CGMCOSMOS-2LV. MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB

Similar documents
CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

cgm.3 system Fully SF6 gas insulated medium voltage switchgear up to 40.5 kv in accordance with IEC Standards

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

ormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION

cpg.0 GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards

ormaset-m Prefabricated metallic transformer substation

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

CPG.0 Single busbar gas-insulated cubicles

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

ormaset Kiosk-type prefabricated transformer substation General Instructions IG-049-EN, version 02, 02/10/2017 LIB

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

ormadis-s Underground prefabricated transformer substations

For your safety! Foreword

PIX-H Metal-clad switchgear up to 17.5kV

Gas Insulated Metal-clad Switchgear, HMGS!

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

NXPLUS C Single busbar. Maintenance-free for lifetime

CGM.3 Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

MESG 12 / 17.5 / 24 / 36 KV

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

Benefits, typical uses

GMA. Medium-voltage switchgear

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

B kv T&D GAS INSULATED SWITCHGEAR

ZX2 Gas-insulated medium voltage switchgear

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

B kv Gas-insulated Substations

8DJ. Maintenance-free for lifetime

UniGear. Technical Guide

CTC UNDER POLE COMPACT TRANSFORMER SUBSTATION

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

SF6 Gas-Insulated Metal Enclosed Switchgear

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

cpg.0 Reliable innovation. Personal solutions. Family of GIS metal-enclosed switchgear assemblies

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais

Modular medium-voltage switchgear. NorMax

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

UniSec Operation and maintenance manual

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

cgm.3 Reliable innovation. Personal solutions. Modular, compact system (RMU) with full gas insulation

SOUTH AFRICAN NATIONAL STANDARD

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais

cpg.0 y cpg.1 Reliable innovation. Personal solutions. Families of single and double busbar GIS-type cubicles

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

CBGS-0. Medium voltage distribution

MCset 4-24 kv Withdrawable SF6 circuit breaker

Product catalogue. ABB AS, Power Products Division SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus 36

ZX2.2 Gas-insulated medium voltage switchgear

ZX-Family Gas-insulated medium voltage switchgear

Unified requirements for systems with voltages above 1 kv up to 15 kv

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

Medium Voltage Distribution Catalogue Flusarc Make the most of your energy

36kV Gas Insulated Medium Voltage Switchgear

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Contents. The RM6 range

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A

EISHO TEK. Vacuum Circuit Breaker

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus kv ABB

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

Product manual. SafeRing/SafePlus 36 kv SF 6. insulated Ring Main Unit and Compact Switchgear

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities.

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

SF6 LOAD BREAK SWITCH. Remote Controlled OCR TELE_1_2013.EN

1. Safety practices General Introduction Standards...3

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

cgm.3 2 ry Distribution Switchgear

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

PATENT PENDING. Phone: (877) Operation and Service Manual

Instruction for Installation and Operation

Metal Clad Air Insulated Switchgear

Medium-Voltage Switchgear OPERATING INSTRUCTIONS

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

RAPIER DSB Disconnectors

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Transcription:

IG-179-GB GENERAL INSTRUCTIONS FOR IG-179-GB General Instructions MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB Transformer Substations Primary Distribution Switchgear Secondary Distribution Switchgear Protection and Automation Low Voltage Boards Distribution Transformers Page 1 of 53

Legal Deposit: 1983/2011 CAUTION! When MV equipment is operating, certain components are live, other parts may be in movement and some may reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks. In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on the following criteria: Elimination of hazards wherever possible. Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are incorporated in the equipment. Communication about remaining risks to facilitate the design of operating procedures which prevent such risks, training for the personnel in charge of the equipment, and the use of suitable personal protection equipment. Use of recyclable materials and establishment of procedures for the disposal of equipment and components so that once the end of their useful lives is reached, they are duly processed in accordance, as far as possible, with the environmental restrictions established by the competent authorities. Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of the forthcoming IEC standard 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the situation according to current legislation. The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically: The equipment must be handled and transported appropriately from the factory to the place of installation. All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment or its essential components. Service conditions must be compatible with the equipment rating. The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable operating and safety principles must be clearly understood. Maintenance should be performed properly, taking into account the actual service and environmental conditions in the place of installation. The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts. Guarantee The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this equipment and its repair by the user shall constitute a violation of the guarantee. Registered Trademarks and Copyrights All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual belongs to the manufacturer. In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject to change without prior notification. These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal s Technical - Commercial Department.

