Technical News. Ensuring low voltage air circuit breakers are fit for service. Issue #61 - October 2011

Similar documents
Technical News. Drives: benefits, operation, pitfalls and harmonic solutions. Issue #59 - January 2011

Air Circuit Breaker Retrofitting

DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS.

Consumer Switchboards and Circuit Protection Flexible range designed for domestic and commercial installations

Fuses still the best form of overload protection

Sinus Penta Variable Speed Drive

MOD6 RCBOs. New and retrofit solutions providing reliable personnel protection POWER DISTRIBUTION AND PROTECTION 1300 NHP NHP 0800 NHP NHP

Technical News. High Efficiency Motors & Type 2 Coordination Motor Starting. Industrial Electrical and Automation Products, Systems and Solutions

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

Grounding Of Standby & Emergency Power Systems

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Guidelines for connection of generators:

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

AS/NZS :2016. Grid connection of energy systems via inverters AS/NZS :2016. Part 1: Installation requirements

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

SENTINEL BATTERY MONITORING

Terasaki (Europe) Ltd

Guideline for Parallel Grid Exit Point Connection 28/10/2010

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

Food power. ABB s rugged UPS PowerLine DPA ensures food and beverage production facilities keep running

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

APPLICATION GUIDE. ACH580 Managing total cost of ownership of HVAC systems

Ultra Fast Earthing Switch UFES retrofit Overview

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits

Don t Discriminate: The importance of selective coordination in electrical installations

TemPower 2 Air Circuit Breaker

Air Circuit Breakers

THORNE & DERRICK UK TEL FAX TEL FAX

OUTDOOR UNIT CONTROLLER (OUC)

Integrated Inverter/Battery Monitoring System (IBMS)

Selective Coordination

FUSE: SAFE & RELIABLE

Transformer Protection

9120 EBCU Battery Charger MODELS: 9120EBCU96V 9120EBCU240V

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Electric Vehicle Supply Equipment EVSE Vehicle Simulator

ELECTRICAL EQUIPMENT & CONTROL SYSTEMS: COMMISSIONING, TESTING & START-UP OF ELECTRICAL SYSTEMS

Air Circuit Breakers

Brochure. Arc Guard System TVOC-2 A protection device for reliable safety

Improves fan ef ciency

LA Motor Protection. A South African Company to be Proud of

Applications of Electrical Machines

Number 1 in efficiency

Session Four Applying functional safety to machine interlock guards

EST Electrical Service Technician Answer Schedule

Cascading & Discrimination

NHP MODdrive TM for Building Services

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

SURE TRIP RETRO KITS

Fuseology. Dual-Element, Time-Delay Fuse Operation

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Capabilities Brochure

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

Arc-Flash Mitigation Technologies. Dennis Balickie

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Unified requirements for systems with voltages above 1 kv up to 15 kv

Variable Frequency Drive Basics

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

Key elements of the AS3000 Wiring standards and some of the recent changes.

Ensuring the Safety Of Medical Electronics

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

EE042: Practical Power System Protection for Engineers & Technicians

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

4-Day Power System Analysis, Coordination, System Studies

ype UP T Busplugs Low Voltage Switchboard Equipment

RIIMPO338D - Conduct Rigid Haul Truck Operations. The Complete Mine-Ready Training Package

Green Star - Office Interiors v1.1 Inn-3 Environmental Design Initiatives

ABB Services for Low Voltage equipment Your choice, your future

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

KD LV Motor Protection Relay

N Daily Weekly Monthly Every 3 months. Every 6 months 1 Remove any materials not related

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Not all Low Voltage Switchgear is created equal

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

TIME REQUIREMENT GUIDE (TRG)

INSPECTIONS TESTING TRAINING & REPAIRS

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers

Life cycle services for protection and control relays Full support from start to finish

Technical News. Power Factor Correction. What technology is best for you? Specialists in electrical and automation products, systems and solutions

REDUCE ARC-FLASH EXPOSURE and INCREASE RELIABILITY

CENTURY YUASA - STANDBY OVERVIEW

Design considerations for generator set mounted paralleling breakers

Installation and Construction Notes for EVSE4

UniSec Maintenance solutions

Connecting your home or small business generation

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

Case Study. Modernising gas fired power plant boiler damper drives and damper bearings

Motor Protection With The MonitorPro

University of Houston Master Construction Specifications Insert Project Name

FUNCTIONAL SAFETY SOLUTIONS in Solenoid Valves

SIEMENS 3WL Air Circuit Breakers

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Transcription:

