BCI164C - Technical Data Sheet Winding 06

Similar documents
BCI164D - Technical Data Sheet

BCI164B - Technical Data Sheet

UCI274H - Technical Data Sheet Winding 06

UCI274C - Technical Data Sheet Winding 06

BCI164A - Technical Data Sheet

UCDI224F - Technical Data Sheet

UCDI274J - Technical Data Sheet

BCI184J - Technical Data Sheet

UCI274H - Technical Data Sheet

BCI184H - Technical Data Sheet

UCI224C - Technical Data Sheet

UCI224E - Winding 06. Technical Data Sheet APPROVED DOCUMENT

UCI274E - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

UCI224C - Winding 06. Technical Data Sheet APPROVED DOCUMENT

HCI 534C/544C - Technical Data Sheet

UCI274D - Technical Data Sheet

UCDI274K - Technical Data Sheet

UCI274D - Technical Data Sheet

UCI274G - Technical Data Sheet

UCI224E - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

HCI 434E/444E - Technical Data Sheet

UCI224F - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

HCI 434D/444D - Technical Data Sheet

HCI 534F/544F - Technical Data Sheet

PI144D - Technical Data Sheet

PI144J - Technical Data Sheet

UCI224F - Technical Data Sheet

UCDI274K - Technical Data Sheet

HCI634G - Technical Data Sheet

UCI224F - Winding 25. Technical Data Sheet APPROVED DOCUMENT

HCI 434E/444E - Technical Data Sheet

HCI 534E/544E - Technical Data Sheet

UCI274E - Winding 14 APPROVED DOCUMENT. Technical Data Sheet

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet

UCI224F - Winding 14. Technical Data Sheet APPROVED DOCUMENT

HCI434E/444E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

HCI534F/544F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044D - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144G - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044H - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

HCI 534E/544E - Technical Data Sheet

HCI434C/444C - Winding 17 APPROVED DOCUMENT. Technical Data Sheet

UCDI224E - Technical Data Sheet

HCI 434F/444F - Technical Data Sheet

PI144D - Winding 17. Technical Data Sheet APPROVED DOCUMENT

HCI634H - Technical Data Sheet

UCI224G - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI274D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI224E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI224C - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCI224D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

UCDI274J - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044D - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCI 534E/544E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCI 534C/544C - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

LVI634E - Technical Data Sheet

HCI634J - Winding 311 and 312 APPROVED DOCUMENT. Technical Data Sheet

HCI634H - Winding 311 and 312 APPROVED DOCUMENT. Technical Data Sheet

HCM634K - Winding 311 and 312 APPROVED DOCUMENT. Technical Data Sheet

HCI634J - Winding 311 and 312 APPROVED DOCUMENT. Technical Data Sheet

HCI634H - Winding 311 and 312. Technical Data Sheet

PI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI736F - Winding 312. Technical Data Sheet

UCM274C - Technical Data Sheet

UCM274H - Technical Data Sheet

UCM274E - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

UCM274E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

UCM224D - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

UCM274C - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434E - Winding 311 Single Phase. Technical Data Sheet APPROVED DOCUMENT

HCM534D - Winding 14 APPROVED DOCUMENT. Technical Data Sheet

HCM534F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PM734E - Winding 28. Technical Data Sheet APPROVED DOCUMENT

HCI634V - Technical Data Sheet

P734H - Technical Data Sheet

S5L1D-G4 Wdg Technical Data Sheet

QSK23-G3. Description. Features rpm (50 Hz Ratings) 1800 rpm (60 Hz Ratings)

QSL9-G5. Description. Features rpm (50 Hz Ratings) 1800 rpm (60 Hz Ratings)

6BTA5.9-G5. Description. Features rpm (50 Hz Ratings)

S3.8 G6 CoolPac. Description. Features rpm (50 Hz Ratings)

This engine has been built to comply with CE certification.

Features. Cylinder Block - Alloy cast iron with removable wet liners.

KTA50-G8. Specification sheet. Features. Description. Codes and standards rpm (50 Hz Ratings)

This engine has been built to co mply with CE certification. Gross Engine Output Net Engine Output Typical Generator Set Output

KTA50-G3. Description. Features rpm (50 Hz Ratings) 1800 rpm (60 Hz Ratings)

KTA38-G5. Features. Description rpm (50 Hz Ratings)

TAD1641GE VOLVO PENTA GENSET ENGINE

Perkins. Perkins. Dimensiones (Largo x Ancho x Alto)cm Peso Aprox. humedo kg. 202x76x x68x

Perkins. Perkins. Perkins. 175x68x Dimensiones (Largo x Ancho x Alto)cm Peso Aprox. humedo kg.

