Slam-Shut Valve OSE LS. Europe, Middle East, and Africa Document Only CONTENTS INTRODUCTION CHARACTERISTICS. Scope of Manual.

Similar documents
SLAM-SHUT VALVE. Type OSE

Baumann Series Flexsleev Control Valve Instructions

Y690A Series Pressure Reducing Regulators

Built-in Slam-Shut Valve. Independent pneumatic control Accuracy class: ±5% Response time: 1 second. 1/2, 11/16, and 3/4-inch (13, 18, and 19 mm)

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Y690A Series Pressure Reducing Regulators

a s s e m b l y t o o l s a n d s y s t e m s Pneumatic Screwdrivers DS Series w w w. d o g a. f r

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

627 Series Pressure Reducing Regulators

STAINLESS STEEL ATEX 2/2 SOLENOID VALVE SPU225-X NF

STAINLESS STEEL PRESSURE REDUCING VALVE PRV ELITE

type 630r relief Valve

MOONRING 1.5 MOONRING 3

INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1

OBSOLETE DOCUMENT. PRX Series Pilots for Pilot-Operated Pressure Reducing Regulators. PRX Series. Introduction. Product Description

Fisher D2T FloPro Control Valve

Type 289P Pilot-Operated Relief Valve

Type 63EG-98HM Pilot-Operated Relief Valve or Backpressure Regulator

BLACKMER BYPASS VALVES

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

Type 310A-32A Pressure Reducing Regulator

INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit

FlowCon SH mm. Adjustable Dynamic Self Balancing Valve SPECIFICATIONS

NL-FTPR150, FUNCTIONAL TRAINER ASSEMBLY INSTRUCTIONS

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Type 99 Pressure reducing regulator

BULLETIN DE DIFFÉRENCIATION DES PRODUITS IPD Mai 2011

NAF-Triball ball valve

T205VB Series Tank Blanketing Vacuum Breakers

Series 100 Slam Shut Valve

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

FOURNISSEUR : CE MANUEL DOIT ÊTRE REMIS À L UTILISATEUR DE CE PRODUIT.

Fisher SS-263 Volume Booster

Type MR108 Direct-Operated Backpressure Regulator

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Safety Shut-Off Valve HON 711 S2

Valves. Rapid opening and closing solenoid valves VMR (E1110 rev /11/2012)

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Declaration of Conformity as per Directive 97/23/EC

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER SAMPLE / INJECTION PUMP

type 63Eg Relief Valve or Backpressure Regulator

Type 99 Pressure Reducing Regulator

INSTALLATION INSTRUCTIONS SUPERPLANE 2.5. Suspended. A nd Avenue, Unit 1 Oakland, CA P E W alwusa.

STAINLESS STEEL ATEX 2/2 SOLENOID VALVE SPU220-X NF

BUTTERFLY VALVE + ADA PNEUMATIC ACTUATOR

T205 Series Tank Blanketing Regulators

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Keystone Butterfly valves ParaSeal Installation and maintenance instructions

Type 644 and 645 Differential Pressure Pump Governors

Specification Grade Contemporary Wall Mount/Technical Installation Data

Type EZR Relief Valve or Backpressure Regulator

Type 2000, Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type MR105 Direct-Operated Pressure Reducing Regulators

167D Series Switching Valves

POOL BOY Powered Solar Blanket Reel

Type 63EG Relief Valve or Backpressure Regulator

627 Series Pressure Reducing Regulators

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

METERING VALVE 2" STEM GUIDED

289 Series Relief Valves

NAF-Torex butterfly valves DN , Size 3-28, PN 10-40, ANSI Class 150, 300

HIGH PRESSURE CONTROL VALVE R2L ACTUATOR

Type 92S Pilot-Operated Steam Regulators

BALL VALVE WITH ADA PNEUMATIC ACTUATOR

627 Series Pressure Reducing Regulators

PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER AUTOMATIC INSERTION PROBE

PN9000 Series Pneumatic Actuators Installation and Maintenance Instructions

Fisher 657 Diaphragm Actuator Sizes and 87

INSTALLATION INSTRUCTIONS LIGHTPLANE 3.5. LP3.5 Suspended LED. A nd Avenue, Unit 1. CA P E W alwusa.