Issue #61 - October 2011 Technical News INDUSTRIAL ELECTRICAL AND AUTOMATION PRODUCTS, SYSTEMS AND SOLUTIONS Ensuring low voltage air circuit breakers are fit for service Written by Nicholas Burley Business Manager - Power Distribution please circulate to: nhp.com.au nhp-nz.com

Air circuit breakers are common place in low voltage (LV) switchboards. Due to their typically passive operation they are a piece of equipment that is often forgotten about until there is a trip or circuit breaker failure leading to a power supply disruption. Importantly, many low voltage switchboards in service today are being protected by air circuit breakers that have been in operation for twenty, thirty or even forty years. To ensure on-going power supply integrity and to improve safety for those working within the vicinity of low voltage switch gear such as air circuit breakers six criteria, should be considered; 1) Appropriate circuit breaker commissioning and documentation; 2) Periodic review of protection settings; 3) On-going end user practical training; 4) Through life service requirement; 5) Retrofit options for air circuit breakers; 6) Utilisation of new technology to improve switchboard safety. INTRODUCTION Air circuit breakers (ACBs) are a special type of switchgear that are typically used as a main switch, outgoing feeder and bus-tie switch within switchboards (refer figure 1.0). Continuous current ratings for ACBs range from 800A up to 6300A and they can typically weigh between 50 to 180kgs. Robustness and mechanical strength are key attributes of a high performance ACB as they are designed to withstand the extreme thermal stress and mechanical forces generated under a short circuit condition. Switchboards and the installed switchgear must be capable of functioning under varying operational and environmental conditions and withstanding damage associated with electrical faults. An ACB is a key component of any large scale low voltage (LV)network and while they normally lead a dormant life their ability to clear a range of electrical faults at any given moment is of high importance. It is common to find legacy LV switchboards containing operating switchgear that has reached the end of its service life and in many cases it is working beyond it! Apart from the increased risk of failure to clear short circuit currents, aging ACBs commonly exhibit functional defects such as: Inability to manually open or close Cluster and main contacts overheating Burning out of accessories such as shunt open coils and charging motors Degradation of insulation on live and earthed components. The consequence of a low level ACB trip can lead to a simple loss of supply power which normally can be restored after a qualified person (usually an engineer or electrician) has deemed it safe to do so. In contrast, equipment failure is far more significant as it can result in major loss of production, safety issues for workers, lengthy shut downs and complicated insurance claims. Industries such as mining and large scale manufacturing often face the dilemma of balancing a minimum number of production shut downs for maintenance while not neglecting the servicing requirements of key devices such as ACBs. By understanding the process of managing new and legacy ACBs it is possible for facilities managers and site engineers to apply a set of criteria which together help to form a plan underpinning workplace safety, uninterrupted production and equipment dependability. 2

Criteria 1: Appropriate circuit breaker commissioning and documentation Commissioning is an essential process for any newly installed ACB as it allows on-site engineers to formally document and test the ACB s trip protection settings, check that the ACB is damage free and confirm it is fit for service. At the most basic level, ACB commissioning should include: Confirmation that a full test report has been supplied by the ACB manufacturer, showing serial numbers and protection settings; Visual confirmation of protection settings; Confirm the on-site wiring diagrams and single line diagrams (SLDs) are correct; Confirmation of accessory functionality (i.e. charging motors, shunt coils etc) at applicable voltages; Unit not damaged and free of dirt / contaminates. Trip protection settings should be a primary focus for commissioning engineers. Whether commissioning a new ACB, or re-evaluating an existing unit, consideration must be given to the overload and short circuit protection characteristics. ACBs typically built within the last thirty years will feature an integrated trip unit, commonly referred to as an over-current release, or OCR. The OCR allows the setting of overload and short circuit trip pickup levels and intentional time delays (refer figure 2.0). Overload and short circuit settings should be configured to achieve two objectives; 1) During a fault it is necessary to protect downstream conductors against overheating and mechanical damage. 2) It is also necessary to provide reliability of supply or selectivity with upstream and downstream devices in accordance with AS/NZ3000:2007. Appling AS/NZS 3000 2.5.7.2.3, in conjunction with OCR trip curves (refer figure 2.0) engineering consultants can undertake the necessary selectivity analysis to determine suitable settings. Furthermore AS/NZS 3000, clause 2.5.5, defines the process to set the OCR to limit the harmful effects of a switchboard internal arcing fault. However, it appears to be a growing trend where many new switchboard installations are commissioned without adequate time being devoted to determining the best OCR protection settings for the power reticulation system. Careful consideration of these settings provides the best level of protection for the switchboard and the conductors connected to the ACB, which increases the level of safety for anyone working within the local area. Circuit breaker manufacturers recommend that OCR trip setting adjustment be confirmed via a calibrated secondary injection (S.I.) test device (refer figure 2.1). Secondary injection testing kits typically consist of a hand held device made by the circuit breaker manufacturer specifically for use with their ACB. A S.I. test proves that the trip pick up points and protection curve tolerances are within specification. Circuit breaker manufacturers can provide end users with blank test forms / software and a written test method. Documentation of the test results, including relevant identifying information such as ACB serial numbers and switchboard cell names should be included on the test forms. Figure 1.0: Modern Low voltage Air Circuit Breaker 3