TAD1344GE VOLVO PENTA GENSET ENGINE

موتور ديزل : Cummins. ژنراتور : Stamford. Standby. Prime KVA KW KVA KW ديزل ژنراتور 1

kva kw kva Dry Weigt Length Width kg K.U.N.Z. Handels-&Produktions GmbH

Transcription:

- Technical Data Sheet Winding 06

SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. Other standards and certifications can be considered on request. VOLTAGE REGULATORS SX460 AVR - STANDARD With this self excited control system the main stator supplies power via the Automatic Voltage Regulator (AVR) to the exciter stator. The high efficiency semiconductors of the AVR ensure positive build-up from initial low levels of residual voltage. The exciter rotor output is fed to the main rotor through a three phase full wave bridge rectifier. This rectifier is protected by a surge suppressor against surges caused, for example, by short circuit. AS440 AVR With this self-excited system the main stator provides power via the AVR to the exciter stator. The high efficiency semi-conductors of the AVR ensure positive build-up from initial low levels of residual voltage. The exciter rotor output is fed to the main rotor through a three-phase full-wave bridge rectifier. The rectifier is protected by a surge suppressor against surges caused, for example, by short circuit or out-of-phase paralleling. The AS440 will support a range of electronic accessories, including a 'droop' Current Transformer (CT) to permit parallel operation with other ac generators. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion. TERMINALS & TERMINAL BOX Dedicated Single Phase generators have 4 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%. NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range. 2

CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT BCI164C WINDING 06 SELF EXCITED STANDARD SX460 OPTIONAL AS440 ± 1.0 % ± 1.0 % SELF EXCITED MACHINES DO NOT SUSTAIN A SHORT CIRCUIT CURRENT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS MAIN STATOR RESISTANCE MAIN ROTOR RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION CLASS H IP23 0.8 SINGLE LAYER CONCENTRIC TWO THIRDS 4 0.255 Ohms AT 22 C SERIES CONNECTED 0.52 Ohms at 22 C 19 Ohms at 22 C 0.134 Ohms PER PHASE AT 22 C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING LINEAR LOAD < 5.0% MAXIMUM OVERSPEED 2250 Rev/Min BEARING DRIVE END BALL. 6309-2RS (ISO) BEARING NON-DRIVE END BALL. 6306-2RS (ISO) 1 BEARING 2 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR² INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE TELEPHONE INTERFERENCE 103 kg 31.2 kg 31.4 kg 0.117 kgm 2 110 kg 64 x 54 x 72(cm) THF<2% 106 kg 31.2 kg 32.18 kg 0.1171 kgm 2 116 kg 64 x 54 x 72(cm) TIF<50 COOLING AIR VOLTAGE SERIES VOLTAGE PARALLEL 220 110 0.09 m³/sec 191 cfm 230 115 240 120 kva BASE RATING FOR REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS X'd DIR. AXIS TRANSIENT X''d DIR. AXIS SUBTRANSIENT Xq QUAD. AXIS REACTANCE X''q QUAD. AXIS SUBTRANSIENT XL LEAKAGE REACTANCE X2 NEGATIVE SEQUENCE X0 ZERO SEQUENCE 10.8 1.817 0.186 0.116 0.903 0.208 0.072 0.174 0.079 10.8 1.662 0.170 0.106 0.826 0.190 0.066 0.159 0.072 10.8 1.527 0.156 0.098 0.758 0.175 0.061 0.146 0.066 REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED T'd TRANSIENT TIME CONST. 0.016s T''d SUB-TRANSTIME CONST. 0.004s T'do O.C. FIELD TIME CONST. 0.3s Ta ARMATURE TIME CONST. 0.005s SHORT CIRCUIT RATIO 1/Xd 3

Winding 06 SINGLE PHASE EFFICIENCY CURVES 4

Winding 06 Locked Rotor Motor Starting Curve 30 220V 230V 240V 25 PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 0 5 10 15 20 25 LOCKED ROTOR kva 5

Winding 06 / 0.8 Power Factor 60Hz RATINGS Class - Temp Rise Cont. F - 105/40 C Cont. H - 125/40 C Standby - 150/40 C Standby - 163/27 C Series (V) 220 230 240 220 230 240 220 230 240 220 230 240 Parallel (V) 110 115 120 110 115 120 110 115 120 110 115 120 kva 10.0 10.0 10.0 10.8 10.8 10.8 kw 8.0 8.0 8.0 8.6 8.6 8.6 Efficiency (%) 75.4 76.0 76.4 74.9 75.5 76.0 kw Input 10.6 10.5 10.5 11.5 11.4 11.4 N/A N/A DIMENSIONS Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100 2006 TD_BCI164C.06.GB_10.06_02_GB