IG-179-GB GENERAL INSTRUCTIONS FOR CONTENTS 1 MAIN DESCRIPTION... 4 1.1... 4 1.2 APPLIED STANDARDS... 4 2 COMPONENTS OF... 5 3 TECHNICAL CHARACTERISTICS... 11 3.1 MECHANICAL CHARACTERISTICS: DIMENSIONS AND WEIGHTS... 11 4 TRANSPORTATION... 13 4.1 LIFTING METHODS... 13 4.2 LOCATION OF ACCESSORIES DURING TRANSPORT... 14 5 STORAGE... 15 6 INSTALLATION... 16 6.1 CIVIL ENGINEERING WORKS FOR INDOOR INSTALLATIONS... 16 6.2 UNPACKING THE EQUIPMENT... 17 6.3 FASTENING TO THE FLOOR... 18 6.4 EARTHING THE EQUIPMENT... 23 6.5 CABLE CONNECTION... 23 7 SEQUENCE OF OPERATIONS... 35 7.1 CHECKING VOLTAGE PRESENCE AND PHASE BALANCE... 35 7.2 OPERATING LEVERS... 36 7.3 FEEDER FUNCTIONAL UNIT... 37 7.4 CIRCUIT-BREAKER... 41 7.5 CABLE TEST... 45 7.6 FITTING THE CABLE COMPARTMENT ACCESS COVER... 45 7.7 INTERLOCKS... 46 8 MAINTENANCE... 47 8.1 VOLTAGE PRESENCE / ABSENCE DETECTOR... 47 8.2 SPARES AND ACCESSORIES... 48 8.3 ENVIRONMENTAL INFORMATION... 48 9 ANNEX 1: ANCHORING DIAGRAM... 50 10 ANNEX 2: AUXILIARY CIRCUITS... 51 10.1 COILS... 51 10.2 MOTORIZED UNITS... 51 11 ANNEX 3: RECOMMENDED CABLE CONNECTION TERMINALS... 52 Page 3 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 1 MAIN DESCRIPTION 1.1 consists of a fully insulated SF 6 multifunctional cubicle, which can be used in secondary electrical distribution diagrams up to 12 kv. It is made up of 3 fully SF 6 insulated functional units: Two feeder functional units One circuit-breaker protection functional unit. 1.2 APPLIED STANDARDS Figure 1.1: single-wire diagram This cubicle system has been designed to meet the requirements of the following standards: Standard IEC 62271-1 SANS 1874 / NRS 006 SANS 62271-200 / IEC 62271-200 SANS 62271-100 / IEC 62271-100 SANS 62271-102 / IEC 62271-102 SANS 60265-1 / IEC 60265-1 SANS 60529 / IEC 60529 SANS 61243-5 / IEC 61243-5 SANS 62271-202 / IEC 62271-202 Description High-voltage switchgear and control gear Part 1: Common specifications standards. Switchgear metal-enclosed ring main units for rated A.C. voltages above 1 kv and up to and including 36 kv. Alternating current metal-enclosed switchgear and control gear for rated voltages above 1 kv and up to and including 52 kv. High-voltage switchgear. Part 100: High voltage alternating current circuitbreakers. Alternating current disconnectors and earthing switches. High Voltage switches for rated voltages above 1 kv up to and including 52 kv. Degrees of protection provided by enclosures. Voltage detectors - Voltage detecting systems (VDS). High-voltage switchgear and control gear Part 202: High-voltage/low-voltage prefabricated substation. Page 4 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 2 COMPONENTS OF is made up of a series of independent compartments, as shown in the next figure. 1 2 4 5 6 3a 3 3b 3c 1 Pressure relief duct (for outdoor installations) 3c Gas relief compartment 2 Tank 4 Name plate 3 Base 5 Driving mechanism compartment 3a Cable test facilities 6 ekorivds 3b Cable compartment Figure 2.1: Main components of Page 5 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB Tank: keeps the switching and breaking elements, as well as busbars inside a unique stainless steel SF 6 -filled tank which is permanently sealed, thus building a fully insulated unit. Figure 2.2: Tank The tank has a manometer for checking the gas pressure, which can easily be seen from outside the cubicle. The manometer scale is divided into different colors: red, grey and green. For safe operation, the needle must be in the green zone of the corresponding temperature band. A membrane at the bottom of the tank allows gases to escape in the event of an internal arc. Figure 2.3: Manometer Inside the tank we find: The Switch-Disconnector and Earthing Switch. This component has three positions: closed, open and earthing. The operation is carried out using the actuating lever on 2 different shafts in the same driving mechanism: one for the switch (switching between the closed and open positions) and another for the earthing switch (which switches between the open and earthing positions). These elements are manually operated in an independent way, i.e., their actuation speed does not depend on the speed of the lever during the manual operation. The protection circuit-breaker and earthing switch: The protection circuit-breaker uses vacuum switching technology. The operation is carried out using 2 different actuating levers on 2 different shafts in the same driving mechanism: one for the circuit-breaker (switching from open to closed position) Page 6 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR and another for the earthing switch (which switches between the open and earthing positions). During the closing operation of the circuit-breaker, with its actuating lever, the springs are charged and the unit gets prepared for opening. The circuit-breaker is opened by means of the button on the front of the unit. The protection circuit-breaker is also capable to ensure the isolating distance by means of its associated disconnector, and has earthing switching capacity. These elements are manually operated in an independent way, i.e., their actuation speed does not depend on the speed of the lever during the manual operation. Driving Mechanism Compartment: This is the compartment in which the switch-disconnector or the circuit-breaker is actuated, depending on the type of functional unit. The mimic diagram for the MV main circuit is displayed on the cover of this compartment, and includes all the position indicators for the actuators. 