Armstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance

Similar documents
PT-516 Pumping Trap Installation and Maintenance

Technical Data P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP SD 9952B

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual

Crispin Valves Operating Guide. Crispin

4" PPF-P Pilot-Operated Pressure Powered Pump

LEVEL CONTROLS 313 IOM

CV Control Valves Installation and Operation Manual

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

Float Dynamic Steam Trap J10

CUSTOM COMBINATION AIR VALVE

TECHNICAL DATA CAUTION

Free Float Air Trap G8

Manufacturer Kakogawa, Japan DC5S

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

1451 Control Valve. General Instructions. Table of Contents

M-3025CB-AV Fuel Pump

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

INSTALLATION & MAINTENANCE MODEL mm

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A

INSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc.

Venturi Flow Meter Installation and Operation Manual

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Free Float Air Trap JA3 JAF3 / JA5 JAF5 JA7 / JA7.2 / JA7.5 / JA8

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

APT14 Automatic Pump Trap Installation and Maintenance Instructions

ETP-5E & ETP-10E ECO-TECH PLUS ELECTRIC CONVECTION STEAMER PARTS AND SERVICE MANUAL

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

APT10-2 Automatic Pump Trap

MFP14 Automatic Pumps Installation and Maintenance Instructions

INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

Valveworks USA Operation and Maintenance Booklet Model FC

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation, Operation & Maintenance Instructions

Wastewater Air Release Valve Models 48A, 49A

Bypass Blowdown Steam Trap BT3N / MBT3N / PBT3N

Pressure Reducing Valve Type 2114/2415

Wastewater Combination Air Valve. Operation, Maintenance and Installation Manual

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

Levalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016

Type 644 and 645 Differential Pressure Pump Governors

Sanitary Design Control Valves V972. Instruction Manual. Installation & Maintenance instructions for W.Arthur Fisher V972 series control valves

CV-COSR. Pneumatic Control Valve. Copyright 2013 by TLV CO., LTD. All rights reserved

SERIES WC & WCS. Watchman Series & WCS Condensate Units. Replacement Parts for. Hoffman PARTS LIST DN0436. Hoffman Pump

Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm

Model DFR 070/156/220 Rotary Actuator

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

Operating & Maintenance Manual For Steam Conditioning Valve

Instructions for Installation, Operation, Care and Maintenance

Surplussing Valve SP-COSR-16

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8

Fisher 644 and 645 Differential Pressure Pump Governors

GL Ludemann Y-Strainers

Check Valves Check Valves are the simplest form of directional control valves, but they can also be used as pressure controls.

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

Fisher 2052 Diaphragm Rotary Actuator

TECHNICAL DATA 1-1/2 (dn40)

Val-Matic 1-4 Combination Air Valve (Single Housing Type)

To ensure proper installation, digital pictures with contact information to before startup.

TECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc

Val-Matic 1-4 Combination Air Valve (Single Housing Type)

HYDRAULIC PUMP. INSTALLATION, OPERATION, & MAINTENANCE MANUAL MAINTENANCE MANUAL #: MM-HP Rev. A Page 1 of 12

Series 34. Specifications

Low Profile J Series Power Unit with Vane Pump

US SERIES. Universal Sewer Valves. Universal Sewer Valves. Valve Function. Features Include

DP556 Pump. 55:1, Air-operated, Grease. General. Operation. Technical Data. Installation. Mounting with Reinforced Cover (Recommended)

Fisher 657 Diaphragm Actuator Sizes and 87

Parts List. Item # Part # # Reqd. Description

270A SERIES HIGH-SIDE FLOAT VALVES BULLETIN 270A-SB13-01 SERVICE BULLETIN

INSTALLATION, OPERATING AND SERVICE MANUAL

Anderson Greenwood Series 400 Piston Pilot POPRV Installation and Maintenance Instructions

type 122a three-way Switching Valve

SUMMIT PUMP Horizontal End Suction Pump Close Coupled and Frame Mounted

Type MR108 Direct-Operated Backpressure Regulator

Replacing the Internal Oil Filter Elements for HS85 and OS 85 Screw Compressors

Power Steering Rack Leak from Right Side: Overhaul Procedure

TITAN FLOW CONTROL, INC.

GP-2000 : Trouble Shooting. Cause of problems

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference. PRESSURE REDUCING VALVES FOR STEAM COS/COSR Series.

TYPE PC Propeller Condensate Pumps

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

I & M MK96 & MK96C. Ideal Installation. Start-Up. Maintenance PROTECT VALVES WITH LINE STRAINERS

AP50 MANUAL AND PARTS LIST VERSA-MATIC PUMP. Service / Maintenance Log SUBMERSIBLE CENTRIFUGAL PUMP. Contact Information. Date Details Completed

Technical Instructions

Digital-Flo TM Boiler Water/Water Plate & Frame Heat Exchanger

Model: TON AXLE JACK. March 1999 Rev.-02

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

SERIES 270A HIGH SIDE FLOAT VALVES BULLETIN 270A-SB11-02 SERVICE BULLETIN

Valtek Spring Cylinder Linear Actuators

WEBER CARBURETOR TROUBLESHOOTING GUIDE

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

4.2 WATER PUMP (GEAR CASE MOUNTED AND LATER) (GCM)

26/01/2017 3GR-FSE ENGINE MECHANICAL: ENGINE UNIT: DISASSEMBLY; 2006 MY GS300 [01/ ]

