RedCos-P Pressure sensor 20 Pa Pa

Similar documents
Data Sheet SCHISCHEK EXCOS-P. Pressure sensor 20 Pa Pa. Supplied by. .com. Call us on +44 (0)

RedBin-P Pressure switches 5 Pa Pa

ExBin-P Pressure switches 5 Pa Pa

InBin-P Pressure switches 5 Pa Pa

SCHISCHEK REDBIN-D TRANSMITTER

RVP-R- VAV controller. In explosion-proof version

m WARNING! READ m BEFORE INSTALLATION

XMP ci. Process Pressure Transmitter with HART -communication. Ceramic Sensor. accuracy according to IEC 60770: 0.1 % FSO.

DMK 331P. Industrial Pressure Transmitter. Pressure Ports With Flush Welded Stainless Steel Diaphragm

JUMO dtrans p20. Process pressure transmitter. Type Brief description. Key features. Block diagram

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

JUMO dtrans p20 DELTA

E II 3 (1) G Ex na [ia Ga] IIC/IIB T4 Gc

DMK 331P. Industrial Pressure Transmitter. Pressure Ports With Flush Welded Stainless Steel Diaphragm. accuracy according to IEC 60770: 0.

JUMO dtrans p20. Process pressure transmitter. Brief description. Special features. Block diagram. Approvals/approval marks (see "Technical data")

L(+) SV1 N(-) NC. Terminal Block Connections L (+) N (-) SV1 K2 K1. Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

DMP 333. Industrial Pressure Transmitter For High Pressure. Stainless Steel Sensor

Differential pressure sensor

Compact temperature switch Model TCS

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

Pressure transmitter JUMO dtrans p02

DMP 331P. Industrial Pressure Transmitter. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm

Type 2REX-A. Oil & Gas / Heavy Industry

SATRON VVFe Pressure Transmitter

Proportional pressure reducing valves type DHRZO and DHRZA standard and ex-proof version, direct operated, ISO 4401 size 06

Type Z & Ex pz purge and pressurization system

INLINE Flow sensor for hazardous area II 1 G/D - II 2 D - II 3 GD - I M1

Compact differential pressure switch Models DC, DCC

Pressure Transmitter

L(+) SV1 N(-) NC. Terminal Block Connections L (+) N (-) SV1 K2 K1. Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

KINAX SR 709 Transmitter for Position Feedback

INTERNATIONAL METAL ENGINEERING

JUMO dtrans p02. Pressure transmitter. General application. Approvals/marks of conformity. Data Sheet Page 1/6. II 1/2G Ex ia IIC T6 Ga/Gb

DMP 331P DMP 331P. Industrial Pressure Transmitter. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm

Pressure transmitter for industrial applications Type MBS 4510

Fieldbus Segment Protector F2-SP-IC* Features. Assembly. Function. Connection. Zone 2 Div. 2

BFS-10-O G1/4: BFS-10-O G1/2: BFS-10-O G1: Contact rating: BFS-10-O G1/4

Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS

SATRON VT Pressure Transmitter

Temperature sensor TE2

SATRON VDt Differential Pressure Transmitter

Output signal active note. Measuring range rel. pressure. Electrical Data Power supply DC V, ±10%, 1.1 W

DMP 331 DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial

CombiTemp Temperature Measuring System

Mini temperature switch Stainless steel switch enclosure Model TXS

SPOOL VALVES pilot or air operated, spool type single/dual solenoid (mono/bistable function)

Assembly. Trunk IN + - S U, I U, I. Spur 1

Technical Data. Dimensions

Material: Weight: Shaft Loads: Enclosure Rating: Cable: Cable Glands:

Actuators & Positioners Electro-Pneumatic Converters I/P Signal Converters - TEIP 11 Model without Booster Stage

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

SPOOL VALVES pilot operated or air operated, spool type single/dual solenoid (mono/bistable function) brass body, 1/4

Metal tube flowmeters Series M21 Variable area flowmeter for low flows of liquids, gases and steam

