance with local effluent standards. There should be two ports (4 or 6 ) extended to grade and capped on either side of the access cover. The outlet side port is the sample port. Avoid hitting the sidewalls of the sample port pipe, which can result in an inaccurate reading. If there are no accessible sample ports, take a sample from the outlet side of the tank through the access cover. Samples should be taken from mid-liquid depth inside the Proceptor using an underwater grab sampler. Testing is generally done through a laboratory that can check for Total Oil and Grease or Mineral Oil and Grease (for oil). Testing should be done by a laboratory that is certified by your local municipality. Test results under allowable limits: If the test results indicate compliance with local bylaws: Great! You can continue to be confident that your wastewater complies with legislation limits and your business is environmentally responsible. Test results above allowable limits: If the test results indicate non-compliance with local bylaws: 1. Measure the solids and oil/grease depths in the unit. 2. If at or near capacity, pump out the Proceptor and refill with clean water. 3. Verify that the maximum flow rate does not exceed the Proceptor model design. 4. Evaluate facility standard operating procedures to confirm that best practices are enforced to reduce the quantity of solids and contaminants entering the Proceptor. 4 Maintenance 4.1 Emptying and Servicing Proceptor Regular maintenance of a Proceptor unit is critical to ensure separation efficiency is not compromised. The build-up of floatables and solids within the separator reduces the water retention time and results in reduced separation efficiency. If contaminants are allowed to accumulate, maximum storage capacities may be exceeded, resulting in the loss of previously captured oil, grease and solids. This may expose the Owner/Operator to unnecessary liability and/or higher sewer-use surcharges. Proceptor separators must be serviced by a vacuum or pumping truck. Liquid waste pump out companies are a well-established sector of the servicing industry. Costs to clean a Proceptor separator vary based on the unit size, geographic area and transportation distances. Consult your local Waste Management Authority for an approved list of licensed liquid waste handlers. Find out the normal liquid volume or model number of your unit. Maintenance companies will require this information to quote for service. Note: 1 Imperial Gallon = 1.2 US Gallon. Proceptor separators must be filled with clean water after cleaning the unit by running a tap that drains into the separator. To determine approximately how long to run the tap, divide the tank volume in US gallons (USG) by 5 (USG per minute for a typical tap). For example 300 Gallon tank / 5 = 60 minutes. If you do not fill the tank with clean water after pump out, your operation will discharge un-separated waste from the separator on startup. 10

4.2 Maintenance Frequency Maintenance frequency depends on the application and the size of the Proceptor separator which is summarized in the following table. Table 1: Maintenance Schedule Model Number Total Liquid Capacity Oil/ Grease Storage Capacity Solids/ Sediment Oil/ Grease Maintenance Recommended Solids/ Sediment (US Gal) (US Gal) (US Gal) (inches) (inches) GMC 50 OMC 50 50 12 11 1.0 1.5 GMC 100 OMC 100 100 42 23 4 3 GMC 150 OMC 150 150 66 48 6 5 GMC 200 OMC 200 200 90 72 8 7 GMC 300 OMC 300 300 156 103 13 9 GMC 500 OMC 500 500 279 87 8 3 GMC 750 OMC 750 750 410 200 11 6 GMC 1000 OMC 1000 1,000 577 295 16 9 GMC 1300 OMC 1300 1,300 707 446 19 13 GMC 1500 OMC 1500 1,500 819 540 22 15 GMC 1000(2) OMC 1000(2) 1,000 559 174 8 3 GMC 1500(2) OMC 1500(2) 1,500 819 401 11 6 GMC 2000 OMC 2000 2,000 1154 589 16 9 GMC 2600 OMC 2000 2,600 1415 891 19 13 GMC 3000 OMC 3000 3,000 1638 1080 22 15 GMC 4000 OMC 4000 4,000 1712 1315 15 15 GMC 5000 OMC 5000 5,000 2226 1776 20 19 GMC 6000 OMC 6000 6,000 2883 2092 26 22 GMC 7000 OMC 7000 7,000 3396 2611 30 27 GMC 8000 OMC 8000 8,000 3810 2707 23 15 GMC 9000 OMC 9000 9,000 4324 3139 26 22 GMC 10000 OMC 10000 10,000 4795 3700 28 30 For larger units, contact Zurn Green Turtle at 1 877 428 8187 (USA) or 1 877 966 9444 (Canada) Maintenance procedures for Proceptor oil separators with internal or external oil reservoirs can be found in section 5.1. 11

