Tolerance-Based Time-Current Coordination

Similar documents
Evaluating Selective Coordination Between

Source-Side Fuse/Load-Side Recloser Coordination

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Selection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

Selective Coordination

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Selective Coordination Enforcement:

A NEW FUSE-SAVING PHILOSOPHY

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Transformer Protection

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3.

3.2. Current Limiting Fuses. Contents

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

ECET Distribution System Protection. Overcurrent Protection

Miniature circuit breaker Application guide

Protective Device Coordination ETAP Star

Shippensburg University

Fusesaver specification form

Pretest Module 29 High Voltage Unit 1

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

EE 741 Over-voltage and Overcurrent. Spring 2014

X-Limiter full-range current-limiting fuse

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Advanced Protective Relay Training

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Engineering Dependable Protection

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

www. ElectricalPartManuals. com Engineering Dependable Protection

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

CHAPTER 4 PROTECTION REQUIREMENTS

Calculating AC Line Voltage Drop for M215 Microinverters with Engage Cables

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Power systems Protection course

Dual Power. Protection. Protection

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011-

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

Safe, fast HV circuit breaker testing with DualGround technology

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

BREAKER FAILURE PROTECTION

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Functional Overview and Operating Principles for the AR-OH and AR360 Overhead AutoRANGER Fault Indicators

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

Motor Protection. Voltage Unbalance & Single-Phasing

Figure 1. Two and Three-phase MagneX.

Cost Benefit Analysis of Faster Transmission System Protection Systems

Close-Open (Short-Circuit) Time Results Interpretation

Power System Solutions (PSS)

Self-Adaptive Relaying Scheme of Reclosers for Fuse Saving in Distribution Networks with DG

The purpose of this lab is to explore the timing and termination of a phase for the cross street approach of an isolated intersection.

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses

Cutler-Hammer May 2001

AutoLink Frequently Asked Questions

Solid Dielectric, Single Phase Recloser

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

PROTECTION AND CONTROL

FUSES. Safety through quality

4-Day Power System Analysis, Coordination, System Studies

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Product Selection Guide

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

AP/UP, AP/MIL Series Magnetic Circuit Protectors

Solid Dielectric, Single Phase Reclosers

FX Full-Range Current-Limiting Fuse

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Selective Coordination Requirements

Recommended Procedures

Fuseology. Dual-Element, Time-Delay Fuse Operation

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

SURE TRIP RETRO KITS

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Mica Element Support. Compacted Quartz Sand. Length B

Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults

ADDITIONAL INFORMATION. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY and RETROFIT KITS. FEATURES and APPLICATION Page 2

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

Advantages of SELF POWERED Overcurrent & Earth Fault Relays

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Transcription:

S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background.... 2 Alternative TCC Representation Method.... 3 Conclusions.... 8 November 23, 2015 S&C Electric Company 2015, all rights reserved Instruction Sheet 766-576

Overview When S&C Electric Company introduced the S&C IntelliRupter PulseCloser Fault Interrupter, the high accuracy sensing and operational precision of the product warranted a new look at the way protection behavior is represented. Rather than follow the existing convention of illustrating a Time Current Characteristic (TCC) as a single, nominal TCC line, S&C elected to demonstrate the precision of the IntelliRupter fault interrupter s time-overcurrent protection responses using TCC tolerance-response bands. The reason for improving upon conventional coordination methods was that the single TCC line, which is coordinated using a Coordinating Time Interval (CTI), doesn t enable users to benefit from the IntelliRupter PulseCloser Fault Interrupter s significantly tighter response tolerances. This is true because the CTI coordination method simply separates single (nominal) TCC lines by a fixed time-value, and it doesn t account for protection-performance differences among devices being coordinated. Background CTI time-values may differ where fault-interrupter fault-clearing and relay-response times vary appreciably. And most users will select different CTI time-values when coordinating electromechanical relays versus microprocessor relays and controls. But once a CTI time-value is applied, the sensing and response tolerances of each device are ignored, and the time-overcurrent protection performance of all breakers and reclosers being coordinated are considered to be equal. What differentiates the superior performance of the IntelliRupter fault interrupters from other breakers and reclosers begins with its use of Rogowski coils. These primarycurrent sensing devices are very precise and remain linear across an extremely wide current range. This is in sharp contrast to the 10% turns ratio error of the class C or 10P20 current transformer (CT) used in many breakers and reclosers. The combination of Rogowski coils, coupled with the IntelliRupter fault interrupter s current-measuring accuracy, results in a +/ 2% current-measurement tolerance during protection functions. (The steady-state current measurements, which are averaged over one second, yield a much higher +/ 0.5% sensing tolerance.) Comparing this performance to the competition, and considering the class C or 10P20 CT as having +/ 5% sensing tolerance, today s most popular relays have a +/ 8% current-measurement error. Further, the IntelliRupter fault interrupter s timing tolerances are also +/ 2%. But today s widely used relays only have a timing accuracy of +/ 4%. Additionally, there is always a fixed-time error associated with today s protection element time response. In the case of the IntelliRupter fault interrupter, its fixed-time error value is +/ 0.008 seconds. In contrast, today s more popular relays have a fixedtime error of +/ 1.5 cycles, or 0.025 seconds at 60Hz. And finally, the IntelliRupter fault interrupter s fault-clearing time of 2 cycles may rival the claims of some of today s alternative fault-interrupting products. But many of the devices presently in service have fault interrupters with fault-clearing times that vary between 3 to 6 cycles. 2 S&C Instruction Sheet 766-576