Criteria 2: Periodic review of protection settings; Over time, the structure of the incoming supply and the outgoing loads may change. For example, a supply transformer may be upgraded, or additional loads may be added to the outgoing circuits. It is important to review the tripping characteristics of affected ACBs in order to achieve the desired outcomes described in Criteria 1. Adjustments should be verified as per the ACB manufacturer s recommendations and documentation should be updated. Criteria 3: On-going end user practical training; Documented ACB handling, operating and troubleshooting procedures should be provided to on-site equipment operators and maintenance workers. While this is a constant challenge for many workplaces, electrical site supervisors need to ensure that workers are fully prepared to interact with the installed switchgear confidently and safely. It is reasonable to conclude that equipment operators and maintainers should insist on a structured, ongoing training program for all on-site switchgear. Switchgear manufacturers will often supply documented procedures relating to transportation, handling, operation and troubleshooting of the device. Training sessions which display the switchgear and explain the manufacturers documented procedures ensures the best level of learning outcomes are achieved. Safety standards can be maintained or improved. Product training can often be enhanced by involving the equipment supplier (refer figure 3.0). Suppliers are usually keen to provide training material and demonstration samples to customers. This provides them with the opportunity to highlight the products key features, answer any questions and therefore leave the trainees feeling confident with the product. Figure 2.0: OCR trip curves used in a selectivity study. Figure 2.1: An OCR and secondary injection tester. Figure 3: NHP ACB demonstration and training. 4

Criteria 4: Through Life Service Requirements; Often once closed, ACBs will remain totally inactive year after year. The truth of the matter is that occasional exercise helps to maintain the correct operation of the ACB s breaking mechanism and contact assembly. Many circuit breaker manufacturers recommend that end users perform five off load open and close operations during a shutdown every six months. This simple procedure helps re-distribute lubrication between the moving internal parts, particularly in modern ACBs between the finger clusters and the pivot point of the fixed contact (refer figure 4.0). Like all electro-mechanical devices that are subjected to heat and in some cases arduous environmental conditions, ACBs need service and maintenance typically every two to three years. Most circuit breaker manufacturers will supply general servicing requirements for the ACB. However, due to the inherent complexity of modern trip mechanisms and the high degree of electronics contained within the ACBs OCR and accessories, seeking out a third party service company that has been accredited by the ACB manufacturer is advisable. Poorly maintained ACBs can lead to catastrophic product failure during operation, fires within switchboards or injury to human operators if working within close proximity to the device. The consequence of this type of failure can be lost production and significant downtime, costly repairs, and / or financial penalties from government safety authorities if on-site personnel are injured. Regular documented maintenance not only ensures that the ACB is fit and safe for service, but in the event of an insurance claim due to an electrical fault, site managers can refer to past service reports to demonstrate that steps had been taken to keep the ACBs in good working order. Servicing of ACBs should always include; 1) Removal of dirt and contaminates; 2) Restoring resistance of main contact to within specification and undertake insulation strength test; 3) Check operation of tripping and latching levers; 4) High temperature grade grease to be applied to finger clusters; 5) Test accessories (ie. Shunt coils, motors etc) at specified minimum and maximum rated voltages; 6) Secondary injection test of OCR and trip circuit; 7) Primary injection test of OCR and CT circuit. All results should be fully documented. Figure 4.0: Terasaki AR ACBs have a unique double break contact mechanism as shown above. Figure 4.1: Service engineer inspecting an ACB. 5