4.3 Troubleshooting Inlet blockage: If the drain upstream of the separator backs up, visually check the inlet pipe through the inspection port for a blockage and snake the pipe if necessary. Outlet blockage: If the liquid level within the Proceptor separator rises above normal, visually check the outlet pipe through the inspection port for blockage. Clean carefully with a snake (pipe cleaning tool) as required. Check the levels of solids and grease within the separator. Have it pumped out if necessary. Eliminate the possibility of drain blockages occurring elsewhere. Note: Repeated blockages may indicate a need for usage evaluation (e.g. the amount of solids entering the Proceptor, excess grease in the system may be solidifying in the pipes, etc.). To ensure the separator functions correctly, take all corrective actions required to reduce the quantity of solids and contaminants entering the Proceptor and ensure that all BMPs are being followed. 4.4 Odor Control Vents Vent ports have been provided with the Proceptor separator. The installer should have connected the port(s) in the top of the tank to the building venting system to maintain air pressure equilibrium in the tank to allow for smooth flow and elimination of odors within the building. Frame and Cover Check the condition of the gaskets and/or O-ring under the access cover. Clean and replace if necessary. 4.5 Spills Proceptor separators can be susceptible to spills given the sometimes unpredictable nature of wastewater surges. If excessive oil, grease or solids flow into the separator, the tank must be pumped immediately to help prevent a spill. If there is an overflow, the appropriate governing agency must be notified. 5 Advanced Accessories and Options 5.1 Oil Reservoir Options An oil draw off pipe option decants oil from the separator to an internal or external reservoir. The oil draw off level is set by the operator so that only a minimum quantity of oil remains in the separator at any time, and that no water may enter the reservoir. The oil draw off system reduces the need for frequent servicing, provides a safeguard against excess oil build-up in the separator and allows oil removal without interrupting the operation of the separator. In some 12

areas, specialized oil recycling companies will offer credit to the owner for the removal of oil from the oil reservoir based on its purity (free from water and solids). Figure 5: Proceptor oil separator with internal oil reservoir As depicted in Figure 5, a Proceptor oil separator with an internal oil reservoir, the oil is pumped directly out of the reservoir allowing the remainder of the separator to operate without interruption. Figure 6: Proceptor oil separator with external draw off pipe Figure 6 shows an alternative design where the Proceptor is installed with a draw off pipe which directs oil to an external reservoir. The oil can be pumped out of the external reservoir without interrupting the operation of the separator. Regular inspection and service is required for a Proceptor separator with an internal or external oil reservoir to ensure proper unit operation. Maintenance: Oil The main factor in determining the need for maintenance is the oil level in the reservoir. If the reservoir is equipped with an electronic high level monitor, have the tank pumped out when the level monitor is triggered. (See level in Section 5.6) 13

If there is no electronic monitor within the reservoir, visual inspection and measurement will be required. Locate the 6 (typical) reservoir port in or near the access way (Figure 7) in reservoir models. Figure 7: Top view of reservoir models showing ports visible at floor level and through access way To perform manual measurement, two measurements must be taken. With a measuring rod, benchmark measure from the bottom of the reservoir to the floor level through the reservoir port. Then measure from the top of the oil level in the reservoir to floor level. The difference between the two measurements is the level of oil in the reservoir. Refer to Table 2 for recommended maintenance levels. Table 2: Reservoir Maintenance Schedule Model Number Treatment Chamber (US Gal) Storage Capacity Total Oil Solids Reservoir (US (US Gal) Gal) Maintenance Recommended Reservoir Oil Solids Level Level (inches) (Inches) OMC 100 RES 100 50 29 18 9 OMC 150 RES 150 50 50 26 13 OMC 200 RES 200 100 64 42 18 OMC 400 RES 400 100 40 18 4 OMC 500 RES 500 250 129 31 12 OMC 750 RES 750 250 223 45 17 OMC 1000 RES 1000 300 347 60 25 OMC 1300 RES 1300 200 471 71 30 If there is a separate oil storage tank, find the access way for it and measure the oil depth within the tank. Maintenance levels for a separate oil storage tank are at the discretion of the owner. Ensure appropriate regulations are followed. If water is getting into the oil reservoir, excessively high flows or a backed up sewer pipe may have pushed the water into the reservoir, or the adjustable oil draw off pipe may be set too low. If no oil is getting into the reservoir, but significant amounts of oil are present in the separator side, the oil draw off pipe is set too high. 14