DC-501 Double Check Backflow Preventer OPERATIONS, MAINTENANCE AND TROUBLESHOOTING GUIDE

Transcription:

Armstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance 119

Overview Warning: This bulletin should be used by experienced personnel as a guide to the installation and maintenance of the Armstrong Double Duty 6 Steam Trap/Pump Combination. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact Armstrong or your local representative if further information is required. 2014 Armstrong International, Inc. Designs, materials, weights and performance ratings are approximate and subject to change without notice. Application...3 Features...4 Operation...5 Installation...6 Instructions...7 Start-Up Procedures...8 Tank and Cap Assembly...9 Mechanism Assembly & Adjustment Procedure...10 Troubleshooting...11

Application When there is modulating control on heat exchange equipment there is a possibility that the system will stall (no longer be able to drain condensate). If only a steam trap is used condensate could flood the heat exchange equipment causing corrosion, water hammer, and poor temperature control. The Double Duty has a steam trap with an integral pump to prevent the system from stalling. If the condensate floods the body of the Double Duty and reaches its upper trip point high pressure steam will enter the body and push the condensate out. This prevents condensate from accumulating in the heat exchange equipment. Suggested Accessories Inlet and discharge check valves Gauge glass assembly for pump Gauge glass assembly for receiver Pressure gauge assembly pump body Pressure gauge assembly receiver Pressure gauge assembly motive steam Pressure gauge assembly discharge piping Pressure gauge assembly heat exchange equipment Receiver Double Duty 6 Physical Data in mm A 29 737 B 16-11/16 424 C 1-1/2 38 D 1 25 E 7/8 22 F 1-1/8 48 G 2-1/4 57 H 24 610 J 14 356 K 10-13/16 275 L 10 254 M 2-13/16 71 N 8 203 O 3-3/16 81 Weight lb (kg) 140 (64) Double Duty 6 Specifications Model DD6 Motive Fluid Steam Maximum Operating Pressure 200 psi Minimum Motive Differential 10 psi Maximum Operating Temperature 400 F Body Carbon Steel Mechanism Stainless Steel Float Stainless Steel Connections (condensate) 150# Flange Inlet Check Valve Optional 1-1/2 Discharge Check Valve Optional 1 Springs Inconel X-750 1/2 NPT Motive 1 NPT Vent K E J D 1 150# Flange Outlet O B G H A C 1-1/2 150# Flange Inlet L 1/2 NPT Drain M N.56 x 1.06 Slot (4 Places) 3

Features 1 The trap body has an integral pump to prevent flooding of the heat exchange equipment. It uses steam motive with no electricity or special mechanical seals required. 2 The pump mechanism is attached to the cap which can be removed from the body without taking it out of the condensate line, and the steam trap mechanism can be accessed through the cap opening. 4

Operation Operating as a trap (system pressure greater than back pressure) As the condensate flows through the inlet check valve, the trap and pump floats become buoyant and rise with the fluid level. The upward movement of the float causes the trap valve to open. If the system pressure is greater than the back pressure the condensate will flow through the steam trap valve into the condensate return. Operating as a pump (system pressure less than or equal to back pressure) If the system pressure is less than the back pressure liquid floods the body. When the condensate reaches the upper trip point of the pump mechanism the motive inlet valve opens and the vent valve closes. The open motive valve allows the motive fluid to enter and pressurize the body. The pressure inside the body shuts the inlet check valve and when it is greater than the back pressure pushes the water through the discharge check valve into the condensate return line. The float lowers with the water level and when it reaches the lower pump trip point the motive inlet valve closes and the vent valve opens. This relieves the pressure in the body and allows it to fill again. 5

Installation 1 Filling head: Install the DD6 below the equipment being drained. Fill head is the distance from the top of the cap to the bottom of the receiver. The standard fill head for the DD6 is 6 inches. 2 Liquid reservoir: Liquid flowing from the heat exchange equipment must be stored during the pump discharge cycle. A liquid reservoir or receiver should be installed above the unit to prevent flooding the equipment 3 4 5 Vent piping: The vent pipe must be pitched to self drain. The vent connection is 1 npt. Replace any temporary plastic plugs with appropriate fittings. Gauge glass connections are ½ npt and 10 center to center. 6

Instructions 1 2 3 4 5 6 7 Before installing make sure the piping is clean and free of debris. When installing take care to not allow pipe tape or similar items to enter the product. * Debris can affect proper operation and performance Check the condensate inlet, condensate outlet, motive inlet, and vent outlet ports before connecting piping. The DD6 must be installed with the vent and motive vertical and the condensate inlet and outlet horizontal. * The product will not function properly if not installed in the correct orientation Connect pipes securely When connecting pipes unions or flanges should be used close to the DD6 connections. This reduces the amount of time needed for maintenance and repair. Avoid water hammer. If water hammer is experienced it could injure personnel or damage the equipment. Do not disassemble product. If the product is disassembled the function or performance of the unit could be compromised. 8 9 10 Attach strainer with blow down valve on motive steam inlet. Attach check valve on condensate inlet and discharge. Attach the motive drip trap to the steam motive line. 11 Provide clearance for future maintenance. 7