BUTTERFLY VALVE WITH ADA PNEUMATIC ACTUATOR

INSTALLATION/OPERATION/MAINTENANCE MANUAL for the FlowMax REGULATOR

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300)

DP556 Pump. 55:1, Air-operated, Grease. General. Operation. Technical Data. Installation. Mounting with Reinforced Cover (Recommended)

Installation, Operation, and Maintenance Manual

type 122a three-way Switching Valve

Fisher 644 and 645 Differential Pressure Pump Governors

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual

INSTALLATION INSTRUCTION & TECHNICAL MANUAL FLOWMETER

ASSEMBLY TOOLS AND SYSTEMS. DPTC Cordless Impulse tools

EZH and EZHSO Series. Pressure Reducing Regulators. EZH and EZHSO Series. Introduction. Scope of the Manual. Product Description !

THE LF-690 SERIES. Operating and Service Manual. Series includes all variants of LF-690/691 and 692

Fisher CV500 Rotary Globe Control Valve

Type 1290 Vapor Recovery Regulator

Operating & Maintenance Manual For Steam Conditioning Valve

ASSEMBLY TOOLS AND SYSTEMS. DPTC Cordless Impulse tools

Butterfly valves Figure 56 Installation & Maintenance Instructions

Type EZR Relief Valve or Backpressure Regulator

Types 63EG and EGR

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER INJECTION PUMP

Fisher 656 Diaphragm Actuator

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

Installation Instructions

NAF-Triball ball valve DN for max. 40bar. Fk (9)GB 03.03

I & M Mark 708ME. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & Motor Actuator

J125. Service Regulator Inlet Pressure up to 8.6 bar

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL

Transcription:

Instruction Manual NTAOSELS0401 OSE LS February 2004 - Rev 03 Slam-Shut Valve CONTENTS Introduction... 1 Characteristics... 1 Labelling... 2 Dimensions and Weights... 3 Operation... 4 Installation... 4 Commissioning... 5 Maintenance... 6 Spare Parts... 8 INTRODUCTION Scope of Manual This manual provides installation, start-up, maintenance, and parts ordering information for the Type OSE LS Slam- Shut Valve. Information on other equipment used with this slam-shut valve is found in separate manuals. Product Description The OSE LS function is to protect transmission and distribution networks or pipe lines supplying industries and commercial businesses. It permits the gas flow to be cut off rapidly and totally in the case of under or over regulator pressure The OSE LS exists in DN 200 (8 ) and DN 250 (10 ) and completes the range covered by the OSE (DN 25 (1 ) to DN 150 (6 )). The OSE LS consists of: A body with a removable orifice, enclosed by a connecting part A valve plug tightshut by an O-ring An external manual bypass A release relay type OSD2 including: - A mechanism box (BM) - A safety manometric box (BMS) to be connected on the outlet side of the pressure regulator. Figure 1. Type OSE LS Slam-Shut Valve CHARACTERISTICS Material Body Connecting part Orifi ce Valve plug O-rings Connections Inlet/Outlet Impulse (IS) Mechanism box vent (E) Impulse diameter Safety contact Steel Steel Stainless steel Stainless steel Nitrile ISO PN 100 B (ANSI 600 RF) ISO PN 50 B (ANSI 300 RF) ISO PN 20 B (ANSI 150 RF) Other connections available (contact factory) ISO PN 16B, 25B, 40B 1/4 NPT threaded 1/4 NPT threaded Tube interior Ø 8/10 mm See NTAOS2 The OSE LS is in conformity with the Pressure Equipment Directive PED 97/23/EC and is classifi ed under category IV.

