REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

Similar documents
Umatilla Electric Cooperative Net Metering Rules

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

Louisville Gas and Electric Company

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Noble County Rural Electric Membership Corporation

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES

Definitions. Scope. Customer Generation Interconnection Requirements

SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT

Net Metering Program

DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase

To complete the process for a net metering interconnection, please follow the steps below:

ENGINEERING SPECIFICATION

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)

White River Electric Association, Inc. Net Metering Information & Service Requirements

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board

TERMS AND CONDITIONS

Municipality Generator Interconnection Application Single Meter Application Part I

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

MISSOURI SERVICE AREA

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone Number:

INTERCONNECTION REQUIREMENTS POLICY

Distributed Generation Interconnection Policy

To complete the process for a net metering interconnection, please follow the steps below:

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS

Consumer Guidelines for Electric Power Generator Installation and Interconnection

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)

Net Metering Interconnection Requirements

MICHIGAN ELECTRIC UTILITY

Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION

Louisiana Net Metering Service. Customer Information Package

Code Compliance. Perspectives on PV. Back to the Grid, Designing PV Systems for

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Overview of State Distributed Generation Interconnection Rules

RENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS

Noble County Rural Electric Membership Corporation

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

University of Houston Master Construction Specifications Insert Project Name

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Customer Requirements Downtown Secondary Network Service

PSNH INTERCONNECTION REQUEST

Montana-Dakota Utilities Co. A Division of MDU Resources Group, Inc. 400 N 4 th Street Bismarck, ND 58501

Solar Power Installation Application

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power

REVISION NO.: 7 EFFECTIVE: 07/07/16

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

Adopted: September 24, 2015 Version: Version 1.0

WOLFEBORO MUNICIPAL ELECTRIC DEPARTMENT NET METERING PILOT PROGRAM. Customer-Owned Renewable Energy Generation Resources (25 Kilowatts or Less)

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

ACTION FORM. EXHIBIT #1 Regular Council Meeting of 11/27/2006

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL

SERVICE CLASSIFICATION "CEF" COMMUNITY ENERGY FACILITY

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less

Supply-Side PV Connections

Application for Interconnection and Net Metering Revision: 1 Revised: November 7, 2017

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

West Virginia Net Metering Service. Customer Information Package

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Rate Schedules. Effective 1/1/2019

Green Building Technology

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

ELECTRICAL DISTRICT # 2

MICHIGAN ELECTRIC UTILITY

Net +Plus Connection Code

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION

TERMS AND CONDITIONS XXV. NET METERING CUSTOMERS AND SMALL AGRICULTURAL GENERATORS

3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements.

GENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview

MICHIGAN ELECTRIC UTILITY

NET METER REQUEST FORM

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Application to Amend Net Metering Service under RS Appendix B. Revised RS 1289 Clean and Black-lined

REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS

MISSOURI SERVICE AREA

MICHIGAN ELECTRIC UTILITY

Oncor Application for Interconnection of Distributed Generation

S T A F F R E P O R T

Transcription:

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used as a guide for customers with small generators who wish to interconnect to PECO electric distribution system. For additional information about PECO services and future updates of this document please contact the PECO New Business office. A. CUSTOMER ELIGIBILITY Applicant must be a PECO customer with at least a 60 Amp, 120/240 Volt secondary service. This document only applies to locations where the total generation to be paralleled with the PECO system is limited to 50 kw. B. EQUIPMENT REQUIREMENTS Figures 1 through 4 show suggested arrangements of equipment, although they are not intended as design documents. Customers with Utility Interactive Inverter power system interfaces which meet current standards set forth in UL Publication 1741 and IEEE 1547 are eligible for an expedited review. The customer shall furnish, install and maintain the following equipment: 1. COMPATIBLE EQUIPMENT: Energy conversion facilities, generator and necessary interface equipment to match PECO service. 2. NEC CONFORMANCE The service shall be modified per the National Electrical Code (NEC), to accommodate an interconnected electric power production source ( See Articles 690, 692, and 705) 3. DISCONNECT SWITCH A readily accessible disconnect switch which is pad lockable and provides a visible break shall be installed between the AC output of the interconnected power source and its connection to the premise wiring system. For residential services, this switch shall be located outdoors, as close as practical to the utility meters. If this disconnect switch is not visible from the utility meters, a plaque shall be located at the utility meters indicating the presence and location of this disconnect switch. For commercial, industrial, or multi-tenant facilities larger than 5 units, this switch may be located indoors, by special permission, where conditions of maintenance and supervision ensure that the customer can provide qualified persons, available 24/7, to service and operate the system as required by PECO. Page 1 of 6 Rev date July 31, 2013

