ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Similar documents
Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

4-Day Power System Analysis, Coordination, System Studies

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Tolerance-Based Time-Current Coordination

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Transformer Protection

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Selective Coordination

Presented to the IAPMO Standards Review Committee on December 9, 2013

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

ECET Distribution System Protection. Overcurrent Protection

Evaluating Selective Coordination Between

FUSES VERSUS CIRCUIT BREAKERS FOR LOW VOLTAGE APPLICATIONS

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Shippensburg University

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

January 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.

Protective Device Coordination ETAP Star

CONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT

Electrical Safety and Overcurrent Protection

Zone Selective Interlocking

Arc-Flash Mitigation Technologies. Dennis Balickie

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke

Medium Voltage Controllable Fuse

Advanced Protective Relay Training

EE 741 Over-voltage and Overcurrent. Spring 2014

Future Proof Your Arc Flash Assessment

KD LV Motor Protection Relay

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY

Understanding Arc Flash Hazards. White Paper

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

Compact Circuit Protector (CCP) Application Note

FUSE: SAFE & RELIABLE

Selective Coordination Enforcement:

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

Recommended Procedures

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

Pretest Module 29 High Voltage Unit 1

ANALYSIS OF OVERCURRENT PROTECTION RELAY SETTINGS OF A COMMERCIAL BUILDING NURUL SYAQIRAH BINTI MOHD SUFI UNIVERSITI MALAYSIA PAHANG

Selective Coordination Compliance Methods for Evaluation and Mitigation

Use of switch-fuse combinations at the medium-voltage level for the protection of distribution transformers siemens.com/tip-cs

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

PREVIEW ONLY - FULL COPY AVAILABLE TO CONSORTIUM MEMBERS. Escalator Specific Electrical Systems. Course 209 PARTICIPANT GUIDE

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Circuit breaker interlocking and operation requirements SIEMENS

Zone Selective Interlock Module. For GE Circuit Breakers

A. Submit manufacturer's literature and technical data before starting work.

Power systems Protection course

TERMS AND DEFINITIONS

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

3.2. Current Limiting Fuses. Contents

CONTROLLING AND DISTRIBUTION PANELS FOR HAZARDOUS AREAS AND THE TECHNOLOGY DEVELOPMENT OVER THE LAST 40 YEARS

Sales Application Engineering Europe & Russia. Application Engineering Training. Course description and Curriculum

Electrical safety and reliability: Selective coordination. Protect with selective coordination

Arc flash hazard mitigation

Industry Automation Control Components

SECTION MOTOR CONTROLLERS

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Item 1: Contents of the complete training & CV of the lecturer

Don t Discriminate: The importance of selective coordination in electrical installations

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Alternator protection, part 1: Understanding code requirements

Application Note. Common Bussing AC Drives. For 650 and 690+ series drives APP-AC-03

Horizontal Circuit Switchers

Specification made simple for selective coordination in a compact size

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Design Standards NEMA

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

Miniature circuit breaker Application guide

Low Voltage Fuses For Motor Protection

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

Short Circuit/Coordination & Arc Flash Study Specifications

Modular Standardized Electrical and Control Solutions for Fast Track Projects

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

TIME REQUIREMENT GUIDE (TRG)

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

Variable Frequency Drive Basics

Transcription:

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy ETAP 17 Goodyear, Suite 100 Irvine, CA 92618 White Paper No.001.14-2016 Albert Marroquin, PE Member IEEE Principal Electrical Engineer Dynamics and Arc Flash Division Manager Mandar Manjarekar Member IEEE Senior Power Engineer Control System Department Manager Abstract: This white paper provides a comprehensive discussion of the modeling of Mersen s medium voltage controllable fuses (MVCF) in ETAP. Two simulation techniques and their incident energy mitigation benefits are presented. Some important considerations in system configuration, protective device coordination, and application are also included. Key Words: Medium Voltage Controllable Fuse, Mitigation techniques, ETAP, Fuse protection, MVCF, 1 INTRODUCTION The use of electrical fuses has been used in the industry to protect electrical system, people and equipment for over 150 years. Medium voltage fuses used for transformer primary protection have successfully fulfilled system protection concerns by isolating fault current from the equipment. Arc faults on the transformer or equipment supplied by the transformer may yield low current magnitudes (in particular with respect to the primary side of the transformer). Such low currents often cause long fuse clearing times. Some of these clearing times may exceed 2 seconds. The end result of such long clearing times is a high incident energy value (typically over 40 cal/cm²). Medium voltage controllable fuses can overcome some of these problems since they can be configured to maintain coordination and still operate in a relatively low clearing time when compared to conventional E- type fuses. The typical application of a MVCF device is to install a secondary current relay which controls the operation of controllable fuse actuator module which bypasses the current into a high speed current limiting fuse. There are two methods which may be used to model MVCF devices in ETAP. 1.1 Method 1: As an external relay interlocked to operate contactors. 1.2 Method 2: As a medium voltage current limiting fuse. Either method can be used to simulate normal and maintenance mode of operation. Their advantages/disadvantages are discussed in the conclusion section later in this paper. 2 PRIMARY FUSE PROTECTION ISSUES In this example, before presenting the implementation of the MVCF device in ETAP, a few application concepts need to be discussed first. Figure 1: Switchgear with no MVCF. The system described in Figure 1 shows a 480V switchgear where an incident energy calculation performed showed incident energy exceeding 40 1

