System 350 S350C Temperature Slave Stage Module

Similar documents
M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350E Electronic Cooling Control

M9109 Series Electric Non-spring Return Actuators

System 350 S350P Proportional Plus Integral Temperature Stage Module

M9106-xGx-2 Series Electric Non-Spring Return Actuators

M9106-AGx-2N0x Series Electric Non-Spring Return Actuators

VA-4233-AGx Series Electric Valve Actuators

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

CSD Series Current Devices Split Core

M9102-AGA-3S and M9104-xGA-3S Series Electric Non-Spring Return Actuators

System 350 P352AB Electronic Pressure Control Series

M9300 Series Switch Kits

TM-11x1 Series Room Temperature Module

M9300 Series Potentiometer Kits

M9104-AGP-2S Series Electric Non-Spring Return Actuator with Pressure Sensor for VAV Applications Part No , Rev. B

VA-715x Electric Valve Actuator

VA-4233-GGx Series Electric Valve Actuators

M9102-AGA-2S and M9104-xGA-2S Series Electric Non-Spring Return Actuators

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

VA-720x Electric Valve Actuator

M Remote Mounting Kit

VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators

M9300 Series Electric Non-Spring Return Actuators

VA9905 Actuator and VG1600 Series Six-Way Valves

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators

M Remote Mounting Kit

P545 Series Electronic Lube Oil Control

M9203-Bxx-2(Z) Series On/Off Electric Spring Return Actuators

M x Series Valve Linkage Kits

M9220-Bxx-3 On/Off Electric Spring Return Actuators

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419ABG-3C Electronic Temperature Control

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

M9220-AGx-3 Floating Electric Spring Return Actuators

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

P78 Series Controls for Dual Pressure and Hazardous Location Applications

P78 Series Controls for Dual Pressure Applications

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

VA-715x Electric Valve Actuator

A25 Series Warm Air Control with Manual Reset

P445 Series Electronic Lube Oil Control

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9216 Series Electric Spring Return Actuators

P70, P72, and P170 Controls for Low Pressure Applications

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

VA-8020 Floating Valve Actuator

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

AV-8020 Series Floating Control Actuated Valve

VA-7450 Series. Electric Valve Actuators

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

VA-4233-GGx Series Electric Valve Actuators

Applications. A421 Series Standard Electronic Temperature Controls Installation Guide

M9220-HGx-3 Proportional Electric Spring Return Actuators

Fan Relay Board (FRBii) Assembly

Two Flashes. N/A for AboveAir Units / Witt Condenser use 75 psig (set with switches 64, 8, 2, & 1 set to ON )

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

P70, P72, and P170 Series Controls for High Pressure Applications

V-2410 Three-Way Multipurpose Solenoid Air Valve

VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators

F61 Series Standard Flow Switches

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

Damper Actuator Installation

P66 Series Electronic Fan Speed Controls

P70, P72 and P170 Series Controls for High Pressure Applications

P1000 Series Pressure Independent Valves

TE-6001 Hardware Assemblies for TE-6000 Temperature Elements

YCCS TE-6800 Series Temperature Sensors

M100F Incremental Motor Actuator R81F Interface Board

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators

TM-9100 Series Room Command Module

M9208-xxx-x Series Electric Spring Return Actuators

F261 Series Fluid Flow Switches

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

Series Y63, Y64, Y65, Y66, and Y69 Transformers

M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications

SEN and SEN Outdoor Air Temperature Sensors

M9220-xxx-3 Electric Spring Return Actuators

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

R81EAA-2 Economizer Circuit Board

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

INSTALLATION DATA ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

M9210-xxx-3 Electric Spring Return Actuators

VSD Series II Variable Speed Micro Drives

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

MS Application. Features. Proportional Valve Actuator General Instructions

INSTALLATION DATA ETC SINGLE Stage

G72x Series Direct Spark Ignition Controls

Transcription:

FANs 930, 930.5, 125, 121 Product/Technical Bulletin Issue Date April 8, 2014 System 350 Temperature Slave Stage Module The Temperature Slave Stage Module is used in conjunction with the A350 Temperature Control to add multiple stage capability with independently adjustable setpoints. The is an electronic control with a Single-Pole, Double-Throw (SPDT) relay output. As are all System 350 products, the is housed in a NEMA 1, high-impact plastic enclosure. The modular design provides easy, plug-together connections for quick installation and future expandability. Figure 1: Temperature Slave Stage Module Modular Design Features and Benefits Enables stage, display, and transformer modules to be purchased and installed as needed Plug-together Connectors and 35 mm DIN Rail Mountability Adjustable Setpoint ( F or C) Independent of A350 Temperature Control Shares Sensor Input with A350 Temperature Control Wide, Adjustable Differential Field-selectable Mode of Operation Light-Emitting Diode (LED) Indication of Relay Status Eliminates wiring between modules, which reduces installation costs Stages equipment with different setpoint requirements using one dual scale setpoint ( F or C) Eliminates the need for a separate sensor Enables the user to match equipment cycle rate and/or sequencing for a given application Suitable for cooling or heating applications Aids in adjustment and troubleshooting 2014 Johnson Controls, Inc. 1 Part No. 24-7664-1199, Rev. B www.johnsoncontrols.com Code No. LIT-930084

A pplication The Slave Stage Module receives power and sensor inputs from the A350 Temperature Control to which it is connected. The features an adjustable setpoint, independent of the A350 Control s setpoint. The output of the is a Single-Pole, Double-Throw (SPDT) relay. The maximum number of stages that can be used in a system varies with the type of control module (on-off, proportional, or reset), type of stage module (on-off, slave, or proportional), and type of power supply (external transformer or Y350R). Use the following table to determine the maximum number of stages that may be used with each control module. Table 1: Maximum S350 Stage Modules per Control Module Control (Power Supply) A350A, A350B, A350E, A350R, A350S (using Y350R) A350P (using Y350R) Any A350 (using an external transformer) Note: Maximum S350A or Stage Modules Maximum S350A or (with 1 S350P) Maximum S350A or (with 2 S350Ps) 9 6 4 4 2 0 9 8 7 For each S350P added, the number of S350A or Stage Modules that can be used with a Y350R decreases by two. If an external transformer is used, the number of S350A and Stage Modules that can be used decreases by one for each additional S350P. O peration IMPORTANT: Use this Temperature Slave Stage Module only as an operating control. Where failure or malfunction of the module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the module. IMPORTANT: Utiliser ce Temperature Slave Stage Module uniquement en tant que dispositif de contrôle de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du module risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du module. The is powered by the A350 and provides an SPDT relay output. A front panel LED lights to indicate that the relay is energized. Features include: adjustable setpoint adjustable differential selectable cooling or heating mode of operation 2 System 350 Temperature Slave Stage Module Product/Technical Bulletin

Differential Potentiometer Relay Energized LED Indicator Setpoint Setpoint Potentiometer NC COM NO Module Connector Jumper Block Position Cooling Figure 2: Interior View of Module The Module features an adjustable setpoint, with both Fahrenheit and Celsius scales, which is independent of the A350 s setpoint. The Module s setpoint is defined as the temperature at which the Module s relay will de-energize. With the mode jumper in either the cooling or heating mode of operation, the relay will de-energize when the sensor temperature reaches setpoint. The setpoint can be adjusted between -30 and 130 F (-34 to 54 C). Adjustment is made using the setpoint potentiometer shown in Figure 2. Differential Differential is defined as the change in sensor temperature between energization and deenergization of the relay. The differential can be adjusted between 1 and 30F (0.5 to 17C ). Adjustment is made using the differential potentiometer shown in Figure 2. Included with the is a Celsius Differential scale decal. If the Celsius scale is desired, follow the Celsius scale conversion procedure in the Installation and Wiring section. Cooling or Operation The features field-selectable operation, allowing its use in either cooling or heating applications. Select the mode by positioning the operation jumpers vertically for heating or horizontally for cooling, as shown in Figure 2. As shipped from the factory, the jumpers are installed in the vertical position. When set for cooling, the differential is above the s setpoint. The relay is de-energized and the LED indicator is off when the sensor temperature drops to the setpoint setting. As the temperature rises to the setpoint plus the differential, the relay energizes and the LED illuminates. See Figure 3. When heating is selected, the differential is below the s setpoint. The relay is de-energized and the LED indicator is off when the sensor temperature rises to setpoint. As the temperature drops to setpoint minus the differential, the relay energizes and the LED illuminates. Increase Setpoint Temperature Decrease Energize Cooling Differential Differential Energize Figure 3: Relay Operation Relative to Setpoint and Mode of Operation System 350 Temperature Slave Stage Module Product/Technical Bulletin 3