Table 1. Technical Characteristics of the Type OSE LS Slam-Shut Valve OPERATING PRESSURE Body, valve plug PS 100 bar max ssocied BMS (1) according to size PSD 10 to 100 bar Maximum Inlet Pressure Pumax 100 bar Type DS Differential strength (2) OPERATING TEMPERATURE (3) LABELLING TS - 20 / 60 C - 30 / 71 C SLAM-SHUT Sizes available DN 200, 250 Norm EN 14382 Operating class A or B (see label, fi gure 2) (1) BMS : Safety manometric box (2) Differential strength (depending on BMS chosen) (3) Temperature depending on bolting material (see label) DN 200 250 Bypass Cg 28830 42180 133 C1 34,6 35,5 32,8 ΔP max (bar) 8,2 4,6 Relay travel (mm) 70 82 OSE LS CLAPET DE SECURITE SLAM-SHUT VALVE BMS setting Max only Min only Accuracy AG 2,5-5 (Piston) Setpoint range Wdu-Wdo 0.010 to 100 bar Response time ta < 1 s Max Differential (valve closed) P max 100 bar Max Differential (valve open) P max See table 2 Rearming Table 2. Flow Coeffi cient, ΔP max, Relay travel All BMS types Security Class Manually after rectifi cation of fault Position indicator On mechanism box FLUID Group 1 and 2 according to PED 97/23/CE, 1st and 2nd family gas according to EN 437, or other gases (compressed air, nitrogen). The gas must be noncorrosive, clean (fi ltration on inlet side necessary) and dry Class 200 250 2 (bolting class 8-8) - (bolting A320L7) PN 40 B 25 B 16 B 20 J 20 B1 50 J 50 B1 100 J 100 B2 Other connections available (contact factory) D55 DD MM YEAR Temperature TS - 20 / + 60 C (bolting class 8-8) - 30 / + 71 C (bolting A320L7) DN Cg 200 28830 250 42180 PN Pumax PT PS D56 Figure 2. Label for Type OSE LS Slam-Shut Valve 2

DIMENSIONS AND WEIGHTS D 25 C MAX B A Figure 3. Type OSE LS Slam-Shut Valve Dimensions E F D59 Table 3. Type OSE LS Slam-Shut Valve Dimensions and Weights DN PN (B) ANSI (RF) DIMENSIONS A B C max D E F WEIGHT (kg) 20 150 543 171,5 294 200 50 300 568 190,5 579 446 336 321 100 600 610 209,5 356 220 20 150 673 203 469 250 50 300 708 222 667 498 363 504 100 600 752 254 577 Other PN16/25/40: contact factory D60 3

BMS BM 6 Safety contact : see NTAOS2. OPERATION The pressure of the zone to be protected (generally the pipe line on the outlet side of the pressure regulator and situated after the slam shut valve) activates the safety manometric box (BMS). If the pressure rises above the release set point the release relay frees the valve plug (key 6). Due to the weight of the valve plug, the closing spring and the fl uid (attempting to close), the valve plug will sit into the orifi ce (key 7). The gas flow is obstructed until the mechanism box is manually rearmed. To reopen the valve plug an equal pressure balance on inlet and outlet sides is required. Rearming is possible after bypassing is performed using the bypass valve (key 8). The bypass valve should be closed after pressure balance is obtained. INSTALLATION! WARNING 7 8 Figure 4. Type OSE LS - Principle of Operation The slam shut valve is installed on the inlet side of the regulator, on the horizontal pipeline. The mechanism box should be situated on top (see above schematic). Installation according to EN12186 is recommended. Install according to direction of the fluid flow (see arrow). When assembling with adjacent elements, care must be taken not to create pressure force on the body and the assembling elements (bolts, O-rings, flanges) should be compatible with the geometry and working conditions of the equipment. If the case arises a support must be used to avoid pressure force on the body (a support can be installed under the flanges). Connect the safety manometric box (IS) to the impulse at 4D on the outlet pipe. It is recommended to install an isolation valve (R1) and an atmospheric valve (R2), which can be useful for tripping and verifications. No modification should be made to the structure of the equipment (drilling, grinding, soldering...). D61 All interventions on the equipment should only be performed by qualified and trained personnel. Verify that the inlet side is protected by an appropriate device(s) to avoid exceeding the limits of utilization (PS, TS). 4