Maintenance: Solids The second maintenance factor is the solids settled at the bottom of the separator portion of the system. When the reservoir needs to be pumped out, check the solids level in the separator (see Section 3.2). At the minimum, inspect and pump out the separator and oil reservoir once a year. Refill the separator portion with clean water and inspect the oil reservoir to insure it is dry and no water has transferred into it. Oil Draw Off Pipe Adjustment The oil draw off pipe can be adjusted inside the tank after it is pumped dry by trained personnel following safe confined space entry procedures. Before adjusting the pipe, measure the no flow and high flow water level in the tank, without oil floating on top. This will be slightly higher than the no flow elevation. See Figures 5 and 6. The pipe has a slip fitting on the top with a nut around it which can be loosened by hand to allow the upper portion to slide up and down. The top of the oil draw off pipe should never be set lower than the bottom of the outlet pipe, otherwise water will flow into the reservoir. The top of a layer of oil will rest at a slightly higher elevation than if the unit contained water only. Set the top of the draw off pipe within approximately one inch above the high flow level to catch the oil as it increases in height. To determine a new elevation of the draw off pipe, an operator s knowledge and experience of site specific conditions should be considered. 15

5.2 Oil Coalescer Figure 8: Proceptor separator with coalescer The Zurn Green Turtle coalescer system is specifically designed for use in a Proceptor separator to assist removing free oil and mechanically dispersed oil. It is comprised of corrugated porous PVC plates mounted in a fiberglass frame within a baffle of the separator. As wastewater enters the Proceptor, some free oil will immediately rise in the first chamber to the surface and most solids will settle to the tank bottom before reaching the coalescer system. Finer oil droplets still within the water will continue and encounter the wetted surfaces of the coalescer material where they will meet with other oil droplets clinging to the plates and combine to form larger droplets (coalesce). The oil globules will follow the inclined channels upwards to the top of the coalescer pack and exit to float on the liquid surface. The newly formed larger oil globules will rise faster. Most suspended solids reaching the coalescer will slide down the inclined surfaces to exit the bottom of the pack and continue to the tank bottom. In a gravity separator, coalescers are not suitable for removing chemically emulsified or dissolved oil. Soap in wastewater will cause chemical emulsification keeping the oil particles suspended like a colloid, impairing the separation efficiency of the Proceptor and the performance of the coalescer system. Use of quick break type soap will help. Quick break soaps are more likely to release the oil held by the soap in the water before reaching the separator, allowing the oil to separate within the separator instead of being carried downstream. For optimal efficiency the Proceptor separator must be cleaned and maintained at regular intervals. The interval depends on the characteristics and flow volume of your wastewater. 16

