User's Manual. Earth Ground Resistance Tester. Model Introduction

Similar documents
Phase Sequence Tester

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

User's Guide. Model RPM10 Laser Photo / Contact Tachometer with IR Thermometer. Introduction

User's Guide. Vane Anemometer. Model Measures Air Velocity & Temperature. Degrees C/F switchable

Model Battery Powered Milliohm Meter

User Guide. Model Insulation Tester / Megohmmeter. Introduction

User's Guide. EzFlex Thermo-Anemometer. Model EZ30 UNITS MAX MIN AVG VEL

Panel Mount Digital Tachometer Model

User's Manual. Model Hot Wire Thermo-Anemometer. Introduction

User's Guide. CO 2 Meter. Model CO250

User's Guide. True RMS Multim eter. Extech 430

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

User Guide. Model Insulation Tester / Megohmmeter

USER GUIDE. Model RH10 Hygro Thermometer. Humidity and Temperature Meter

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

Solar Power Light Meter

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL PSMR1

User Guide. Model Insulation Tester / Megohmmeter

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

Non-Contact Phase Rotation Tester

Digital/Analog Megohmmeter Model 1026 USER MANUAL

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

4-WIRE EARTH RESISTANCE TESTER C1 ES P1 S. Max. AC 200V MICROPROCESSOR CONTROLLED TEST. Switch ON, TEST, SCROLL RESULTS 20Ω 200Ω 2000Ω OFF

Model Insulation Tester / Megohmmeter. User Manual

i400s Calibration Information Introduction

362 Clamp Meter. Users Manual

Non-Contact Phase Rotation Tester

Instruction Manual. Model 307A Analog Insulation & Continuity Meter


PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

Tracer ORP PockeTester TM Code 1742

365 Detachable Jaw True-rms Clamp Meter

OPERATING INSTRUCTION

For technical questions and replacement parts, please call

DT304. Digital Temperature Logger INSTRUCTION MANUAL

MY /2-DIGIT DIGITAL MULTIMETER Users Manual

302+/303 Clamp Meter. Users Manual

Digital/Analog Megohmmeter Model 1026

LH41A. User Manual. Clamp On Ammeter. For detailed specifications and ordering info go to

Mini Multimeter with Non-Contact Voltage Detector (NCV)

USER MANUAL. Insulation Tester + DMM. Model MG320

DIGITAL INSULATION RESISTANCE TESTER (5KV, 1T )

KMP Insulation-Continuity Tester. Users Manual

Safety design conforming to the following provisions

Calibration Manual. Detachable Jaw True-rms Clamp Meter

Visit us at

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale:

Table of Contents Title Page No.

INSTRUCTION MANUAL DM5B Fax: (503)

1 AMP CURRENT SOURCE

373 Clamp Meter. Users Manual

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

712 RTD Calibrator. Instruction Sheet. Introduction

Users Manual. Phase Rotation Indicator

IAQ-CALC INDOOR AIR QUALITY METER MODEL 7515

362 Clamp Meter. Users Manual

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

KMP7010. Ground Resistance Tester. Users Manual

OPERATING INSTRUCTIONS

HIGH VOLTAGE DIGITAL AMMETER

PD-20 HIGH VOLTAGE PROBE INSTRUCTION MANUAL

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc

USER MANUAL. White LED Light Meter. Model LT40. Additional User Manual Translations available at

DAFM4. Digital Air Flow Meter INSTRUCTION MANUAL Fax: (503) ENGLISH DAFM4 VOL CFM

716 Pressure Calibrator

INSP-3 Wiring Inspection Tester

POCKET-TACH 100 MONARCH INSTRUMENT Rev 1.4. Instruction Manual. Printed in the U.S.A. Monarch Instrument 2001 all rights reserved

HIGH VOLTAGE PROVING UNIT

Dawson DDM190D. Digital Multimeter User s Manual

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

323/324/325 Clamp Meter

SECULIFE PS100 PATIENT SIMULATOR

Megohmmeter Test Probe

IAQ-CALC TM Indoor Air Quality Meter

SOIL RESISTIVITY TESTER

OPERATING INSTRUCTIONS

717 Series. Pressure Calibrators. Instruction Sheet. Introduction

Cable Length Meter INSTRUCTION MANUAL

Users Manual. MegOhmMeter

Bio-Pump Plus. Operating Instructions. Product # ZBP-200. Description. Specifications