E IS R2 R1 4D Pu REGULATOR D Pd D62 Verify that the limits of utilization correspond to the appropriate operating conditions. Verify that the safety manometric box (BMS) and spring correspond to the appropriate operating conditions on the outlet side of the regulator. The equipment should not receive any type of shock, especially the release relay. The user should verify or carry out a protection adapted to the environment. Fire, seismic and lightening are not taken into consideration for standard regulators. If required, a special product selection and/ or specific calculations may be supplied according to specific requirements. COMMISSIONING! WARNING All interventions on the equipment should only be performed by qualified and trained personnel. Figure 5. Type OSE LS - Installation Impulse atmospheric valve Open Setpoint Verification Using the atmospheric valve, inject a pressure equal to the pressure foreseen for the regulator st 1 release relay stage Set (Stage 1) Slam shut valve Open (Stage 2) Progressively increase the pressure to reach tripping Adjust setting if necessary (NTAOS2) Note the set point value on the equipment or mark it in a commissioning document. D63 1 2 D64 Preliminary Verifications Start-up positions Inlet and outlet valves Verify absence of pressure between inlet and outlet valves Slam shut valve plug Slam shut bypass Impulse isolation valve STAGE 1 STAGE 2 Figure 6. Setpoint Verifi cation Positions before Commissioning Impulse isolation valve Open Impulse atmospheric valve Slam shut valve plug The equipment is ready for commissioning 5

Commissioning (max. only or max. and min.) Inlet valve Open slowly Slam shut bypass Open slowly Regulator Put into operation (see corresponding manual) st 1 release relay stage Set (Stage 1) Slam shut valve plug Open (Stage 2) Slam shut bypass Outlet valve Open slowly The equipment is commissioned After checking and commissioning the release relay it is recommended to seal it MAINTENANCE Service Check Recommended frequency: Twice yearly minimum Verification: Tripping and tripping value Slam shut valve plug tightness Departure positions Inlet valve Open Outlet valve Open Slam shut valve plug Open Regulator In operation Inlet and outlet sides of the regulator under pressure Tripping verification: Inlet valve Closed Outlet valve Closed Regulator Increase set point to reach tripping (without exceeding the outlet limits) Table 4. Recommended Tools Key Dimension Spanner Torque (N.m) 10 M8 13 mm 15 13 1 1/8-8x70 mm 1 11/6 400 19 M8 6 six-sided wrench 15 D65 Disassembly Recommended frequency: Every 4 to 6 years (or less depending on operating conditions) Verification: Condition of O-rings, diaphragm, lubrication Replacement: O-rings, diaphragm Tools: Spanners 10, 13, 6 six-sided wrench Spanner (see table 4) M8 and M10 screws + disassembly tool (approx. length 800) (valve plug disassembly) Valve plug closed Inlet and outlet valves closed Bleed off outlet pressure Bleed off inlet pressure Unscrew the impulse connection IS Remove the BM cover (key 1) Remove the travel stop (key 2) Unscrew the nuts (keys 3 and 4) Remove the resetting part (key 5) Remove the bolt (key 6) and the spacer (key 7) Remove the cam (key 8) and yoke (key 9) Unscrew the two screws (key 10) Remove the BM and fl at joint Retain the square nut (key 11) situated at the extremity of the valve angle (key 12) Unscrew the screws (key 13) Remove the O-ring (key 2) DN 200 only: insert a spacer D15 min. - 7.5 x 20 or stack washers of 8 and 6 beneath the square nut (key 11) Remove the connector assembly (key 14) / valve plug (keys 15 and 16) Disassembly of the valve plug (if required) Remove the square nut (key 11) Remove the packing gland (key 17) Extract the connector assembly (key 14) / valve cylinder Note Normally this part cannot be dismantled (screw CHc 27 fixed with loctite thread locking adhesive) Remove the spring (key 18) Remove the screws (key 19) and fi xing ring (key 20) (pin (key 21) remains mounted on (key 15)) Disassembly of the valve plug O-ring (if required) The valve plug body (key 15) is screwed in the valve plug cylinder (key 16), the O-ring (key 22) is reached by 6