1 8 2 3 7 4 5 6 1 Protection unit 5 Status indicators Operation area: 2 GREY for circuit-breaker 6 Voltage presence/absence detector ekorivds YELLOW for earthing switch 3 Spring charge indicator 7 Locking with a padlock 4 Operation counter 8 Manometer window Figure 2.4: Mimic diagram of circuit breaker function Page 7 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 4 1 3 2 1 Operation area: GREY for switch disconnector 3 Status indicators YELLOW for earthing switch 2 Voltage presence/absence detector ekorivds 4 Locking with a padlock Figure 2.5: Mimic diagram of feeder function NOTE The B and BM driving mechanisms can be replaced (due to improved characteristics) in any of the three switchdisconnector positions. These positions can be blocked on the B and BM mechanisms by means of a padlockable fixing device, whether or not the function is operating. The BR-AV and BR-AMV driving mechanisms can be replaced in either open or earthing positions (never when the circuit-breaker is closed). Figure 2.6: Fixing device DANGER Only personnel specially trained and approved by Ormazabal can replace the driving mechanisms. Base: Made up of the cable test facilities, cable compartment and the gas relief compartment: Cable test facilities: located in the intermediate front section of the cubicle, it has a cover interlocked with the earthing switch, thus allowing front access to the cable test female bushings. Cable compartment: located in the lower front section of the cubicle, it has a cover interlocked with the earthing switch and with the cable test facilities. The function has to be in its earthing position and it s needed to remove the cable test facilities cover before you have front access to the Medium Voltage cables. Figure 2.7: Cable compartment Page 8 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR The cable compartment is designed to contain up to: 1 shielded screw-in terminal per phase with space for the corresponding incoming power cables (three-core or single-core cables for feeders and single-core cables for circuit-breaker). Cable ties for the power cables. Earthing bars Gas relief compartment: This is located in the lower bottom section of the unit. In the event of an internal arc, the gases produced are deflected downwards, to the rear and upside, and in no way affecting any persons, cables, or the rest of the Transformer Substation switchgear. ekorivds The ekorivds unit displays three signals which correspond to each of the phases. The presence of voltage is indicated in each phase by means of flashing indicators. The ekorivds unit indicates presence of voltage within the operating range specified in standard SANS 61243-5 / IEC 61243-5. The ekorivds unit displays the following indications: L1, L2, L3 Figure 2.8: Voltage presence / absence detector Display each of the indicator phases The numbering corresponds to the order of the phases, from left to right, seen from the front of the cubicle. Each phase has a test point for checking the phase balance between cubicles. Test point connected to earth This is only used for comparing the phases. Voltage presence indicator A flashing light indicates the presence of voltage in that phase. The purpose of the test points for the three phases and earth is to make it easier to check the phase balance between functional units. Ormazabal s specific phase comparator ekorspc can be used to do this. NOTE If the indicators do not light up, use other means to check that there is no voltage. Page 9 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB Name plate has a name plate indicating some of the following values: No. Cubicle serial number (*) Figure 2.9: Name plate on Designation General instru. Standards U r U p U d f r I r Class n I k / I p t k IAC SF 6 P me P re Sequence Ormazabal cubicle model Manual of General Instructions (IG-179) Regulations applied to the equipment Rated voltage (kv) Lightning impulse withstand voltage (kv) Power frequency withstand voltage (kv) Rated frequency (Hz) Rated current (A) Breaking element classification according to IEC Number of mainly active load breaking operations Short-time withstand current/short-time withstand peak value Short-time withstand current time Internal Arc Classification Weight of insulating fluid (g) Minimum operating gas pressure (MPa) Gas pressure inside the tank (MPa) Circuit-breaker rated sequence I SC Ic Year Rated short-circuit switching current in circuit-breaker function (ka) Cable charging switching current in circuit-breaker function (A) Year of manufacture TC Thermal class (ºC) ( * ) In the event of a problem or