D imensions Mounting Slots for No. 6 Screws 3/16 (4) 1/2 (13) 2 15/16 (75) 5 (127) ON 1 9/16 (40) 7/16 (11) DIN Rail Mount 2 3/8 (61) 1 3/16 (31) 9 3/4 (248) Sensor 2 (50) 1/4 (6) 2 3/8 (61) 7/8 (22) 7/8 (22) Conduit Hole Installation and Wiring Figure 4: Dimensions, in (mm) Celsius Scale Conversion Included with the is a Celsius scale decal for the differential potentiometer. If the Celsius scale is desired: 1. Use a small screwdriver to pry underneath the existing decal, and remove it along with the differential potentiometer knob. 2. Apply the Celsius scale decal in the same place as the original decal. (Number 9 should be at the top.) 3. Rotate the knob stem completely counterclockwise. 4. Reinstall the potentiometer knob so the arrow points to the minimum scale temperature. Mounting the The Slave Stage Module is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting. The is not position sensitive but should be mounted for convenient wiring and adjustment. Use the four key-slot mounting holes on the back of the control case for surface mounting. Note: Wiring When mounting the (or any System 350 module) to rigid conduit, attach the hub to the conduit before securing the hub to the control enclosure.! CAUTION: Risk of Electrical Shock. Disconnect the power supply before making electrical connections to avoid electric shock. MISE EN GARDE: Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.! CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. 4 System 350 Temperature Slave Stage Module Product/Technical Bulletin

MISE EN GARDE: Risque de dégâts matériels. Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement. Install all wiring to conform to the National Electrical Code and local regulations. For maximum electrical rating, refer to the label inside the control cover. Use only copper conductors. Consult Figures 5 and 6 for proper wiring and terminal designations. A djustments Follow this procedure to set up the for the types of operation desired. 1. Remove the s cover by loosening the four captive cover screws. 2. Set the cooling/heating jumpers to the desired position: horizontally for cooling or vertically for heating. See Figure 2. 3. Adjust the differential potentiometer (DIFF) to the desired setting. 4. Adjust the setpoint potentiometer to the desired setting. Clockwise rotation increases setpoint. 5. Reinstall the cover and secure in place with the four captive cover screws. Shield (Connect to COM on A350.) Isolate and tape. Sensor A350A Y350R D350 120 VAC Load Load Figure 5: Typical Wiring Diagram for an, Y350R, and A350 Temperature Control System 350 Temperature Slave Stage Module Product/Technical Bulletin 5