Criteria 5: Retrofit options for Air Circuit Breakers Problems with aging ACBs are typically mechanical in nature. Failure to open or close, finger clusters suffering heat stress, the integral trip unit is out of calibration are typical issues with legacy ACBs. Often replacement parts are no longer manufactured or the cost of employing specialist maintenance tradesmen to provide a bandaid repair is prohibitive. Throughout the 1960 s, 70 s and 80 s in Australia, ACBs from manufacturers such as the Nilsen (refer figure 5.0), UNELEC / CROMPTON PARKINSON and the WESTINGHOUSE (refer figure 5.1) along with many other types were installed in a plethora of industrial and commercial developments. Many of these ACB which are still installed today are operating beyond their intended service life. As previously described, the consequence of ACB failure can be financially costly and potentially dangerous to people. To help address this issue, some circuit breaker manufacturers and smaller specialist third party companies have devised retro-fit kit solutions which allow end users to modernise their ACBs (refer figure 5.2) with minimal downtime. Retro-fit kits are designed to allow the existing switchboard to remain fundamentally unchanged, with only the obsolete ACB being replaced. Existing busbars and cables remain unaltered, therefore simplifying the installation process and reducing downtime. Retro-fitting ACBs in the method described above is generally considered switchboard maintenance. Providing the retro-fit kit has been designed with relevant Australian standards in mind and recognised industrial practices, the use of such kits can lead to the controlled removal of ACBs that are obsolete and potentially dangerous. Figure 5.0: Obsolete NILSEN ACB Figure 5.1: Obsolete Westinghouse LA50 ACB Figure 5.2: Modern new Terasaki ACB 6

Criteria 6: Utilisation of new technology to improve switchboard safety Modern ACBs and complementary protection relays compared to their predecessors provide a greater range of performance features that can bolster overall switchboard longevity and safety. Minimising the damage caused by arc faults is a topic under frequent discussion within many large scale industrial workplaces. One technology that is gaining support within the mining and manufacturing sectors is the arc detect relay (refer figure 6.1). Arc detect relays use a network of fibre optic sensors (refer figure 6.2) distributed throughout the switchboard which respond to sudden changes in light intensity caused by the ignition of an electric arc. The arc detect relay responds to this event by closing an internal alarm contact which can be used to trigger the shunt trip coil of an incoming ACB. This type of technology including the relay and the fibre optic sensors lend themselves to retro-fit applications as they can easily be installed at the same time as the new ACB. By combining arc detect relay technology with a modern super fast tripping ACB it is possible to dramatically reduce the amount of energy released by the arc fault, therefore minimising the level of damage to the switchboard and lowering the risk of personal injury to electrical maintenance workers. Industrial automation is another area that can assist in improving the safety of switchgear and switchboards. A Human Machine Interface or HMI is generally understood to be a touch screen / display with an imbedded PLC that can run software to perform tasks. Traditionally this form of technology would be supplied by automation gurus or Systems Integrators (SIs). Many circuit breaker manufacturers however are now producing HMI based systems for the purpose of monitoring and controlling their ACBs within switchboards. Typically using communications protocols such as MODBUS RTU, HMI s allow the user to clearly interrogate the ACBs, revealing all relevant details such as close or tripped status, current, voltage, power parameters and trip history logs. Furthermore complete open / close control is normally possible. Safety of workers is greatly improved because the HMI can be situated outside the switch room providing complete separation. Figure 6.1: Arc detect relay Figure 6.2: Arc detect fibre optic sensor SUMMARY Low voltage air circuit breakers are a vital component in industrial power systems. Often they lead uneventful lives but during an electrical fault they may be required to respond, clearing the fault quickly and safely to minimise damage to the power reticulation system. ACBs are highly engineered, complex devices that require careful handling by users and regular maintenance is necessary to ensure longevity and reliability. Poorly maintained ACBs can catastrophically fail during operation resulting in loss of production and significant down time, costly repairs and injury to maintenance workers. Modern ACBs can in many cases be easily retro-fitted into existing switchboard to replace obsolete models, and when combined with contemporary arc fault protection relays and HMI solutions, substantial value to the integrity and safety of the switchboard can be achieved. 7