cal/cm². The primary transformer protection is an E-rated fuse selected based on the transformer protection criteria. Figure 2 shows the time current characteristic curve for the system of figure 1. It can be easily noted that for an arc fault anywhere in the secondary of the transformer and/or main protective device (optional in some designs) that the clearing time of the fuse will be in the seconds range. This is caused by the very inverse characteristic of the primary side fuse. Figure 3: MVCF Diagram The E-rated fuse is present and will protect the transformer against overload conditions and primary faults, but the MVCF device will operate much faster under short-circuit or arc fault conditions. Figure 5 showed the normal mode of operation which significantly reduces the incident energy level at the line side of the main switchgear breaker from 40+ to approximately 14 cal/cm 2. Figure 2 Time Current Curve for LV System 3 MVCF MODELLING TECHNIQUES 3.1 MVCF ETAP Implementation-Method I The basic goal of the MVCF device is to mitigate incident energy and reduce equipment damage. Figure 3 shows the actual implementation and components needed to implement the MVCF. Figure 4 shows how these components would be modeled in ETAP by using a current transformer, overcurrent relay with multiple OC levels and a normally closed bypass switch. In figure 5, it can be observed that the 50P OC relay level is set to operate the bypass at the required time delay (for coordination with downstream devices). A 51P OC level is used to simulate the CLF fuse total clearing time. Figure 4: Method I-Modelling MVCF as an external relay in ETAP 2

3.2 MVCF ETAP Implementation-Method II In this approach, (Figure 7), the MVCF is modelled as an actual fuse and it is coordinated to isolate secondary side faults while continuing to provide coordination with downstream elements. It is modelled in such a manner that it will block any current below 100A and anything above 1000A will be cleared by the main fuse. Figure 5: Time Current Curves of Controlled Fuse with 200 ms delay. If further incident energy mitigation is required, a maintenance mode may also be implemented using the MVCF device. The maintenance mode can be modeled in ETAP by adjusting the instantaneous and overcurrent levels down to very low pickup values which are enabled only during energized work. The resultant incident energy is much lower (approximately 3 to 4 cal/cm 2 ). Of course, just like with any maintenance mode incident energy mitigation technique, coordination is compromised during the time energized work is taking place. Figure 6 shows the TCC of the same system with the maintenance mode enabled. Figure 7: MVCF Implementation with Fuse Curves Figure 8 shows how the MVCF device is modeled as a TCC fuse curve. There are no calculation differences expected from ETAP arc flash when modeling the device using method I or II. The total clearing time of the fuse (upper fuse curve edge) is used by ETAP to calculate the total incident energy. The energy released at the line side of the main secondary protective device is still expected to be approximately 14 cal/cm 2 since both methods are equivalent. Figure 6: Method I :MVCF with Maintenance Mode 3

Figure 8: Method II- MVCF Fuse TCC Similar to method I, to implement maintenance mode, a second fuse curve can be activated by means of the ETAP revision tool. The revision tool allows the selection of an infinite number of TCC curves for the same device. Figure 9 shows the MVCF curve activated in an ETAP revision. This is a nice feature which allows the simulation of this device without having to insert a third fuse into the diagram. methods. Both methods yields the same results but have slightly different application advantages in ETAP. Method I advantages are: ETAP Sequence of Operation (both for shortcircuit and arc flash simulations) can graphically simulate the operation of the bypass switch and fuse. This provides rich graphical instructional simulation of the actual MVCF operation. Another advantage is that no multiple sizes or elements need to be entered. Relays in ETAP can easily be adjusted to different delays and pickup values. Both normal and maintenance modes can be simulated with the same device. Only disadvantage may be the more complex modeling requirements of an adjustable relay with multiple OC levels (50/51 OC levels). Method II advantages are: Simpler to model. Data entry of points to represent the MVCF is far simpler than that of modeling the relay. Figure 9: Method II :MVCF Maintenance Mode Fuse TCC Implementation In both methods, switching to maintenance mode removes the additional coordination time delay but effectively reduces the incident energy to 3 to 4 cal/cm 2. Disadvantages are that for each adjustment, a new fuse size needs to be created in the library. The same is true for normal and maintenance modes. At least two different fuse curves are needed in the library to model both modes. For different sizes and continuous current ratings, the number of elements in the library may be significant. 4 PERFORMANCE ANALYSIS Several arc flash simulations were used to evaluate the performance of the MVCF. This section presents a quick comparison of the incident energy mitigation benefits when applying the MVCF under two configurations (normal and with maintenance mode enabled). Note no difference is expected in the results of table 1 when implementing the MVCF device in ETAP using either method I or II. Table 1: Comparison of Incident Energy Results Equipment Configuration I.E. (cal/cm²) E-RATED FUSE (No MVCF) ~40 + MVCF NORMAL (Method I or II) ~14 MVCF MAINT. (Method I or II) 1~2 5 CONCLUSION Mersen s medium voltage controllable fuse can be effectively simulated in ETAP using two 6 REFERENCES The following documents were consulted during the creation of this white paper: [1] IEEE Standard 242, IEEE Buff Book, IEEE- 1986 [2] Mohla, D.C; Driscoll, T.; Hamer, P.S---- Mitigating electric shock and arc flash energy a total system approach for personnel and equipment protection. [3] Mersen Tech topic Arc Flash Note 7 issue 1--- - Using a Medium Voltage Controllable Fuse to mitigate arc flash energies on low voltage switch gear [4] IEEE Standard C37.46, Standard for High-Voltage expulsion and Current-Limiting Type Power Class Fuses. 4

7 Authors Albert Marroquin: Arc Flash product manager at ETAP. IEEE 1584 member and NFPA 70E Electrical Branch Member. Over 15 years experience in arc flash analysis and simulation software design. Mandar Manjarekar: IEEE member and Senior Power Engineer at ETAP. 8 Appendix A- ETAP Model Setup Sample MVCF implementation model and library files used are attached with this paper. http://etap.com/qualityassurance/documentation/mvcfmersen.zip 5