non-conformity, note down this number and send it to Ormazabal's Technical - Commercial Department. Page 10 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 3 TECHNICAL CHARACTERISTICS 3.1 MECHANICAL CHARACTERISTICS: DIMENSIONS AND WEIGHTS a Width h Cubicle height f Depth i Bushings height (protection position) g Bushings height (feeder position) k Pressure relief duct height Figure 3.1: dimensions (with pressure relief duct - Outdoor installations) Pressure relief duct height (k) [mm] Cubicle height (h) [mm] Width (a) [mm] Depth (f) [mm] 1700 1500 1095 940 Bushings Height [mm] Feeder Position (g) Protection Position (i) 800 485 Weight [kg] 440 Page 11 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB a Width h Height f Depth i Bushings height (protection position) g Bushings height (feeder position) Figure 3.2: dimensions (without pressure relief duct - Indoor installations) Height (h) [mm] Width (a) [mm] Depth (f) [mm] 1500 1095 823 Feeder Position (g) Bushings Height [mm] Protection Position (i) 800 485 Weight [kg] 420 Page 12 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 4 TRANSPORTATION 4.1 LIFTING METHODS For indoor installations, the cubicles must always be kept upright, directly on the ground or on a pallet depending on the type of handling involved. To handle, one of the following methods must be used: 1. Using a forklift truck or hand-operated pallet truck [1] Figure 4.1: Lifting using a fork-lift truck 2. Raising it using slings fixed to the lifting supports on the sides of the top of the cubicle. The angle of pull should be as vertical as possible (with an angle greater than 60º from the horizontal). Figure 4.2: Lifting with slings ATTENTION The use of lifting beams is required for cubicle assemblies with control boxes. As the sole exception, slings may be used if the cubicles of the assembly have identical height control boxes installed. [1] Position the rear of the cubicle facing the driver, to avoid damaging the front. Page 13 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 3. If it is not possible to use the aforementioned methods, rollers may be used underneath the cubicles. Another option is to slid the cubicles over rods (these same rods can be used to help get over the trench). 4.2 LOCATION OF ACCESSORIES DURING TRANSPORT During transport, the cubicle must be perfectly seated and fixed so that it cannot move about and possibly damage the equipment. A number of accessories are supplied with the cubicles, located on the roof of the tank, as indicated in the following figure: 1 1 Accessory Box Figure 4.3: Location of accessories during transport The accessory box contains the following items: Ormazabal s IG-179 General Instructions Document Actuating levers Floor fastening assembly Page 14 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 5 STORAGE If it needs to be stored, the equipment must be placed on dry ground or on top of damp-proof insulating material, still in its original packaging. After prolonged storage, clean all the insulating parts carefully before commissioning the equipment. The enclosure should be cleaned with a clean dry lint-free cloth. 55ºC max - 5ºC min Figure 5.1: Storage Maximum height above sea level 2000 m Store in non-corrosive environments The equipment must be adjusted to the atmospheric pressure of the installation site; otherwise, the manometer needle may indicate an incorrect value (red scale) even if the internal pressure is correct. Page 15 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 6 INSTALLATION 6.1 CIVIL ENGINEERING WORKS FOR INDOOR INSTALLATIONS The minimum distances to the walls and roof, and from the trench for the MV cables are as follows: b d a c Figure 6.1: Distances for civil engineering works (without pressure relief duct - Indoor installations) Minimum Distances [mm] Cubicle Side wall (a) 100 Ceiling (b) 600 Clearance (c) 800 Rear wall (d) > 100 These measurements have been obtained in accordance with the internal arc tests which have been carried out, according to Annex A of standard IEC 62271-200. Page 16 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 6.2 UNPACKING THE EQUIPMENT comes wrapped in protective plastic. On receiving the equipment, check that the goods supplied correspond to the order and associated documentation. The procedure for unpacking the equipment is as follows: 1. Using a blade, cutter or similar tool, cut the cellophane wrapped around the cubicle [2]. 2. Remove the cellophane. 3. Detach the white polystyrene corner pieces. 4. Unscrew the fixings between the base and the pallet. 5. Remove the pallet, handling the cubicle as indicated in section 2.1. 6. Unpack the accessory box located at the top of the cubicle. 7. Remove the self-adhesive protective plastic from the cable compartment cover. Remove the cover. 