Pressure transmitter for general industrial purposes MBS 3000 and MBS 3050

Compact pressure switch Model PCS

SITRANS P measuring instruments for pressure

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /09

Differential pressure transmitter PASCAL Ci4 Delta P

ANKERSMID Temperature controller ATC 510/520/525 for wall-mounting. Application

KINAX SR 709 Transmitter for position feedback

T 3965 EN Type 3965 Solenoid Valve Island To control pneumatic actuators

Intrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS Technical brochure

Pressure transmitters for heavy-duty applications MBS 2000 and MBS 2050

Differential Pressure Sensors

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

LMK 387. Stainless Steel Probe. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO

Pressure transmitters for heavy duty applications MBS 3200 and 3250

DMK 331P DMK 331P. Industrial Pressure Transmitter. Pressure Ports With Flush Welded Stainless Steel Diaphragm. Pressure Transmitter.

SPOOL VALVES pilot or air operated, spool type single/dual solenoid (mono/bistable function) brass body, 1/4

Ø 68 mm to ø 115 mm. Material: Weight: Shaft Loads: Enclosure Rating: Connection Options. Cable: Cable Glands:

Solenoid coil for control in potentially explosive areas Type BZ

INSTRUCTION MANUAL (ATEX / IECEx)

FAIRCHILD T8001 SERIES STANDARD RANGE MINIATURE TWO-WIRE, P/I PRESSURE TRANSDUCER. Installation, Operation and Maintenance Instructions

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Pressure transmitter for general industrial purposes Type MBS 3000 and MBS 3050

AP ATEX AIRPOWER POSITIONERS AP2000 FEATURES AP1000 & AP1200 FEATURES OPTIONS OPTIONS

ABB Instrumentation. 50T Series Transmitters Model 54G/A gauge/absolute pressure transmitter for sanitary use. Specification sheet

Type 4746 Electric or Pneumatic Limit Switch

Pressure transmitter for marine applications MBS 3100 and MBS 3150

High temperature pressure transmitters for heavy-duty applications MBS 2200 and MBS 2250

Pressure transmitter PASCAL CV4

Type Electronic Limit Switch

PRESSURE TRANSMITTER PYRP-28 INDUSTRIAL & INTRINSICALLY SAFE PRESSURE TRANSMITTER PRESSURE TRANSMITTER

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

Inductive conductivity meter

Centrifugal fan with highly efficient EC drive motor

Explosion and flame-proof single phase electric motors

EE300Ex-HT. Humidity/Temperature Transmitter for Intrinsically Safe Applications. Typical Applications. Features. Display

Thermocouple For additional thermowell Model TC10-B

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Resistance thermometer Without thermowell Model TR10-H

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

Explosion and flame-proof cast iron electric motors

ABB MEASUREMENT & ANALYTICS DATA SHEET. TEIP11 I/P signal converter for standard signals

Portable pressure calibrator, Wally Box III Model CPH7600

Positive displacement flowmeter

Mechanical features. Spring-loaded elastic terminals: resist vibrations

Transcription:

RedCos-P Pressure sensor 20 Pa... 7.500 Pa Electrical, explosion-proof pressure / differential pressure sensors 24 VAC/DC supply voltage, 0...10 V / (0) analogue output EC type-approved in acc. with ATEX directive 2014 / 34 / EU for zone 2, 22 Compact. Easy installation. Universal. Cost effective. Safe. RedCos - P-... RedCos - P-... - A RedCos -... - CT RedCos -... - OCT RedCos -... - VA RedCos -... - OVA Subject to change! Type Sensor Supply Range min. Setting max. Pressure Ex-i output Wiring diagram RedCos- P- 100 Pressure /Diff. press. 24 VAC /DC ± 100 Pa 20 Pa 25.000 Pa (0) / 0...10 V SB 1.0 RedCos- P- 250 Pressure /Diff. press. 24 VAC /DC ± 250 Pa 50 Pa 25.000 Pa (0) / 0...10 V SB 1.0 RedCos- P- 500 Pressure /Diff. press. 24 VAC /DC ± 500 Pa 100 Pa 50.000 Pa (0) / 0...10 V SB 1.0 RedCos- P-1250 Pressure /Diff. press. 24 VAC /DC ± 1.250 Pa 250 Pa 50.000 Pa (0) / 0...10 V SB 1.0 RedCos- P-2500 Pressure /Diff. press. 24 VAC /DC ± 2.500 Pa 500 Pa 50.000 Pa (0) / 0...10 V SB 1.0 RedCos- P-5000 Pressure /Diff. press. 24 VAC /DC ± 5.000 Pa 1.000 Pa 75.000 Pa (0) / 0...10 V SB 1.0 RedCos- P-7500 Pressure /Diff. press. 24 VAC /DC ± 7.500 Pa 1.500 Pa 120.000 Pa (0) / 0...10 V SB 1.0 RedCos- P-... - A Types as above with additional intrinsically safe analogue output to connect an external digital indicator (0) 4 20 ma SB 3.1 RedCos- P-... - CT Types as above with aluminium housing and seawater resistant coating (cable glands M16 brass nickel-plated, screws in stainless steel) RedCos- P-... - OCT Types as above, offshore version with aluminium housing and seawater resistant coating (stainless steel tubes for clamping ring connection, RedCos- P-... - VA cable glands M20 brass nickel-plated, screws in stainless steel) Types as above with stainless steel housing for aggressive ambient (cable glands M20 brass nickel-plated, screws in stainless steel) RedCos- P-... - OVA Types as above, offshore version with stainless steel housing for aggressive ambient (tubes for clamping ring connection and screws in stainless steel, cable glands M20 brass nickel-plated) Product views and applications Pressure / Differential press....cos-p...-ct...cos-p...-va Offshore...-OCT Offshore...-OVA Description The RedCos-P-... pressure sensor generation from ± 100 Pa to ±7.500 Pa (acc. to type) is a revolution for differential pressure measuring in HVAC systems, in chemical, pharmaceutical, industrial and offshore /onshore plants, for use in hazardous areas zone 2 (gas) and zone 22 (dust). Highest protection class (ATEX) and IP66 protection, small dimensions, universal functions and technical data guarantee safe operation even under difficult environmental conditions. All sensors are programmable on site without any additional tools. The measuring ranges are scalable within the maximum ranges. At...Cos-P-100 the smallest P range is 20 Pa. The analogue output signal is either 0...10 VDC or (0) and can be selected on site. The integrated display is for parametrisation and an actual value indication at working mode (can be switched off as needed)....cos-p-...-a sensors are equipped with an additional intrinsically safe (IS) output, e. g. for an external indicator....cos-p-...-oct and...-ova offshore versions are equipped with stainless steel tubing Ø 6 mm. Highlights For all types of gases, mists, vapours and dust for use in zone 2 and 22 Power supply 24 VAC / DC Scalable analogue output, selectable 0 10 V / (0)4 20 ma Integrated Ex terminal box No addional Ex-i module required No intrinsically safe wiring / installation between panel and sensor required No intrinsically safe wiring / installation and no space in the panel required Optional IS-output (0)4 20 ma for external indicator in Ex-areas Display with backlight, can be switched off Password locking Down to 20 C ambient temperature applicable Compact design and small dimension Robust aluminium housing (optional with seawater resistant coating) or in stainless steel IP66 protection Offshore versions with pressure tube connection for clamping ring Ø 6 mm 1 / 5