User's Manual Digital High Voltage Insulation Tester Model

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

TES-1601 INSTRUCTION MANUAL AUTORANGING INSULATION TESTER SAFETY INFORMATION TES ELECTRICAL ELECTRONIC CORP. Warnings and Safety symbols:

OPERATING INSTRUCTION

DIGITAL RCD(ELCB) TESTER

IAQ-CALC TM Indoor Air Quality Meter

AMB V Insulation Resistance Tester. Users Manual. For detailed specifications and ordering info go to

True RMS Autoranging Multimeter

Autoranging Industrial Multimeter

41210S CIRCUIT BREAKER FINDER WITH GFCI Instrucciones de uso Detector de Interruptores con GFCI 41210S. Operating Instructions

Autoranging Multimeter

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter

Indoor Air Quality Meter

OPERATING INSTRUCTION

operating manual DL7 101 DIGITAL THERMOMETER

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

SINGLE STICK DIGITAL VOLTMETER

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

AIR VELOCITY METER ALNOR MODEL AVM410 AIRFLOW INSTRUMENTS MODEL TA410

Model C230 Pump Controller

Transcription:

User's Manual Earth Ground Resistance Tester Model 382152 Introduction Congratulations on your purchase of the Extech Earth Ground Resistance Tester. This device can measure resistance (in 3 ranges) and AC voltage to 200V. 2mA constant current test signal permits earth resistance tests without tripping current breakers in the circuit under test. Single, momentary tests or automatic 3-minute tests can be selected. This device was designed to meet IEC-1010 (EN 61010) safety standards. Earth Ground Resistance Testers are useful for: Estimating ground resistance of a proposed substation or transmission tower. Computing inductive coupling between neighboring power and communication circuits. Designing cathode protection systems. Geological surveys. Careful use of this meter will provide years of reliable service.

Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies to sensors and cables). If it should become necessary to return the instrument for service during or beyond the warranty period, contact the Customer Service Department at (781) 890-7440 ext. 210 for authorization or visit our website www.extech.com for contact information. A Return Authorization (RA) number must be issued before any product is returned to Extech. The sender is responsible for shipping charges, freight, insurance and proper packaging to prevent damage in transit. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation outside of specification, improper maintenance or repair, or unauthorized modification. Extech specifically disclaims any implied warranties or merchantability or fitness for a specific purpose and will not be liable for any direct, indirect, incidental or consequential damages. Extech's total liability is limited to repair or replacement of the product. The warranty set forth above is inclusive and no other warranty, whether written or oral, is expressed or implied. Safety Please read the following safety information carefully before attempting to operate the meter and use the meter only as specified in this manual. Environmental safety information Do not use meter outdoors when precipitation is likely Installation Category III Pollution degree 2 Altitude: 2000 meters max. Ambient conditions: 32 to 104 o F (0 to 40 o C); RH: 80% max Observe the following international safety warning symbols Safety Symbols Caution: Refer to this manual before using this meter Dangerous Voltages Meter is protected throughout by double or reinforced insulation Organizations that provide rules and guidelines for proper grounding The National Electrical Code (NEC) Underwriters Laboratories (UL) National Fire Protection Association (NFPA) American National Standards Institute (ANSI) Occupational Safety Health Administration (OSHA) Telecommunications Industry Standard (TIA) 2

Specifications Measurements Display Data hold Automatic Test Measurement triggers Test lead length Power supply Low battery indication Over-range indication Safety Weight Dimensions Supplied accessories Earth ground resistance (in 3 ranges) and AC voltage to 200V 3-1/2 digit (1999 count) LCD with LED test status indicator Freezes latest reading on the LCD display 3 minute test timer with automatic power down Momentary test or 3 minute test with lock function Red lead: 50' (15m), Yellow: 33' (10m), Green: 16' (5m) Six 1.5V 'AA' batteries (included) LCD displays 'B' icon '1' displayed as most significant digit IEC-1010 (EN-61010) category III 27.7oz. (800g) with batteries 6.42 x 3.94 x 2" (163 x 100 x 50 mm) Test leads (3), auxiliary earth bars (2), six 'AA' batteries, and carrying case Range Specifications Measurement Range Resolution Accuracy Earth Ground Resistance 2mA test current (820Hz) 20, 200, 2000Ω 0.01Ω, 0.1Ω, 1Ω ± (2% rdg + 2 d) or ± 0.1Ω whichever is greater Earth Voltage Frequency: 40 to 500Hz 0 to 200VAC 0.1V ± (1% rdg +2d) Meter Description 1. Earth ground test lead terminal 2. Test status LED 3. Data Hold switch 4. Automatic 3-min. test OFF button 5. LCD Display 6. C1, P1 Aux bar test lead terminals 7. Function select switch 8. Resistance range select switch 9. Push-button momentary test 10. Automatic 3-min. test ON button 3