4. G OPTIONS: All services shall be metered for registered kwh and KW usage as dictated by the PAPUC tariff. The qualifications for Net Metering are listed in the PECO 'Rate RS-2 Net Metering' Tariff. PECO will provide the and meters for customers electing a Net Metering option. Customers must provide and install the required meter sockets or metering transformer enclosures to contain the PECO metering equipment. For the residential, two meter option, both sockets must be outdoors, with space for mounting a copy of the source directory required per NEC, Article 705.10, showing location of all electrical sources to the premises. The various metering options available are indicated in the table below G OPTIONS Option Description Meter Configuration A Net Metering 2 Meters 1 B Single Meter, Detented Notes Two meters - Customer billed monthly for net usage. 1-1 Meter only Generation output should not exceed premise load. Customer does not expect to export power or Net Meter. C D Sale of Energy to Third Party Virtural Net Metering Separate Service to System 2 Meters PECO Third Party Multiple meters Multiple meters PECO meter reads only. Customer is billed for all registered usage. Third party agreement through PJM to purchase energy. meter and communications to meet requirements of PJM. Combined registration of multiple usage and source meters within 2 mile radius under the same ownership and PECO account name. 5. ELECTRICAL TERFACE PROTECTION All interconnected power systems are required to monitor current, voltage and frequency and to disconnect the power source from the utility service, per IEEE 1547 protection levels and time delays, if the PECO supply is interrupted. Over/Under Voltage, and Over/Under Frequency protection shall meet the requirements of IEEE 1547. Manufacturer specifications for frequency and voltage protection schemes must be submitted to PECO for review. If this protection is not an integral part of a listed, manufactured power source interconnection system, PECO shall have the right to require testing of the protection device systems at the customer s expense. Minimum protection requirements are dependent on the type of generation source as listed below. Additional protection may be installed such as reverse power, reverse current, or out of step relaying, at the manufacturer s discretion. Note: Page 2 of 6 Rev date July 31, 2013

Utility Interactive Inverters meeting the requirements of UL Publication 1741, and IEEE 1547 satisfy these interface protection requirements. a. Overcurrent Protection - All Generation Types Circuit breakers or fuse elements sized in accordance with the NEC must be present in the circuit interconnecting the generation source to the premise electrical system. b Utility Interactive Inverters Utility Interactive Inverters shall meet UL publication 1741, which requires monitoring the service voltage and frequency to detect utility service interruption and shut down the inverter operation upon loss of utility supply. c Induction Generators A protective device meeting IEEE 1547 shall monitor the service voltage and frequency to detect utility service interruption, and disconnect the induction generator from the service. d. Synchronous Generators Synchronous generators produce power without the need of a utility source for excitation, and have the capability to supply loads independent of the utility electric supply. PECO shall review these installations for their expected contribution to fault currents. The installer shall calculate the fault contribution of the synchronous generator at the service voltage, and submit X d, X d, and X d impedance values for the generator being installed. A protective device meeting IEEE 1547 shall monitor the service voltage and frequency to detect utility service interruption and disconnect the generator from the electrical service. Frequency protection shall be set to trip the generator if less than 59.5 Hertz or greater than 60.5 Hertz. In addition, these sources must be interconnected to supply the phase to neutral loads on the service. e. Self Commutating Inverters Self commutating inverters produce power without the need of a utility source for commutation, and have the capability to supply loads independent of the utility electric supply. PECO shall review these installations for their expected contribution to fault currents. The installer shall calculate the steady state fault current contributions of a self commutating inverter to a single phase fault on the service, and or a three phase fault where appropriate.. A protective device meeting IEEE 1547 shall monitor the service voltage and frequency to detect utility service interruption and shut down the inverter. Frequency protection shall be set to shut down the inverter if less than 59.5 Hertz or greater than 60.5 Hertz. In addition, these sources must be interconnected to supply the phase to neutral loads on the service Page 3 of 6 Rev date July 31, 2013