Technical data Supply voltage, frequency Current, power consumption Galvanic isolation Electrical connection Cable glands Cable glands...-ct Protection class Display Control elements Housing material Dimensions (L W H) Weight Special solutions and accessories 24 VAC / DC ± 20 % (19,2...28,8 VAC / DC), 50 / 60 Hz 150 ma, ~ 4 W, internal fuse 500 mat, without bracket, not removable Supply for analogue in- and outputs min. 1,5 kv, supply for relay output min. 1,5 kv Terminals 0,14...2,5 mm² at integrated Ex terminal box, stripping length 9 mm, torque 0,4...0,5 Nm, equipotential bonding 4 mm² 2 M16 1,5 mm, Ex approved, for cable diameter ~ Ø 5...9 mm 2 M16 1,5 mm, Ex approved, brass nickel-plated, for cable diameter ~ Ø 6...10 mm...-va,...-oct,...-ova 2 M20 1,5 mm, Ex approved, brass nickel-plated, for cable diameter ~ Ø 6...13 mm Class I (grounded) 2 16 digits, dot-matrix display, backlit, for configuration, user guidance, parameter and actual value indication 3 buttons for configuration Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CT/...-OCT) or stainless steel housing, 1.4581 / UNS-J92900 / similar AISI 316Nb (...-VA /...-OVA) Aluminium housing ~ 180 107 66 mm, stainless steel housing ~ 195 127 70 mm (each without connectors) ~ 950 g aluminium housing, stainless steel version ~ 2,5 kg Ambient temperature 20...+50 C, storage temperature 35...+70 C Temperature class Aluminium housing T6 (T80 C) at 20...+50 C Ambient humidity Sensor circuit Sensor Pressure connection Measuring range Stainless steel housing T5 (T95 C) at 20...+40 C, T4 (T130 C) at 20...+50 C 0...95 % rh, non condensing Internal intrinsically safe (IS) circuit Piezo pressure transmitter P+ / P sleeves Ø 4...6 mm. OCT versions have 2 stainless steel (316L) tube connections for clamp ring fittings Ø 6 mm ± 100 Pa, ± 250 Pa, ± 500 Pa, ± 1.250 Pa, ± 2.500 Pa, ± 5.000 Pa, ± 7.500 Pa in acc. to type Minimum measuring range is 20 % of full range (e. g. 20 Pa at ± 100 Pa sensor) Response time of sensor T90 / 5 s Accuracy of pressure < ± 1 % typically, max. ± 2 % of end value ± 1 Pa Non linearity and hysteresis ±0,05 % typically, max. 0,25 % of end value Start delay 5 s Setting zero point Via menu. Short-circuit mechanically both tube connectors P+ / P for the moment of zero point setting Stability Long term stability < 0,2 % /year, temperature influence < 0,02 % /K, supply voltage influence < 0,01 % Voltage U [V] or current I [ma], selectable on site via menu, protected against short circuit and external voltage up to 24 V and against polarity reversal Voltage output U 0...10 VDC adjustable, invertible, burden > 1 kω, influence < 0,05 % / 100 Ω Current output I adjustable, invertible, burden < 500 Ω, influence < 0,1 % / 100 Ω, open circuit voltage < 24 V in alarm mode Increasing or decreasing output signal, selectable on site, down to 0 VDC / 0 ma or up to 10 VDC / 20 ma Wiring diagram SB 1.0 Scope of delivery Sensor, 3 self-tapping screws 4,2 13 mm resp. in stainless steel (with...ct and...va versions), short circuit tube Cos-P-...-A with 1 additional plug for cable Ø 6...8 mm Parameter at delivery min. /max. pressure range limits (e.g. RedCos-P-100 = 100 +100 Pa), output 4 20 ma, output in alarm mode decreasing to 0 V /0 ma...cos-p-...-a as above and 1 additional intrinsically safe analogue output Ex-i analogue output (0), intrinsically safe (IS), burden max. 400 Ω Accuracy ±0,5 % Wiring diagram SB 3.1...-CT Types in aluminium housing with seawater resistant coating, parts nickel-plated...-oct Offshore version in aluminium housing with seawater resistant coating, parts nickel-plated...-va Types in stainless steel housing, parts nickel-plated...-ova Offshore version in stainless steel housing, parts nickel-plated EXC-RIA-16 LCD indicator (IS) for Ex- /RedCos-... sensors in Ex-zones 1, 2, 21, 22 MKR Mounting bracket for round ducts up to Ø 600 mm Kit 2 Flexible pressure tube, 2 m, inner Ø 6 mm, 2 connection nipples Kit-S8-CBR 2 cable glands M16 1.5 mm, Ex-e, brass nickel-plated, for cable Ø 5...10 mm Kit-Offs-GL-CBR 2 cable glands M20 1.5 mm, Ex-d, Ms-Ni, for armoured cables CSA Hazardous Location EMPLACEMENTS DANGEREUX This equipment is suitable for installation in Class I, Division 2,! Group A, B, C, D hazardous locations or nonhazardous locations only. CET ÉQUIPEMENT EST SEULEMENT APPROPRIÉ À L INSTALLATION DANS LA CLASSE I, DIVISION 2, GROUPES A, B, C, D DES EMPLACEMENTS DANGEREUX OU DES EMPLACEMENTS NON DANGEREUX. WARNING EXPLOSION HAZARD:! Substitution of components may impair suitability for Class I, Division 2. AVERTISSEMENT RISQUE D EXPLOSION : LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.! WARNING EXPLOSION HAZARD: Do not connect or disconnect this equipment unless power has been removed or the area is known to be nonhazardous. AVERTISSEMENT RISQUE D EXPLOSION : NE PAS BRACHER OU DÉBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, Kit-PTC-CBR 2 connecting tubes for tube fittings Ø 6 mm, stainless steel 316 L À MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DANGEREUX. 2 / 5