Operation Test Connection Diagram Red lead Yellow lead Green lead METER C1 Bars equidistant 17 to 33 ft (5 to 10m) apart P1 E 17-33 ft (5-10m) Existing ground connection Ground surface Test Preparation and Setup 1. Connect the test leads to the meter as follows: Green lead to the 'E' terminal Yellow lead to the 'P' terminal Red lead to the 'C' terminal 2. Drive the Auxiliary Earth Bars C1 & P1 (included) into the ground. Align the bars equidistant to the existing Earth ground connection and in a straight line as shown in the diagram above. 3. Ensure that the bars are between 17 and 33 ft (5 and 10 meters) apart. If the auxiliary bars are placed in close proximity to the ground stake, measurement inaccuracies will result. 4. Connect the clamp ends of the test leads to the Earth bars and existing ground connection spike as shown above. Earth Voltage Test 1. Set the meter's function switch to the ACV position. 2. Press the PUSH-ON button to perform a single, momentary test. 3. Press the PUSH-ON and TIMER ON buttons simultaneously to begin a 3-minute test. The 3-minute test automatically shuts down after 3 minutes. Press the Timer OFF button to end an automatic test at any time. 4. The front panel test status LED will light if the test is operating correctly. If the LED does not light check for problems such as open circuits or overload conditions. 5. Note the LCD reading. 6. Confirm that the voltage measurement is less than 10V AC; otherwise accurate Earth resistance measurements cannot be made. If voltage is present (higher than 10V AC), the source of the voltage must be found and corrected before testing can continue. 4

Earth Resistance Test 1. Set the meter's function switch to the ohms position and set the range switch to the desired resistance range. 2. Press the PUSH-ON button to perform a single, momentary test 3. Press the PUSH-ON and TIMER ON buttons simultaneously to begin a 3-minute test. 3-minute tests automatically shut down after 3 minutes. Press the Timer OFF button to end an automatic test at any time. 4. Note the displayed reading. The front panel test status LED will light if the test is operating correctly. If the LED does not light, check for problems such as open circuits or overload conditions. 5. If high resistance is detected, note the value and take appropriate steps to correct the ground connection if necessary. 6. Readings 1 Ω are typical when the test leads are not connected to the meter. Data Hold Data Hold freezes the latest measurement reading on the LCD. 1. Select ON from the Data Hold selector switch to turn Data Hold ON. 2. The reading that was on the display when the switch was set is now held on the LCD. 3. The Data Hold function does not retain measurement data if the meter is turned off. 4. Select OFF from the Data Hold selector switch to return meter to normal operation. 5

Maintenance Battery Replacement When the low battery icon 'B' appears on the LCD, the meter's batteries must be changed. 1. Remove power and disconnect the test leads from the meter. 2. Remove the rear battery compartment screw with a Phillips head screwdriver. 3. Remove the battery compartment cover and replace the six 1.5V 'AA' batteries. 4. Affix compartment cover and tighten screw. Cleaning and Storage Periodically wipe the meter's case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for a period longer than 60 days, remove the batteries and store them separately. Calibration and Repair Services Extech offers repair and calibration services for the products we sell. Extech also provides NIST certification for most products. Call the Customer Service Department for information on calibration services available for this product. Extech recommends that annual calibrations be performed to verify meter performance and accuracy. Support line (781) 890-7440 Technical support: Extension 200; E-mail: support@extech.com Repair & Returns: Extension 210; E-mail: repair@extech.com Product specifications subject to change without notice For the latest version of this User Guide, Software updates, and other up-to-the-minute product information, visit our website: www.extech.com Extech Instruments Corporation, 285 Bear Hill Road, Waltham, MA 02451 Copyright 2006 Extech Instruments Corporation All rights reserved including the right of reproduction in whole or in part in any form. 6