8. Dispose of any waste in an environmentally-friendly manner. It is advisable to make a visual inspection of the equipment to check whether it has suffered any damage in transit. If so, contact Ormazabal s Technical - Commercial Department immediately. ATTENTION The self-adhesive plastic must be removed from the cable compartment cover so that the equipment enclosure s earth connection may have the proper electrical continuity. [2] It is advisable to cut the cellophane at the rear of the cubicle or at the corner to avoid scratching the surface. Page 17 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 6.3 FASTENING TO THE FLOOR Before assembling, the floor must be carefully leveled to prevent any deformation. The unit can be fastened to the floor in two ways: 6.3.1 Floor Fastening on a Profile If the floor of the Transformer Substation is not sufficiently uniform, it is advisable to install the MV cubicle assembly on an auxiliary profile. This profile must be anchored to the floor using expansion screws. 1 2 3 1 M10 x 25 screw 3 Anchoring support 2 66 x 65 x 4 mm profile Figure 6.2: Location of on profile 6.3.2 Fastening to the Floor by Anchoring If the floor of the Transformer Substation is even enough, it is advisable to install directly anchored to the floor. The sequence for anchoring the cubicles to the floor is as follows: NOTE By default, is supplied with the switches in earthing position. Page 18 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 1. The unit's switches must be in the earthing position [3]. 2. Remove the two covers of the cable test facilities, using its central handle to pull it up and forward as indicated in the figure. Figure 6.3: Removing the cable test facilities cover 3. Unscrew the screws and remove the cable compartment cover, using the central handle on the cover to pull it up and forward as indicated in the figure. Figure 6.4: Removing the cable compartment cover [3] See section 7. Sequence of Operations Page 19 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 4. Anchor the cubicle to the floor of the Transformer Substation using screws through the holes made in the base for this purpose. This will prevent vibrations or movements due to short-circuits, possible flooding of the Transformer Substation, etc. Anchoring dimensions are shown in annex 1. To have access to the front fastening points, the cable support clamp, the rubber grommet and gland plates have to be removed as shown in the figures. 2 1 3 1 Cable support clamp 2 Rubber grommet 3 Gland plates Figure 6.5: Cable support clamp, rubber grommet and gland plates Figure 6.6: Cable support clamp removed Figure 6.7: Rubber grommet and gland plates removed Page 20 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 1 1 Front fastening points Figure 6.8: Access to the front fastening points If there is enough free space to access the back of the cubicle, rear fastening points can be anchored through the rear holes of the base. Figure 6.9: Rear accessibility Page 21 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB In an installation with the cubicle near the rear wall, the intermediate division plate can be dismounted to gain accessibility to the rear anchoring points. Figure 6.10: Intermediate division plate to be dismounted Figure 6.11: Access to rear anchoring point CAUTION After anchoring the unit to the floor, do not forget to fix the intermediate division plate again. Take special care with the lower flange. Another possibility for rear anchoring points is to fasten the cubicle to the floor via the two anchorage holes on the side. Figure 6.12: Fixing the cubicle with a side L piece via holes on the side Page 22 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 6.4 EARTHING THE EQUIPMENT DANGER Earthing the equipment is an essential condition for safety. At each side of, connect the end earthing bar to the transformer substation s general earth connection. Figure 6.13: earth connector 6.5 CABLE CONNECTION DANGER Never touch live connectors, not even screened connectors. Screening does not constitute a protection against direct contact. When the equipment is in service and a reserve cubicle is left with voltage in the upper busbar and without the cables in the lower bushings, insulating plugs must be placed in the bushings (EUROMOLD type) or close the earthing switch and lock that position with a padlock. The MV feeder inputs, as well as outputs to the transformer or other cubicles are via cables. These cables and the corresponding bushings on can be connected with reinforced (screw-in) connecting points, IEC type. The recommended terminals are described in annex 3. Page 23 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 6.5.1 Front Connection 1. Close the earthing switch. 