Start-Up Procedures Caution Make sure all connections are secure before opening valves. Open valves slowly to reduce the chance of water hammer 1 2 3 4 5 Open isolation valve(s) in condensate discharge. Open isolation valve in equalizing line. Open motive isolation valve. Confirm that the steam does not flow into the pump body or equalizing line by checking pressure gauges. Open the isolation valve on the thermostatic air vent. Open the isolation valve on the condensate inlet. 6 The start-up is complete if the Double Duty Six performs trap operation or pump operation and is confirmed by use of the gauge glasses and pressure gauges. Maintenance and Inspection Most failures occur because of debris in the piping. Caution Before starting any maintenance make sure the Double Duty 6 is completely isolated from the system. Make sure the system is at atmospheric pressure 8

Tank and Cap Assembly Tank Assembly FH2626 Cap Assembly FH2620 Body B6991 Float 2 X FH1373 Pipe Plug 8 (203) 11.5 (292) FH1373 Pipe Plug Trap Assembly (D24092) = C6213 (Mechanism) + B6991 (Float) + B7549 (Gasket) Cap Assembly 3 X FH1372 Washer FH2630 Inlet Seat FH1393 Vent Seat 1 X FH1372 Washer FH1373 Pipe Plug D6413 Nameplate 2 X FH1398 Drive Screw 2 X D6470 Bolts FH1391 Inlet Valve FH1392 Vent Valve FH114 Cap Flange D6471 Motive Deflector FH2625 Mechanism 2 X FH1532 Bolts FH1546 Float FH1543 Bolt 9

Troubleshooting Problem Diagnosis Solution Condensate not discharging Inlet isolation valve closed Open valve Pump inlet and outlet switched Motive inlet and vent switched Discharge isolation valve closed Equalizer line isolation valve closed Motive pressure not adequate Motive inlet isolation valve closed Motive strainer clogged Air vent damaged Motive pressure exceeds pump rating Outlet check valve installed backward Outlet check valve does not open Inlet check valve does not open Inlet check valve is not completely closed Vent valve leaks Motive steam valve leaks Float damaged Re-pipe Open valve Adjust pressure Open valve Clean or replace Replace air vent Adjust pressure Install check valve properly Replace Confirm lack of pressure in body Disassemble and clean check valve Disassemble, clean and inspect - replace defective parts Disassemble and replace inlet valve Disassemble and replace float Motive steam remains on Motive steam valve leaks Disassemble and clean or replace Mechanism not assembled properly Steam leaks out of body Body gasket leaks Replace gasket Plugs leak Assemble so the motive valve is inserted in motive seat Remove, add thread sealer and reinstall 11

Mechanism Assembly & Adjustment Procedure Mechanism Assembly 2x FH2122 Spring Sub-Assembly FH1545-1 (Ref.) FH1534-1 Tube Pin FH1548 Spring Arm Long FH1534-2 Tube Pin 5 X FH1545 Cotter Pin FH1536-2 CLEVIS PIN 4x FH-1536-1 Clevis Pin 2 X FH1376 Nut FH1381 Valve Holder FH2627 Actuator Rod FH2622 Mounting Bracket FH2624 Actuator 2 X FH2207 Nut FH2628 Spacer 2 X FH2269-2 Bushing FH2183 Float Arm 4 X FH2269-1 Bushing Adjustment Procedure Note: 1. All adjustments must be made while mechanism secured to cap. 2. Be sure all lock nuts are tightened. 3. Use dial caliper to set dimensions. 1, 2, or 3 washers (Note 4) Adjust lock nuts to achieve the.55 dimension Moving the lock nuts up toward the cap will reduce the.55 dimension Motive Deflector.55±.03 Motive Vent Notes: 1. Measured when mech is fully tripped with the vent valve seated and the motive valve full open. 2. Spring arm should be manually lifted thru its entire range to make sure no binding occurs on the motive vent valves. 3. If binding is felt loosen lock nuts and straighten valve holder and retighten (start process again). 4. Recommend that compressed air be plumbed to the motive and the mech tripped against air several times..25±.03 Notes: 1. Measure the point at which the motive valve starts to lift the motive ball. 2. Air should be plumbed to motive so point of valve contact can be felt. 3. Spring arm should be manually lifted until the valve contacts motive ball. This will be evident by the increased effort and the sound of leaking air. 4. The dimension is adjusted by adding or subtracting washers under the motive seat. Notes: 1. Position motive deflector to cover the top of the motive valve. 2. Plumb air to motive and trip mechanism making sure the air does not bypass the deflector. 3. Tighten retaining bolt. 10

Armstrong International 816 Maple Street, Three Rivers, MI 49093 USA Phone: (269) 273-1415 Fax: (269) 278-6555 armstronginternational.com 119 Printed in U.S.A. - 6/14 2014 Armstrong International, Inc.