The IntelliRupter fault interrupter TCCs have superior precision when compared to S&C expulsion fuses. With expulsion fuses, an operating-response band is developed using the fuse s minimum-melt and total-clear TCCs. Similarly, an IntelliRupter fault interrupter TCC tolerance-response band accounts for all the individual tolerances contributing to its minimum and maximum time-overcurrent fault-clearing response. And instead of relying on a fixed CTI time-value, the basis for coordinating these TCC tolerance-response bands is rooted in how expulsion-fuse TCCs are graphically coordinated. As a reminder, the coordination of series fuses is accomplished by simply ensuring a fuse s slower (total-clear) and faster (minimum-melt) TCCs don t touch or cross adjacent upstream and downstream fuses for an appropriate level of fault current. Other manufacturers sometimes recommend using a 25% setback allowance to account for prior fuse damage. However, S&C fuses don t require derating for potential damageability. But to appreciate why TCC tolerance-response bands provide a better means of coordination, graphic examples may better illustrate these benefits. For example, let s begin by coordinating two series devices using the CTI method. Figure 1 illustrates two IEEE Extremely Inverse single (nominal) TCC lines separated by a CTI of 250 milliseconds, which is frequently used when coordinating microprocessor relays. The upper TCC line represents a pickup of 900 amperes and a time-multiplier or time-dial of roughly 4.8. The lower TCC line represents a pickup of 600 amperes and a time-multiplier of 1.0 Figure 1. IEEE Extremely Inverse single, nominal TCC lines separated by a CTI of 250 milliseconds. S&C Instruction Sheet 766-576 3

Figure 2 now adds the specification tolerances of an IntelliRupter fault interrupter to these single TCC lines. These tolerances are: +/ 2% current (includes any contribution from the primary-current sensing device) +/ 2% time +/ 0.008 seconds fixed-time error +2 cycles fault-clearing time As seen in Figure 2, there is an appreciable gap between the top and bottom TCC tolerance-response bands, and this gap is in fact 188-milliseconds. Figure 2. IntelliRupter fault interrupter IEEE Extremely Inverse TCC tolerance-response bands. This 188-millisecond gap is so large, Figure 3 on page 5 indicates that two additional IntelliRupter fault interrupters can easily be inserted between the upper and lower TCC tolerance-response bands with no coordination challenge whatsoever. 4 S&C Instruction Sheet 766-576

Figure 3. IntelliRupter fault interrupter s performance precision enables the addition of two more IntelliRupter fault interrupters. S&C Instruction Sheet 766-576 5

TCC tolerance-response bands are not limited to the IntelliRupter fault interrupter. In fact, Figure 4 uses a relay-based recloser or circuit-breaker for the upstream device and an IntelliRupter fault interrupter for the downstream device. In this instance, one of today s more popular relays is used for the previous IEEE Extremely Inverse TCC coordination example. The pickup and time-multiplier settings are as before (600 and 900 amperes, with time-multipliers of 1.0 and roughly 4.8 respectively). The TCC response tolerances for the upstream (crosshatched) relay and breaker or recloser TCC reflected in the plot of Figure 4 are: +/ 8% current (includes +/ 5% primary-current sensing-device error) +/ 4% time +/ 0.025 seconds fixed-time error +3 cycles fault-clearing time Figure 4. IEEE Extremely Inverse TCC tolerance-response bands for an IntelliRupter fault interrupter (lower TCC band) and a relay-based recloser or breaker (upper TCC band). 6 S&C Instruction Sheet 766-576

Unlike the results produced by the precision of the IntelliRupter fault interrupter, there is only about a 140-millisecond separation between the top and bottom TCC tolerance-response bands plotted in Figure 4 on page 6. However, Figure 5 demonstrates there is still enough separation margin to enable the addition of another relay-based recloser control. Figure 5. One more competitor s IEEE Extremely Inverse TCC relay-based recloser is added (middle TCC band). S&C Instruction Sheet 766-576 7

To better illustrate the contrast between the two previous tolerance-response coordination examples, Figure 6 not only highlights the superior performance and precision of the IntelliRupter fault interrupter versus the less precise behavior of a relay, but it also demonstrates the benefit of using tolerance-response coordination. Instead of coordinating only two series devices using the CTI method, where the time-value is 250 milliseconds, the tolerance-response technique enables three or four series devices to be well coordinated within the same time interval. Figure 6. A side-by-side comparison of the IntelliRupter fault interrupter TCC toleranceresponse bands (TCC plot on right) with those of an IntelliRupter fault interrupter and two of today s popular relay-based fault interrupters (TCC plot on left). Conclusions The illustration of TCC tolerance-based coordination conclusively demonstrates that time-overcurrent protection responses can be better modeled using cumulative response tolerances. Instead of simply relying on a single, nominal TCC line and a fixed CTI time value (which are overly conservative), graphically coordinating comprehensive TCC response bands results in more accurate TCC margins. So, if increasing the number of series-coordinated, time-overcurrent devices is the ultimate objective, using the proposed TCC tolerance-response coordination technique (and ideally the IntelliRupter PulseCloser Fault Interrupter) can appreciably improve upon what can be achieved using the conventional CTI method. 8 S&C Instruction Sheet 766-576