2. Remove the cover to access the cable test facilities, using its central handle to pull it up and forward. Figure 6.14: Remove cable test facilities cover 3. Unscrew the screws and remove the cable compartment cover, using the central handle on the cover to pull it up and forward Figure 6.15: Remove cable compartment cable cover Page 24 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 4. The next step varies depending on the type of cable and functional unit. You can thus find two cases: 4a. three-core-cable in feeder position 4b. single-core cable in feeder or protection position 4a. Case of three-core cable (feeder position) a) Dismount the front angular sheet. Figure 6.16 b) Dismount the cable support clamp. Figure 6.17 Page 25 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB c) Dismount the rubber grommet and gland plates. Figure 6.18 d) Mount the cable support clamp as shown in the figure below. Next, fit the rear gland plate. Then, loosen the cable clamp. Figure 6.19 Page 26 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR e) Connect the terminals on the front bushings. Figure 6.20 f) Secure the cables using the rubber grommet, as well as the cable clamp. Figure 6.21 Page 27 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB g) Mount the front gland plate. Figure 6.22 h) Mount the front angular sheet. Figure 6.23 Page 28 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 4b. Case of single-core cable (feeder position and protection position) a) Dismount the front angular sheet. Figure 6.24 b) Dismount the cable support clamp Figure 6.25 Page 29 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB c) Dismount the rubber grommets and gland plates. Figure 6.26 d) Mount the cable support clamp as shown in the figure below. Next, fit the rear gland plate. Then, loosen the cable clamps. Figure 6.27 Page 30 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR e) Connect the terminals on the front bushings. Figure 6.28 f) Secure the cables using the rubber grommets, as well as the cable clamps. Figure 6.29 Page 31 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB g) Mount the front gland plate. Figure 6.30 h) In the case of a protection position, mount the current transformers Figure 6.31 Page 32 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR i) Mount the front angular sheet. FEEDER POSITION Figure 6.32 PROTECTION POSITION 5. Connect the terminal earth connectors and the cable screen earth connectors if applicable. Figure 6.33: Terminal earth connection Page 33 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB Figure 6.34: View of all the cables connected 6. Put the cable compartment cover back in place. 7. Put the cable test facilities cover back in place. Page 34 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7 SEQUENCE OF OPERATIONS ATTENTION Before carrying out any operation when voltage is present, check the SF 6 pressure with the manometer. gas ATTENTION For safety reasons, maintenance operations performed directly on the driving mechanism must be performed WITHOUT any actuating lever inserted. 7.1 CHECKING VOLTAGE PRESENCE AND PHASE BALANCE Ormazabal s ekorspc [4] phase comparator should be used for checking that the MV cables are correctly connected to the Transformer Substation feeder cubicles. Firstly, connect the red cables of the ekorspc unit to the corresponding phase test points on the ekorivds [5] units, and the black cable to the earth test point. This operation must be repeated for all the phases L1, L2 and L3. Figure 7.1: ekorspc unit Balanced phases Figure 7.2: Comparison of phases Unbalanced phases [4] Optionally, other comparison devices which comply with the IEC 61958 standard may be used. [5] See section 1.1.1. ekorvpis- Voltage Presence Indicator Unit. Page 35 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.2 OPERATING LEVERS 7.2.1 Lever for feeder This lever is used for operating the feeder functional units of with driving mechanisms B and BM. It is an anti-reflex lever that is used for closing and opening operations in both the switchdisconnector and the earthing switch. 7.2.2 Lever for circuit-breaker Two levers are used for operating the BR-AV and BR-AMV mechanisms of the circuitbreaker position of. One is used for the closing operations of the circuit-breaker. The other is used for closing and opening operations of the earthing switch (this is the same lever as the one used in the feeder functional units). Figure 7.3: Feeder lever Figure 7.4: Circuit-breaker levers Page 36 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7.3 FEEDER FUNCTIONAL UNIT 7.3.1 Opening Operation from the Earthing Position 1. Move the actuation shaft access handle in the yellow zone to its lower position. 2. Insert the lever in the earthing switch actuation shaft. 3. Turn the lever anticlockwise. Figure 7.5: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.6: Turn lever anticlockwise 5. Verify that the feeder is in disconnected position. Figure 7.7: Verify feeder disconnection Page 37 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.3.2 Switch Closing Operation from the Open Position 1. Move the actuation shaft access handle in the grey zone to its lower position. 2. Insert the lever in the switchdisconnector actuation shaft. 3. Turn the lever clockwise. Figure 7.8: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.9: Turn lever clockwise 5. Verify that the feeder is in connected position. Figure 7.10: Verify feeder connection Page 38 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7.3.3 Opening Operation from the Closed Position 1. Move the actuation shaft access handle in the grey zone to its lower position. 