C. Requirements for Connection 1. The applicant shall submit the following to the appropriate PECO regional New Business office: a. A Level 1, 2, 3, or 4 TERCONNECTION APPLICATION / AGREEMENT application form b. A PECO Service and Meter Application c. Appropriate application fee.forms and fees are available on the PECO web site, www.peco.com, search TERCONNECTION APPLICATION LEVEL GUIDE LE Level Size of Interconnected Power Source 1 10 kw or Less 2 >10 kw <= 50 kw 3 <= 50 kw 4 <= 50 kw Applicability Power interface is inverter based. Power interface with utility is pre-certified by a Listed testing agency to meet UL-1741 and IEEE 1547. Exported power will be Net-Metered with PECO and service meters, if the customer requests and meets the qualifications in the 'Rate RS-2 Net Metering' Tariff. Power interface is inverter based. Power interface with utility is pre-certified by a Listed testing agency to meet UL-1741 and IEEE 1547. Exported power will be Net-Metered with PECO and service meters, if the customer requests and meets the qualifications in the 'Rate RS-2 Net Metering' Tariff. Systems submitted as Level 1, 2, or 4 which were not approved Systems which do not meet Level 1 or 2 criteria Installation may require PECO system modifications to interconnect. Non-Inverter based interface Interface protection is not certified by a Listed testing agency to meet UL-1741 and IEEE 1547 Exported power will be Net-Metered with PECO and service meters, if the customer requests and meets the qualifications in the 'Rate RS-2 Net Metering' Tariff. Systems submitted as Level 1 or 2 which were not approved Export of power is not expected Reverse power relays or other protection functions that prevent power flow onto the utility grid. PECO service meter to be detented to register only Page 4 of 6 Rev date July 31, 2013

2. A diagram, similar to Figures 1 thru 4, shall be submitted by the contractor indicating: Where the electrical interconnection will be made with the premise wiring List equipment ratings, conductor sizes, and fuse and breaker ratings Note: Transformer rated metering installations will require special review for modification to the meter board. This type of installation is not included in the Figures. 3. Submit all available manufacturers information concerning the system s electrical components. Note: not required for systems meeting IEEE Standard 1547, and UL Publication 1741. 4. The installation must meet all local municipality building codes, the National Electrical Code, and the National Electrical Safety Code, and shall be inspected by an electrical underwriter listed in PECO s Electric Service Requirements handbook. 5. PECO will review the application per PAPUC PA Code Chapter 75 criteria. If the proposed installation is approved for connection to the PECO system, the results will be forwarded to the submitter with instructions to modify PECO s metering installation. If PECO distribution facilities must be modified to meet the Chapter 75 criteria, the submitter shall be notified per section D. Rearrangement Of PECO Distribution Facilities, below. 6. Upon the completion of the interconnected power system s installation and any required PECO system and or metering upgrades, the applicant shall sign and submit PECO s Certification of Completion form and an electrical underwriter s inspection of the interconnected power system wiring, The Certification of Completion. is available on the PECO Net Metering and Interconnection webpage. PECO reserves the right to require a witness test of the system s protection scheme. Testing will be required for systems meeting the following criteria: a. Any system which is not pre- certified by an independent testing laboratory (UL 1741). b. Systems with field adjustable relays will require calibration by an independent testing service. A trip test shall be witnessed by a PECO representative. In addition, a test report of the relay calibrations shall be submitted to PECO for review. Note: PECO net- meter billing will not become active until the witness test has been waived, or satisfied, the Certificate of Completion has been completed and signed by the applicant, and an electrical under writer inspection has been submitted. Page 5 of 6 Rev date July 31, 2013

D. Rearrangement Of PECO Distribution Facilities Where the review of a Level 1, 2, or 4 application determines that PECO facilities must be modified to accommodate the connection of the applicant s system, the application will be returned to the applicant to be re-submitted as a Level 3 with appropriate Level 3 application fee. An explanation of the reason for the return will be indicated. The new Level 3 application will keep the queue position of the original application. A Level 3 review response may require the applicant to pay for an Interconnection Feasibility Study and or an Interconnection Impact Study, to determine the modifications to PECO s system required to accommodate the interconnection of the proposed power system. When the extent of PECO s system modifications have been determined, PECO will prepare an Interconnection Facilities Study to communicate the nature of the PECO system modifications, costs for engineering, procurement, construction, and overheads, as well as an estimated time to complete the construction associated with the modifications. The applicant must agree to pay for the modifications, in advance, before work begins. Page 6 of 6 Rev date July 31, 2013

PECO RESIDENTIAL 120/240 VOLTS 1 PHASE 3 WIRE FORM 2S FIGURE 1 RESIDENTIAL NON-UTILITY GENERATION TYPICAL & EQUIPMENT ARRANGEMENT PHOTOVOLTAIC / UTILITY TERACTIVE VERTER All equipment shown, except for watt-hour meters (), are owned, operated and maintained by the customer. Both breakers and switch/fuse equipment may be interchanged. Symbols were selected for convenience only. Separate*, self-contained meter sockets of the same size shall be installed outdoors, with space provision for NEC Source directory. Meters register flow in direction shown. Meters are detented to prevent reverse registration. PANEL,_:POWER POWE\ I) I) I) f) ~ HOUSE LOADS SEE DETAIL ~) r I * MULTIPLE SOCKET BOARDS WITH COMMON BUS ARE NOT PERMITTED. WIRE SIZE Interconnection may be made on the supply side of the main service disconnect per Figure 2. Interconnection on the load side of the service disconnect requires special NEC considerations. DOOR 100 AMP, 2 POLE VOLTAGE & FREQUENCY PROTECTION COMG TO DISCONNECTS VERTER TRIP SOLID-STATE UTILITY TERACTIVE VERTER KW VOLTS AMPS MAKE DETAIL MODEL