unscrewing the above using a bar of 800 and four screws (two M8 on cylinder (key 16) and two M10 on valve plug body (key 15)) The removal of the orifi ce (key 28) (not recommended) requires a special extraction tool Reassembly The reassembly of a new orifi ce (key 28) requires a special tool Lubricate the mechanism of the release relay (BM face contact + keys 8, 7, 6, 5) (molybdenum graphite grease) Leave minimum operational space (rotation of the cam/ bolt) between the locked nut and the resetting part Lubricate the BMS spring (molybdenum graphite grease) Perform the above operations in reverse order (respect tightening torques) Replace O-rings at each disassembly Precaution should be taken when removing or replacing the valve plug to avoid damaging the segments (key 26) Lubricate screws before tightening (molybdenum graphite grease) Lightly lubricate O-rings (silicone grease) If the valve plug assembly (key 15/16) has been disassembled: Lightly lubricate the valve plug O-ring (key 22) (silicone grease) Lubricate the thread of the valve plug cylinder (key 16) (molybdenum graphite grease) Positioning the valve plug O-ring (key 22): DN 200: Screw the valve plug body (key 15) partly in the valve plug cylinder (key 16) and insert the O-ring (key 22) into the groove before tightening to reach metal/metal contact DN 250: Place the O-ring (key 22) into the groove of the valve plug cylinder (key 16), assemble and screw the valve plug body to reach metal/metal contact Wipe the valve plug O-ring (key 22) after assembly Lightly lubricate the valve plug shaft (key 12) (silicone grease) on the packing gland travel Check that the spring (key 18) is correctly positioned Positioning the O-ring (key 25) : DN 200 Mount on connector part DN 250 Place in the bore of the body Table 5. Troubleshooting for Type OSE LS Slam-Shut Valve 9 11 12 1 17 24 25 26 19 22 28 BM TRAVEL STOP POSITION DN 200 DN 250 Figure 7. Type OSE LS - Commissioning Schematic 8 6 7 3 5 2 10 13 14 27 16 18 20 15 21 4 D66 SYMPTOMS CAUSE ACTIONS If the valve will not close Operating fault Check the release relay Check the valve plug or contact after-sales If the valve closes If the outlet pressure in the slam shut is decreases If the outlet pressure in the slam shut is constant If the outlet pressure increases Operating correctly External leak Internal leak Observe the evolution of the outlet pressure (check tightness) Locate and seal the leak or contact after-sales Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure (check tightness) Check the slam shut valve plug Check the orifi ce Check the bypass or contact after-sales 7

SPARE PARTS BMS BM 5 4 Key Description DN 200 DN 250 1 Bypass valve 450 759 2 Valve plug O-ring 400 090 400 091 3 Segments 197 533 197 534 4 O-ring 1P5585X0022 400 093 Natural Gas Technologies Emerson Process Management Regulator Technologies, Inc. Francel SA Z.A. La Croix Saint Mathieu 28320 Gallardon, France Tél : +33 (0)2 37 33 47 00 Fax : +33 (0)2 37 31 46 56 3 2 1 Figure 8. Type OSE LS Spare Parts Table 6. Type OSE LS Spare Parts D57 Key Description DN 200 DN 250 5 O-ring 400 093 400 017 Packing gland «Kit» 198 426 Set of O-rings* 197 535 197 536 Release Relay Type OSD2 (*) Set of O-rings and segments including O-ring key nos 2, 3, 4, 5 See NTAOSD2 manual D58 Pour plus d information visiter : www.emersonprocess.com/regulators Le logo Emerson est une marque commerciale et une marque de service de Emerson Electric Co. Toutes les autres marques appartiennent à leurs propriétaires respectifs. Francel est une marque appartenant à Francel S.A., une succursale d Emerson Process Management. Les renseignements contenus dans cette publication sont présentés uniquement à titre informatif et, bien que tout ait été fait pour assurer leur exactitude, ils ne doivent pas être interprétés comme des garanties, expresses ou tacites, en ce qui concerne les produits ou services décrits ici ou leur usage ou applicabilité. Nous nous réservons le droit de modifi er ou d améliorer la conception ou les spécifi cations de ces produits à n importe quel moment, sans préavis. Francel décline toute responsabilité en ce qui concerne la sélection, l utilisation ou la maintenance d un produit. La responsabilité de la sélection, de l utilisation et de la maintenance de tout produit Francel incombe uniquement à l utilisateur. Francel S.A., 2008; Tous droits réservés