2. Insert the lever in the switchdisconnector actuation shaft. 3. Turn the lever anticlockwise. Figure 7.11: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.12: Turn lever anticlockwise 5. Verify that the feeder is in disconnected position. Figure 7.13: Verify feeder disconnection Page 39 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.3.4 Earthing Operation from the Open Position 1. Move the actuation shaft access handle in the yellow zone to its lower position. 2. Insert the lever in the earthing switchactuation shaft. 3. Turn the lever clockwise. Figure 7.14: Move actuation shaft access handle 6. Remove the lever. The handle returns to its original position. Figure 7.15: Turn lever anticlockwise 7. Verify that the feeder is in earthing position. Figure 7.16: Verify earthing position Page 40 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7.4 CIRCUIT-BREAKER 7.4.1 Opening Operation from the Earthing Position 1. Move the actuation shaft access handle in the yellow zone to its lower position. 2. Insert the lever in the earthing switchactuation shaft. 3. Turn the lever anticlockwise. Figure 7.17: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.18: Turn lever anticlockwise 5. Verify that the circuit-breaker is in disconnected position. Figure 7.19: Verify circuit-breaker disconnection Page 41 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.4.2 Switch Closing Operation from the Open Position 1. Move the actuation shaft access handle in the grey zone to its lower position. 2. Insert the lever in the circuit-breaker actuation shaft. 3. Move the lever up and down until the status indicator changes. Figure 7.20: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.21: Turn lever clockwise 5. Verify that the circuit-breaker is in connected position. Figure 7.22: Verify circuit-breaker connection Page 42 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7.4.3 Opening Operation from the Closed Position 1. Press the red button. Figure 7.23: Location of red button 2. Verify that the circuit-breaker is in disconnected position. Figure 7.24: Verify circuit-breaker connection Page 43 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.4.4 Earthing Operation from the Open Position 1. Move the actuation shaft access handle in the yellow zone to its lower position. 2. Insert the lever in the earthing switchactuation shaft. 3. Turn the lever clockwise. Figure 7.25: Move actuation shaft access handle 4. Remove the lever. The handle returns to its original position. Figure 7.26: Turn lever clockwise 5. Verify that the circuit-breaker is in earthing position. Figure 7.27: Verify earthing position Page 44 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 7.5 CABLE TEST is equipped with cable test facilities. For more information on how to perform the cable test, please refer to Ormazabal's Spare parts and accessories instruction document RA-235. 7.6 FITTING THE CABLE COMPARTMENT ACCESS COVER 1. Rest the cover on the lower profile of the base 2. Lift the cover slightly until it engages in the side slots on the base Figure 7.28: Rest the cover on the lower profile 3. Push the cover down until the top engages in place Figure 7.29: Lift the cover until it engages Figure 7.30: Push the cover down 4. Screw the cover with two M8 bolts. Figure 7.31: Tops engaged in place ATTENTION Before carrying out any operation it s mandatory to screw the cover with the two M8 bolts with a 25 Nm torque. NOTE To unlock the cable compartment access cover, reverse the sequence of operation. Page 45 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 7.7 INTERLOCKS 7.7.1 Locking with a padlock The cubicles are supplied with an independent padlock interlock for both the switchdisconnector, in its closed or open positions, and the earthing switch, in its closed or open positions. Padlocks with ring diameters of between 8 and 12 mm can be used. NOTE Figure 7.32: Feeder Unit with padlock interlock In the case of the circuit-breaker unit, it is also possible to lock it by padlock. Page 46 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 8 MAINTENANCE ATTENTION For safety reasons, maintenance operations performed directly on the driving mechanism must be performed WITHOUT any actuating lever inserted. The live parts of s main circuit and switching equipment do not require inspection or maintenance, as they are completely insulated in SF 6 and therefore unaffected by the external environment. Class E2 electrical endurance tests mean there is no restriction on maintenance of the breaking components. The operating mechanism for switching equipment does not require lubrication for correct operation, according to the service conditions specified in IEC 62271-1, throughout its estimated lifetime. These mechanisms must be inspected when used under extreme conditions (dust, salt, pollution). It is advisable to carry out at least one operation during the inspections. Components manufactured from galvanized sheet steel have been painted to ensure their resistance to corrosion. Any scratches, dents or similar on them must be repaired to prevent corrosion. 