Electrical connection All sensors require a 24 VAC / DC power supply. The electrical wiring must be realized via the integrated terminal box acc. to ATEX. Attention: Before opening the terminal box cover, the supply voltage must be shut off! The supply has to be connected at terminals 1 ( / ~) and 2 (+ / ~), the analogue output at terminals 3 (ma / V) and 4 (GND). The optional analogue output at...cos-p-...-a is intrinsically safe. Note the maximum connection values of intrinsically safe parameters (see table below). Display, buttons and parameters Display for programming and indication Push button ENTER RedCos-P-... SB 1.0 24 VAC / DC + ~ ~ Push button for level selection Change operation parametrisation mode To change from operation to parametrisation mode and vice versa, push ENTER button for minimum of 3 seconds. Back to operation mode with menu save. PE (0) / 0...10 V GND ( C / % rh) 1 2 3 4 5 no function PA U m 30 V Indication of data logging A flashing star in the display shows that data is received and the device is working. Password input The default / delivery setup is 0000. In this configuration the password input is not activated. To activate the password protection (menu 20) change the 4 digits into your choosen numbers (e. g. 1234) and press ENTER. Please keep your password in mind for next parameter change! Due to a new parameter setup the password is requested. Intrinsically safe parameters (IS) Internal pressure sensor U o = 7.9 V C i 0 IIC IIB IIA I o = 48 ma L i 0 L o 2 mh 5 mh 10 mh P o = 95 mw C o 1.3 μf 5.8 μf 7.1 μf Internal sensor IS values are corresponding to the internal pressure sensor. Due to the matter of fact that there is no external sensor connected, these IS values are not relevant for the customer but shown for the sake of completeness. Ex-i output (IS) (optional) Female connector 3 1 2 U o = 15.8 V I o = 85 ma P o = 336 mw C i 0 L i 0 Zero point compensation 4 RedCos-P-...-A Connector and terminals SB 3.1 Male connector 4 1 3 2 5 + to connect e.g. an external LCD indicator (IS) Intrinsically safe parameters (IS) Analogue Ex-i output IIC IIB IIA L o 2 mh 5 mh 10 mh C o 0.33 μf 1.6 μf 1.8 μf...cos-p-... pressure sensors are equipped with a zero point compensation to adjust the module to the installation position. The pressure nipples P+ / P must be connected with a short circuit tube and the zero point compensation performed by following the menu for parametrisation (menu 18). Before starting the zero point compensation, the device should be connected to power supply for a minimum of 15 minutes to reach the uniform working temperature! Important information for installation and operation A. Installation, commissioning, maintenance All national and international standards, rules and regulations must be complied with. Certified apparatus must be installed in accordance with manufacturer instructions. If the equipment is used in a manner not specified by the manufacturer, the safety protection provided by the equipment may be impaired. For electrical installations design, selection and erection, EN /IEC 60079-14 can be used. Canada: Install per Canadian Electrical Code (CEC). USA: Install per National Electrical Code (NEC).! Attention: Apply all Ex rules and regulation before opening the internal terminal box. Do not open cover when circuits are live! Draw the wiring cables through the cable glands. For connection use the internal Ex terminal box and connect equipotential bonding. After connection install the cables in a fixed position and protect them against mechanical and thermical damage. Close all openings and ensure IP protection (min. IP66). Avoid temperature transfer and ensure not to exceed max. ambient temperature! For outdoor installation a protective shield against sun, rain and snow should be applied. After mounting and installation a zero point compensation must be done to ensure correct measurement results (see description). Sensors are maintenance free. An annual inspection is recommended. For electrical installations inspection and maintenance, EN / IEC 60079-17 can be used. Clean with damp cloth only. Ex sensors must not be opened and repaired by the end user. B. Long cabling We recommend using shielded signal wires and to connect one end of the shield to the...cos-... terminal box. C. Separate ground wires For supply and signal wires use separate grounds. 3 / 5