Maintenance: Coalescer Regularly monitor oil and sediment level in your Proceptor separator. When the separator is pumped out, Zurn Green Turtle recommends cleaning the coalescer system at the same time. The coalescer may become plugged up if the solids loading is too high in the influent wastewater. Although this will not affect flow through the separator, it may reduce the oil removal efficiency and expose the Owner/Operator to unnecessary liability. To clean the coalescer system: 1. Visually inspect the unit from the access way to make sure there is no obstruction on top of the coalescer and the lifting device is secured. There may be tabs bolted on the baffle to hold the coalescer in place during original shipment. Swivel them out of the way if they are holding the coalescer down. 2. Pull the handle gently to lift and remove coalescer pack(s) one at a time. 3. Use caution when handling the coalescer packs to avoid damage. 4. Inspect for damage. Ensure frames are intact. 5. Rinse each coalescer pack with low pressure clean water. Note: Do not use soap in the cleaning process. Tip: Before the separator is pumped out, suspend each pack over the tank access way using a bar through the handle at floor level. The rinse water will flow back into the tank and be pumped out by the waste maintenance company. 6. Look through the porous sides of the pack to ensure channels are clear. If low pressure flow will not clear the channels due to packed solids, a high-pressure wash may used. Use care not to damage the internal parts of the pack with a high-pressure wash. 7. Ensure all oil, water and sediment is pumped out/removed from the oil separator until it is clean to the bottom. 8. Ensure the frames in the Proceptor baffle inside the tank are free of debris, especially at the bottom where the coalescer is installed. 9. Before refilling the separator with clean water, reinstall each pack by lowering carefully into the baffle frame, making sure pack(s) are seated and level with the top of the baffle. When the coalescer packs are equipped with vertical guide bars (a feature added in 2007), it prevents the packs from being reinstalled incorrectly. These bars protrude from the box frame. Note: If the coalescer system does not have guide bars, ensure the pack(s) are installed with the open celled sides facing the inlet and outlet. The top and bottom of the packs also have open cells. If installed incorrectly, waste water will flow over the coalescer instead of flowing through it. Refill the separator with clean cold water. Do not add soap to the unit. An alternative to pulling out coalescer packs is to pressure wash them in place after the tank is pumped out during scheduled maintenance. Please ensure the water used to clean the coalescer system is also pumped out. However, Zurn Green Turtle recommends removal of the coalescer packs for optimal cleaning and inspection. 17

Illustrating one baffle pack partially lifted. Pack configuration varies with separator model. Direction of wastewater flow. Figure 9: Typical coalescer construction Repair If a coalescer system appears damaged call your Zurn Green Turtle representative for further information. 5.3 Suction Pipe A suction pipe is used when remote tank cleanout is desired, typically for an indoor installation. The suction pipe is an internal system that allows the tank to be maintained even if a servicing vehicle cannot access the main access cover at the top of the tank. 18

Figure 10: Proceptor with suction pipe option The suction pipe may be plumbed to floor level, or to an exterior wall allowing a pump truck to attach to the port outdoors instead of the typical service method of entering the building to open the access cover. A space at the base of the baffle allows solids to be drawn from both cells. 5.4 Oil Alarm Any Proceptor separator may have an alarm to indicate when the oil/grease layer has reached a preset storage volume. There will be an alarm panel on a nearby wall (typically) and a steel alarm probe rod inside the access way extending down into the tank. When the tip of the probe, which is normally submerged in water, senses a decrease in capacitance from contact with the oil/grease, the alarm switch closes a relay contact and triggers an alarm light and buzzer at the panel. This is the signal for the maintenance operator to have the tank pumped out and then refilled with clean water. The audio alarm can be silenced by using the acknowledge button on the panel front. Once the unit is refilled with clean water the alarm light will go out. Complete operational instructions were provided with the sensor alarm when it was originally shipped. Calibration If the alarm does not appear to be working, Zurn Green Turtle recommends the calibration be checked as follows: 1. Open the alarm panel box and set the switches of the controller as follows: DIELECTRIC High dielectric (When probe tip is submerged in water) SENS Position 3 ALARM DELAY Position 6 (15 seconds) RELAY Low relay 19