8.1 VOLTAGE PRESENCE / ABSENCE DETECTOR To test the ekorivds voltage presence/absence detector, connect it to a 230 Vac power supply. To do this, disconnect it from the cubicle and, using 4 mm terminals, apply voltage between the test point for the phase to be checked and the earth test point. Polarity does not apply to the 230 Vac connection, so the phase and neutral can be connected either way. If an intermittent light signal is observed, the indicator is working correctly. To correctly test the indicator, this check should be carried out for all three phases. The ekorivds indicator can be replaced if necessary. To do so, remove the two screws on the top right and bottom left of the indicator. The indicator can then be disconnected from the base without needing to power down the feeder. Figure 8.1: ekorivds connection Page 47 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 8.2 SPARES AND ACCESSORIES Although the unit has been designed for a service life in accordance with IEC 62271-200, certain components can be replaced and installed for various reasons. NOTE Certain spares and accessories must be installed in the cubicle by specialized personnel. Please contact Ormazabal's Technical - Commercial Department. Driving mechanism [6] Switch Disconnector Circuit-Breaker Position Position B X - BM X - BR-AV - X BR-AMV X Opening coil X X Bistable X X Actuating lever X X Protection, Metering and Switch Disconnector Circuit-Breaker Control Position Position ekorivds [7] X X ekorvpis X X ekorspc X X Enclosure Switch Disconnector Circuit-Breaker Position Position Cable compartment access cover X X Cable test facility cover X X MV cable fixing support X X Others Switch Disconnector Circuit-Breaker Position Position Control box X X Auxiliary profiles for fastening to the floor X X If any of the stated auxiliary components need to be changed, the corresponding spare parts kit must be ordered, and the instructions given in the corresponding documentation must be followed. 8.3 ENVIRONMENTAL INFORMATION is defined as a sealed, pressurized system, according to IEC 62271-1, which contains sulphur hexafluoride (SF 6 ). SF 6 is included in the Kyoto Protocol list of greenhouse gases. SF 6 has a GWP (Global Warming Potential) of 22,200 units. (TAR, IPCC 2001). [6] Components which can only be replaced by specially qualified Ormazabal personnel. [7] Components which can only be replaced by specially qualified Ormazabal personnel. Page 48 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR At the end of the product's life, the SF 6 contained in it must be recovered for processing and recycling, to prevent it being released into the atmosphere. Extracting and handling of SF 6 must be carried out by qualified personnel, using a sealed piercing system. For the usage and handling of the SF 6, the indications listed in IEC 62271-303 must be followed. Page 49 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 9 ANNEX 1: ANCHORING DIAGRAM Figure 9.1: : Anchoring diagram Page 50 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR 10 ANNEX 2: AUXILIARY CIRCUITS 10.1 COILS The electrical characteristics of the coil and contact indicating the switch position are as follows: Tripping Coil Indicating Contact Electrical Characteristics Driving Mechanism BR-AV Rated Voltage Maximum consumption Internal Insulation Opening Time Break Time Closing Time Switch position indicating contacts Rated Voltage Rated Current 24 V dc 130 W 2 kv 55 ms 65 ms 55 ms 2 NO + 2 NC 250 V ac 16 A 10.2 MOTORIZED UNITS The electrical characteristics are as follows: Electrical Characteristics Driving Mechanism BM Driving Mechanism BR-AMV Rated Voltage 24 V dc 24 V dc Motorized units Indicating Contact Peak current <5 A <15 A Motor operation time 3 s <20 s Motor Consumption 50 W 50 W Switch indication contacts 2 NO + 2 NC 2 NO + 2 NC Earthing indication contacts 1 NO + 1 NC 1 NO + 1 NC Rated Voltage 250 V ac 250 V ac Rated Current 16 A 16 A NOTE The electrical diagrams are supplied with the order documents. Page 51 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB 11 ANNEX 3: RECOMMENDED CABLE CONNECTION TERMINALS Type Cable Dry insulation Impregnated cable Connector SCREENED Manufacturer Cable connections Current rating [A] 12 kv Connector type Section [mm 2 ] 630 450SR 70-300 630 400LB 50-300 EUROMOLD ( * ) 630 400TB 70-300 630 440TB 185-630 KABEL-DRAHT 630 SEHDT13 185-240 NKT 630 AST 10/630 25-240 EUROMOLD ( * ) 630 15TS 35-630 NOT SCREENED KABEL-DRAHT 630 SEHDG12 35-185 630 UHGK+RICS 120-300 RAYCHEM 630 IXSU+RICS 16-800 SCREENED EUROMOLD ( * ) 630 K-400TB-MIND 25-240 NOT SCREENED RAYCHEM (*) Connectors tested in CGMCOSMOS cubicles. 630 UHGK+RICS 120-300 630 IXSU+RICS 16-800 Page 52 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR NOTES Page 53 of 53

GENERAL INSTRUCTIONS FOR IG-179-GB NOTES Page 54 of 53

IG-179-GB GENERAL INSTRUCTIONS FOR NOTES Page 55 of 53

TECHNICAL COMMERCIAL DEPARTMENT: www.ormazabal.com