Supply Sensor D350 A350R S350A S350A Master (O.A.) Sensor D350 120 VAC Pump 24 VAC Limit Limit Limit Stage 3 Stage 2 Stage 1 Figure 6: Typical Wiring Diagram for an, Y350R Power Module, and A350R Temperature Reset Control for Pump Control Checkout Procedure Before applying power, make sure that the installation and wiring connections comply with job specifications. After necessary adjustments and electrical connections have been made, put the system in operation and observe at least three complete operating cycles before leaving the installation. T roubleshooting If the control system does not function properly, verify that the proper operation is selected on each module (for example, heating or cooling) and perform the following procedures to determine the cause of the problem: 1. Check for proper voltage applied to the A350 Control. a. Connect a digital voltmeter (DVM) between the 24V (+) and COM (-) terminals located on the A350 s terminal block. If an external transformer is used, select AC volts on the DVM and verify that the voltage is between 20 and 30 VAC. If a Y350R Power Module is used, select DC volts on the DVM and verify that the voltage is between 16 and 38 VDC. b. If the DVM reading is within the indicated voltage range, proceed to Step 2. c. If the DVM reading is not within the indicated voltage range, you may need to correct the wiring, replace the Y350R, or replace the external transformer. 2. Check sensor for proper resistance at a given temperature. (The resistance across the sensor changes with the temperature of the sensor.) a. Disconnect power from the A350 control. b. Disconnect the sensor from the control and measure the resistance across sensor leads. c. When measuring the sensor s resistance, use an accurate thermometer to measure the temperature at the sensor. d. Refer to Figure 7 to determine the optimal resistance for the measured temperature. e. If the measured resistance varies substantially from the optimal resistance for that temperature, the sensor or wiring must be replaced. f. If the sensor s resistance conforms to the chart in Figure 7, reconnect the sensor to the control. g. Reconnect power to the control. 6 System 350 Temperature Slave Stage Module Product/Technical Bulletin

F Temperature C 260 240 220 200 180 160 120 100 80 140 60 120 100 40 80 60 20 40 0 20 0-20 -20-40 -40 500 700 900 1100 1300 1500 1700 1900 2100 Resistance (Ohms) Figure 7: Temperature vs. Resistance Chart for the A99B Series Sensor Repairs and Replacement Do not make field repairs or perform calibration. Temperature sensors and replacement controls are available through local Johnson Controls representatives. Ordering Information Table 3: Ordering Information Product Code Description Number C-1C Temperature Slave Stage Module Note: The sensor reading indicated by the D350 may differ from thermometer readings due to sensor tolerances, time constants, thermometer accuracy, and other factors. 3. Check the for proper operation. a. Remove the cover from the and adjust its setpoint potentiometer to below the sensor temperature (T S ) determined in Step 2. b. Increase the s setpoint by slowly adjusting the setpoint potentiometer until the control relay and LED turn On and Off. c. If the relay does not perform as indicated in Table 2, adjust the differential potentiometer to minimum and try again. d. If the relay still does not turn On and Off, replace the defective. Note: Though unlikely, it is possible that a defect in one stage module could cause defective symptoms in all modules. To verify, plug each stage into the control individually and check its performance as outlined in Steps 3a and 3b. Table 2: Relay Troubleshooting Action LED NO Relay Status Setpoint Dial Setting ON Closed (T S )* = Sp - Diff OFF Open (T S ) = Sp Cooling ON Closed (T S ) = Sp + Diff Cooling OFF Open (T S ) = Sp * (Ts) is sensed temperature. System 350 Temperature Slave Stage Module Product/Technical Bulletin 7

Specifications Product Supply Voltage Temperature Slave Stage Module 5 VDC reference and 24 V power supply provided by the A350 Ambient Temperatures Operating: -30 to 150 F (-34 to 66 C) Shipping: -40 to 185 F (-40 to 85 C) Humidity Setpoint Adjustment Range 0 to 95% RH non-condensing; maximum dew point: 85 F (29 C) -30 to 130 F (-35 to 55 C) Differential Adjustment Range 1 to 30F (0.5 to 17C ) SPDT Relay Output 120V 208 to 240V Horsepower: 1/2 1/2 Full Load: 9.8A 4.9A Locked Rotor: 58.8A 29.4A Non-Inductive: 10A at 24 to 240 VAC Pilot Duty: 125 VA at 24 to 240 VAC Output Indication LED Mode of Operation Material Agency Listing Cooling or heating mode is jumper selectable. Case, Cover: NEMA 1 high-impact thermoplastic UL Listed, CCN XAPX, File E27734 UL Listed for Canada, CCN XAPX7, File E27734 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. Copyright 2014 by Johnson Controls, Inc. All rights reserved. 8 System 350 Temperature Slave Stage Module Product/Technical Bulletin