If you would like previous copies of Technical News, please complete the following form and fax to NHP on (03) 9429 1075 to the attention of the Marketing Department. Name:... Title:... Company:... Please post to: address...... Telephone: ( )... Fax: ( )... Please email to:... Other issues currently available. Please tick those you would like to receive. 1. First edition (Latched and delayed contactors) 2. Non-standard contactor applications (Parallel and series connections of contacts varying frequencies) 3. Contactor failure (Reasons for the failure) 4. Soft start for generator loads (Advantages of electronic soft starters) 5. Set the protection (MCCB breakers and application) 6. Contactor operating speed (Difference between AC and DC systems) 7. Quick guide to fault levels (Calculating the approximate fault levels) 8. IP ratings what do they mean? (IP Ratings, use and meaning) 9. Utilisation categories (Electrical life of switches) 10. AC variable frequency drives and breaking (Regenerative energy) 11.Don t forget the motor protection (Motor protection devices and application) 12. Electrical life of contactors (How and why contactors are tested) 13. Liquid resistance starter developments (For large slipring motors) 14. Taking the hiss out of DC switching (DC switching principles) 15. Start in the correct gear (Application of different motor starters) 16. Application guide to lamp selection (Industrial pushbutton controls) 17. Electrical surges can be expensive (Electrical surges) 18. Putting the PLC in control (advantages of the PLC) 19. The thinking contactor (The development of the contactor) 20. Some don t like it hot (Temperature rise in electrical switchgear) 21. Pollution of the airwaves (Unwanted signals and their effects on motor protection devices) 22. What s different about safety? (Safety devices and their application) 23. Talk about torque (Motors and torque) 24. Power factor what is it? (Power factor and correction equipment) 25. Terminations, good or bad? (Terminals) 26. RCDs are saving lives (Earth leakage protection; RCDs) 27. The quality switchboard(switchgear and protection devices for Switchboards) 28. How does electrical equipment rate (Understanding ratings of electrical equipment) 29. EMC - what s all the noise about (Understanding EMC) 30. Controlling high short circuit currents with current limiting circuit breakers (Short circuit co-ordination KT 7) 31. Another step in electrical safety (Changes to electrical safety) 32. Keep your cables cool (New requirements on cable protection) 33. A leak to earth can be electric (RCDs) 34. Keep Cool (Derating) 35. Improving star-delta protection (Overload and short circuit protection) 36. Does your CT measure up? (Selecting the correct current transformer) 37. Is your copper flexible? (Flexible busbars) 38. Where did the 10 volts go? (World uniform voltages) 39. Motor protection and wiring rules (overload protection) 40. Confused about which RCD you should be choosing? 41. Circuit breakers working together 42. Keeping in contact 43. Is your switchboard in good form? 44. Automation in a technological world 45. Thermal simulation of switchgear 46. Cable Considerations 47. Output chokes for use with variable speed drives 48. VSD Installation Techniques 49. The modern Scada System 50. 50th Edition Special 51. Electrical design considerations for commercial buildings 52. Terminal temperatures - how hot are they? 53. Causes of premature failure 54. Control voltages for contactors 55. Will it turn you off? (Electrical switchgear welding) 56. Electrical Arcs - Beauty and the Beast 57. The Power of Copper 58. Industrial networking with Ethernet IP TNL is available as a download from NHP s Online Resource Centre (ORC), visit nhp-online.com.au. The ORC provides members with up-to-the-minute technical information and powerful product tools, all at the click of a mouse button. Register for membership today! Editorial content: Please address all enquiries to: The Editor - NHP Technical News PO Box 199, Richmond, Victoria, 3121. NHP Electrical Engineering Products Pty Ltd A.B.N. 84 004 304 812 Copyright NHP 2010 NTNL61AUS 1011 * Rockwell Automation products not available from these locations AUSTRALIA nhp.com.au 1300 NHP NHP Victoria Melbourne +61 3 9429 2999 Laverton +61 3 9368 2901 Albury/Wodonga +61 2 6049 0600 Dandenong +61 3 8773 6400 Tasmania Hobart +61 3 6228 9575 Launceston +61 3 6345 2600 New South Wales Sydney * +61 2 9748 3444 Newcastle * +61 2 4960 2220 Wollongong * + 61 2 4272 5763 Act Canberra +61 2 6280 9888 Queensland Brisbane * +61 7 3909 4999 Townsville +61 7 4779 0700 Rockhampton +61 7 4927 2277 Toowoomba * +61 7 4634 4799 Cairns +61 7 4035 6888 South Australia Adelaide +61 8 8297 9055 Western Australia Perth +61 8 9277 1777 Northern Territory Darwin +61 8 8947 2666 NEW ZEALAND nhp-nz.com 0800 NHP NHP Auckland +64 9 276 1967 Hamilton +64 7 849 0257 Napier +64 6 843 6928 New Plymouth +64 800 NHP NHP Wellington +64 4 570 0634 Christchurch +64 3 377 4407