2. Be sure the separator is filled to capacity with water. The probe should be submerged in water, NOT grease or oil. 3. Press the CALIBRATE push-button until the STATUS LED light above the calibration button glows red. Release. 4. The STATUS LED should begin flashing green, indicating that the unit is in calibration mode. 5. Press the CALIBRATE button again until the STATUS LED glows red. Release. 6. Check to make sure the STATUS LED goes to steady green and the ALARM LED is red. This indicates the relay energized under normal conditions with a failsafe alarm setup. Electrical hook-up is typically wired through the common and normally closed contact of the relay. 7. The unit is now calibrated and will alarm when the sensing section of the probe tip is exposed to oil or grease. The alarm will also be activated if the probe tip contacts air, such as when a vacuum truck removes the liquid from the tank. 5.5 Double Wall Proceptor separators are available with a secondary wall made from durable fiberglass for added protection against leaks. The double wall Proceptor typically is ordered with an interstitial monitor for leak detection. No additional maintenance of the secondary wall is required. 5.6 Level There are three configurations where a level monitor may be installed oil reservoir, double wall (for interstitial leak monitoring), and liquid holding tank. In all of these applications, the level monitor probe is normally dry, and will trigger when fluid contacts the probe. In an oil reservoir and holding tank, the level probe is set at a preset elevation. In the double wall, the level probe is typically installed between the tank walls near the bottom of the tanks, where any potential leak would pool, to give early warning of a leak condition. Maintenance When the monitor sounds, press the acknowledge button to silence the horn, if desired. The light should remain red as a reminder. Call your liquid waste removal company for pump-out. When the tank has been pumped out, the light will go out. If the monitor sounds and the probe is still dry, check the system for electrical faults. Power outages may also cause alarms. To check the sensor probe condition, lift the sensor pipe out of the bracket. If debris is found on the probe forks, clean them carefully with a soft brush and detergent, being careful not to scratch the surfaces or break the forks. 20

Testing With power supplied to the system, the following are nominal conditions for the LED lights: LED DRY WET / TEST Panel Alarm OFF RED Panel Power GREEN GREEN Panel Caution OFF ORANGE until acknowledged Controller Power GREEN GREEN Controller Input 1 GREEN ORANGE (green if test only) Controller Relay RED OFF (red if test only) Push the test button on the panel. The Caution LED will light YELLOW and stay on until the Acknowledge button is pushed. Adjust the horn volume by rotating the black shutter. To test the probe operation, immerse the forks of the probe in liquid. 21

6 30-Year Warranty This warranty is provided by Zurn Green Turtle Technologies Ltd. for products sold in Canada, and by Zurn Green Turtle Americas Ltd. for products sold in the continental U.S. Although the companies are collectively referred to herein as Zurn Green Turtle, each company only warrants products sold in its respective market. Proceptor oil and grease separators are not intended for residential or consumer use, and may not be purchased or sold for those applications. Zurn Green Turtle warrants to the original purchaser that all Proceptor oil and grease separators purchased from Zurn Green Turtle will be free from defects in materials and workmanship for a period of one (1) year following the date of initial delivery to the purchaser, subject to the terms and conditions below. Upon submission of a warranty registration card (www.greenturtletech.com/warranties) to Zurn Green Turtle by the owner within the first 30 days of ownership, Zurn Green Turtle further warrants that if the Proceptor separators are installed, operated, and maintained in accordance with Zurn Green Turtle instructions and applicable state/provincial and federal regulatory requirements, the Proceptor devices: 1. Will not leak for a period of 30 years from date of initial delivery due to natural external corrosion. 2. Will not leak for a period of 30 years from date of initial delivery due to internal corrosion, provided the Proceptor is used solely in respect of the treatment of commercial/institutional wastewater (other applications, including but not limited to residential, and consumer not being covered by the warranty). 3. Will not leak for a period of 30 years from date of original delivery due to structural failure, which shall be defined as spontaneous breaking or collapse. All of the warranties herein are subject to the following conditions: 1. The Proceptor is installed, operated, and maintained in accordance with the Proceptor Installation Instructions and Proceptor. 2. Oil Multi-Cell (OMC) and Gravity Grease Multi-Cell (GMC) models up to 4000 gallons are installed as shallow burial having a maximum depth of 6 feet from the top of the tank to grade. Models 4000 gallons or more have a maximum depth of 4 feet from the top of the tank to grade. (For deeper installation, a custom reinforced Proceptor must be authorized by Zurn Green Turtle.) 3. There are no post-installations or repairs of the original Proceptor separator. 4. The original installation has been carried out in Canada or the United States. 5. The original installation was performed following the Proceptor installation procedures by a trained contractor with all his/her required registrations, certificates and/or licenses, to complete the installation, repair or alteration in accordance with recognized industry practices and applicable regulatory requirements. 6. The Proceptor has been operated and maintained in accordance with regulatory requirements designed to minimize the possibility of structural failures and releases of regulated substances. 7. The Proceptor shall not be installed or used in any application other than commercial, industrial, or institutional use. 8. After initial installation of the Proceptor, the tank installation checklist supplied by Zurn Green Turtle must be properly completed by the contractor and/or the owner s representative, and the completed checklist must be submitted to Zurn Green Turtle within 30 days after installation (failure to deliver the document may result in denial of the claim). 9. If the Proceptor is remanufactured, moved, or removed from the ground for any reason prior to the expiration of this warranty, the structural warranty protections will terminate unless the Proceptor is inspected, repaired (as necessary), and re-certified by Zurn Green Turtle and, upon reinstallation, the purchaser continues to satisfy the other conditions of the warranty. 10. The sole warranty for accessories, including but not limited to frames and covers, extension collars, alarms, pumps, valves, coalescers, suction pipes, sludge judge, draw-off pipes, strainers, etc. is that they are warranted for a period of one (1) year against defects in materials and workmanship from date of shipment. 11. Consumable parts including but not limited to gaskets and o-rings are excluded from this warranty. 22