RedCos-P... Parametrisation and commissioning To change from operation to parametrisation mode push the ENTER button for minimum 3 seconds. If password protected: type password and push. Back over to menu Save and exit. Operation Parametrisation push for min. 3 s Menu Function ENTER Indication Select ENTER Next indication Select ENTER Next menu Menu 1 DE, EN, FR Select language: German, English, French Menu 2 DE, EN, FR English Deutsch, English, Francais Example: Menu language Range Ex-i English 25...+25 Pa Menu 3 Menu 4 Unit sensor Select physical unit Menu 5 Range Adjust the measuring range Menu 6 unit sensor Pa Pa, mbar, inh 2 O range 25...100 Pa range 25...25 Pa Menu 7 Menu 8 Menu 9 Menu 10 Menu 11 V, ma Select output signal as V or ma range Adjust output range Sensor error Select signal at sensor error Select signal output behaviour output V / ma ma V, ma output range sensor error 10 V / 20 ma 10 V / 20 ma or 0 V / 0 ma output increasing increasing, decreasing output range Menu 12 Menu 13 Menu 14 Menu 15 Menu 16 Menu 17 Ex-i (option, only at...cos-p-...-a) Select lower output signal: 0 ma resp. 4 ma (0...20 or ) output Ex-i output Ex-i Menu 18 Menu 19 Menu 20 Zero point compensation After short circuit the pressure nipples P+/P the sensor gets a zero point calibration Display function Select display settings Password Select password protection set zero point yes no display function on illuminated on, on illuminated, off new password yes no password 0000 Menu 21 Menu 22 Save and exit Select: save data, factory setting, discard or back to menu Set offset Add / subtract offset from measure value save and exit save data save data, factory setting, discard, back to menu set offset 0.00 Pa Menu 23 Menu 24 Attenuation Damping the output signal (signal filter) attenuation 0 4 / 5

Dimensions [ mm ] Aluminium housing...cos-p...-oct 68 80 107 181.7 2 4.5 Ø 4.5 102 59 21.5 182.7 213 123.3 ~ 194 ~ 226 157,5 166 ~ 180 170 117 138 66 55 Stainless steel housing...cos-p...-ova 69 81.3 126.3 ~ 61 70 Approbations ATEX directive 2014 / 34 / EU EC type-approved EPS 14 ATEX 1 656 X IECEx certified IECEx EPS 14.0023X Approval for gas II 3 (1) G Ex nc [ia Ga] IIC T6...T4 Gc Types...-CT,...-OCT II 3 (1) G Ex nc [ia Ga] IIB T6 Gc Approval for dust II 3 (1) D Ex tc [ia Da] IIIC T80 C...T130 C Dc IP66 CE identification CE 0158 EMC directive 2014 / 30 / EU Enclosure protection IP66 in acc. with EN 60529 CSA 13.2672226 Aluminium housing RedCos-P... (not...-a and...-ct,...-oct types): Class Division Class I, Division 2, Groups ABCD, T6, IP66 Ex na IIC Gc Class Zone Class I, Zone 2, AEx na IIC T6 Gc, IP66 (not...-ct,...-oct types): Class Division Class I, Division 2, Groups ABCD, T6, IP66 Ex na [ia Ga] IIC Gc Class Zone Class I, Zone 2, AEx na [ia Ga] IIC T6 Gc, IP66 Types...-CT,...-OCT... Ex na... IIB Gc, IP66 EAC TC RU С-DE.ГБ08.В.01510 5 / 5