FIGURE 2 RESIDENTIAL NON-UTILITY GENERATION TYPICAL & EQUIPMENT ARRANGEMENT SYNCHRONOUS OR DUCTION GENERATOR AND PHOTOVOLTAIC / UTILITY TERACTIVE VERTER All equipment shown, except for watt-hour meters (), are owned, operated and maintained by the customer. Both breakers and switch/ fuse equipment may be interchanged. Symbols were selected for convenience only. PECO RESIDENTIAL 120/240 VOLTS Separate*, self-contained meter sockets of the same size shall be 1 PHASE 3 WIRE installed outdoors, with space provision for NEC Source directory. FORM 2S Meters register flow in direction shown. Meters are detented to prevent reverse registration. Interconnection on the load side of the service disconnect requires special NEC considerations.,_:power POWE\ SEE DETAIL * MULTIPLE SOCKET BOARDS WITH COMMON BUS ARE NOT PERMITTED. PANEL I) I) I) ~ ~ HOUSE LOADS WIRE SIZE DOOR 100 AMP, 2 POLE VOLTAGE & FREQUENCY PROTECTION COMG TO DISCONNECTS -,:... MAGNETICALLY HELD CONTACTOR GENERATOR TRIP NEMA SIZE O.L. SET [ ] SYNC [ ] DUCTION DETAIL ROTATG GENERATOR KW VOLTS AMPS RPM

FIGURE 3 THREE-PHASE GENERAL SOCKET NON-UTILITY GENERATION TYPICAL & EQUIPMENT ARRANGEMENT PHOTOVOLTAIC / UTILITY TERACTIVE VERTER PECO THREE-PHASE GENERAL 3 PHASE 4 WIRE FORM 15 / 16S All equipment shown, except for watt-hour meters (), are owned, operated and maintained by the customer. Both breakers and switch/fuse equipment may be interchanged. Symbols were selected for convenience only. Separate*, self-contained meter sockets of the same size shall be installed outdoors, with space provision for NEC Source directory. Meters register flow in direction shown. Meters are detented to prevent reverse registration. PANEL,_:POWER POWE\ I) I) I) f) ~ HOUSE LOADS SEE DETAIL ~) r I * MULTIPLE SOCKET BOARDS WITH COMMON BUS ARE NOT PERMITTED. WIRE SIZE Interconnection may be made on the supply side of the main service disconnect per Figure 4. Interconnection on the load side of the service disconnect requires special NEC considerations. DOOR Pole VOLTAGE & FREQUENCY PROTECTION Amps COMG TO DISCONNECTS VERTER TRIP SOLID-STATE UTILITY TERACTIVE VERTER KW VOLTS AMPS MAKE DETAIL MODEL

FIGURE 4 THREE-PHASE GENERAL SOCKET NON-UTILITY GENERATION TYPICAL & EQUIPMENT ARRANGEMENT SYNCHRONOUS OR DUCTION GENERATOR AND PHOTOVOLTAIC / UTILITY TERACTIVE VERTER All equipment shown, except for watt-hour meters (), are owned, operated and maintained by the customer. Both breakers and switch/ fuse equipment may be interchanged. Symbols were selected for convenience only. PECO THREE-PHASE GENERAL Separate*, self-contained meter sockets of the same size shall be 3 PHASE 4 WIRE installed outdoors, with space provision for NEC Source directory. FORM 15 / 16S Meters register flow in direction shown. Meters are detented to prevent reverse registration. Interconnection on the load side of the service disconnect requires special NEC considerations. 4'.POWER POWE\ SEE DETAIL * MULTIPLE SOCKET BOARDS WITH COMMON BUS ARE NOT PERMITTED. PANEL I) I) I) ~...,, HOUSE LOADS WIRE SIZE DOOR 1 - Pole VOLTAGE & FREQUENCY PROTECTION Amps COMG TO DISCONNECTS -,::... MAGNETICALLY HELD CONTACTOR GENERATOR TRIP NEMA SIZE O.L. SET [ ] SYNC [ ] DUCTION DETAIL ROTATG GENERATOR KW VOLTS AMPS RPM