ZURN GREEN TURTLE S LIABILITY UNDER THIS WARRANTY IS LIMITED, AT ZURN GREEN TURTLE S DISCRETION, TO REPAIR THE DEFECTIVE PROCEPTOR, TO REPLACE PROCEPTOR IN EXCHANGE FOR THE DEFECTIVE TANK, OR TO REFUND OF THE ORIGINAL PURCHASE PRICE. ZURN GREEN TURTLE IS NOT LIABLE FOR ANY LABOR, SHIPPING, OR OTHER INSTALLATION COSTS, AND SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, PUNITIVE, CONSEQUENTIAL OR OTHER DAMAGES IN CONNECTION WITH SUCH PROCEPTOR INCLUDING, WITHOUT LIMITATION, COSTS, EXPENSES, OR LIABILITIES ASSOCIATED WITH ENVIRONMENTAL CONTAMINATION, FINES OR PENALTIES, FIRES, EXPLOSIONS, OR ANY OTHER CONSEQUENCES ALLEGEDLY ATTRIBUTABLE TO A BREACH OF THE WARRANTY OR DAMAGES UNDER DECEPTIVE TRADE PRACTICES OR SIMILAR CONSUMER PROTECTION ACTS. THE FOREGOING CONSTITUTES ZURN GREEN TURTLE S EXCLUSIVE OBLIGATION AND ZURN GREEN TURTLE MAKES NO EXPRESS OR IMPLIED REPRESENTATION OR WARRANTY, OR ANY WARRANTY OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSES WHATSOEVER. NO EMPLOYEE OF ZURN GREEN TURTLE OR ANY OTHER PARTY IS AUTHORIZED TO MAKE ANY OTHER REPRESENTATIONS OR WARRANTIES OTHER THAN THE WARRANTY SET FORTH HEREIN. 12. Customer assumes the risk of and agrees to indemnify Zurn Green Turtle against and hold Zurn Green Turtle harmless from all liability relating to (i) assessing the suitability for Customer s intended use of the Proceptor and of any system design or drawing and (ii) determining the compliance of Customer s use of the Proceptor with applicable laws, regulations, codes and standards. For Proceptors resold by Customer, Customer retains and accepts full responsibility for all warranty and other claims relating to, or arising from, Customer s Proceptor system which includes or incorporates Proceptor or components thereof manufactured or supplied by Zurn Green Turtle, and Customer is solely responsible for any and all representations and warranties regarding the Proceptor system made or authorized by Customer. Customer will indemnify Zurn Green Turtle and hold ZurnGreen Turtle harmless from any liability, claims, loss, cost or expenses (including reasonable legal fees) attributable to Customer s Proceptor system or representations or warranties concerning same. 23

ZMKTG700-06