Investigation into UK socket-outlets incorporating USB charging points

Similar documents
Australian/New Zealand Standard

AS/NZS :2016. Grid connection of energy systems via inverters AS/NZS :2016. Part 1: Installation requirements

Understanding BS 1363 Amendment No.4

AS/NZS 3112:2004 AS/NZS

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

Counterfeit and imitation Apple chargers 98% Safety Test Failure Rate

INTERNATIONAL STANDARD

AS/NZS 3131:2001 AS/NZS

Reviewed: DD Month University Code of Practice for Electrical Safety. PART B - Design and Construction of Electrical Equipment within the University

The Impact of the 18 th edition (BS 7671:2018)

CHAPTER 2: ELECTRICAL SAFETY

TECHNICAL SPECIFICATION

Presented to the IAPMO Standards Review Committee on December 9, 2013

BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012

INTERNATIONAL STANDARD

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

Unified requirements for systems with voltages above 1 kv up to 15 kv

With Compliments PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : : 1006

Household appliances. Terje Ulsrud. 12 June 2018

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas

THE HEARTBEAT B E H I N D T H E HEARTBEAT MEDICAL POWER BROCHURE

Renewable sources of electricity a brief overview

TEST REPORT IEC Part 1: General requirements for basic safety and essential performance

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

FINAL-ER 42 Electrician Regulations Answer Schedule

EARTHING YOUR QUESTIONS ANSWERED

1.Safe testing IMPORTANT:

Element C8.3 Installation, Use and Inspection of Electrical Systems

TEST REPORT. NO.: A001T Date: Jul 29, 2014 Page 1 of 7

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)

Photovoltaic Solar Plan Review

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

Ensuring the Safety Of Medical Electronics

TECHNICAL SPECIFICATION

BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY. (Not to be reproduced without the permission of BIS or used as a STANDARD) Draft Indian Standard

2012 IECEE CTL PTP Workshop. Ingrid Flemming IFM Quality Services Pty Ltd

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles

Key elements of the AS3000 Wiring standards and some of the recent changes.

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

Books. Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication

Maharashtra Electricity Regulatory Commission (Renewable Purchase Obligation, Its. Regulations, 2016 STATEMENT OF REASONS

ENGINEERING SPECIFICATION

ES5 Security Theory/Regulations Answer Schedule

This standard covers the requirements of lighting chains. This standard covers only the safety requirements.

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Australian/New Zealand Standard

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017

Major changes within the New 18 th Edition Wiring Regulations announced by The IET

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

FAQ S. Main Switchboard Design Criteria. ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)

SPECIFICATION AND PERFORMANCE TABLE OF CONTENT. 1. Scope Reference Documents Material and Components... 2

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

COMMISSION REGULATION (EC)

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Electrical Awareness and Considerations

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY

Status of the Informal Working Group on ACSF

DEPARTMENT OF TRADE AND INDUSTRY NO APRIL 2016

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

Small craft Electric propulsion system

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Consumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations

Test Report No. 55S071315/ZHY/PKS dated 10 JUL 2007

S T A N D A R D. Copyright American Society of Agricultural and Biological Engineers. All rights reserved.

Regulation No Uniform provisions concerning the approval of replacement pollution control devices for power-driven vehicles

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE

AS/NZS :2013. Wheelchairs AS/NZS :2013. Australian/New Zealand Standard

Australian/New Zealand Standard

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

Earthing Principles. Symmetra PX 250/500 kw

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )

045 : 2000 CEB STANDARD

Professional Wireless Products

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

Electric Vehicle Charging Safety Guidelines Part 1: Safety Fundamentals Edition DRAFT

Applying Interrupting Rating: Circuit Breakers

LED Emergency Luminaires

SOUTH AFRICAN NATIONAL STANDARD. Plug and socket-outlet systems for household and similar purposes for use in South Africa

2016 Photovoltaic Solar System Plan Review List

TRANSMISSION SYSTEMS

Applying Interrupting Rating: Circuit Breakers

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Test Report No EEC12-03/MLM dated 27 MAR 2012

REPORT NO INSPECTION, TEST AND EVALUATION OF. Interlock Kits SUBMITTED TO MASTER ELECTRICAL SERVICES 3107 LANVALE AVENUE RICHMOND, VA 23230

NCSA 20plus Service Manual

WIRING MATTERS SEPTEMBER 2018

PROJECTS $500K AND OVER FOR 2014

EMERGENCY ONE-LED TM SOLO TM NON MAINTAINED LED LAMP AND DRIVER KIT

FAQ s. Are you AS/NZS Ready?

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

POWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012

Session Four Applying functional safety to machine interlock guards

V1606 3U RACK ENCLOSURE

COUNCIL OF THE EUROPEAN UNION. Brussels, 11 December /3/06 REV 3 ADD 1. Interinstitutional File: 2003/ 0153(COD) ENT 84 CODEC 561

Transcription:

Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of its investigation conducted in 2014. This was done for two reasons to see if the quality and safety of the products had improved, particularly in light of the arrival of larger manufacturers onto the market, and to see if the products are capable of meeting the recently introduced standard requirements regarding socket-outlets incorporating USB charging points. As part of a comprehensive revision of the BS 1363 series of standards, Part 2 - Specification for 13 A switched and unswitched socket-outlets published in August 2016 now includes in its scope Socket-outlets incorporating electronic components, including USB circuits intended for charging portable devices. A new annex in the standard sets out the conformity criteria for USB circuits - referencing existing component standards - and further specifies particular requirements to deal with the safety of incorporated components into socket-outlets. While the previous edition of BS 1363-2:1995+A4:2012 remains current until its withdrawal in August 2019, manufacturers are encouraged to use the revised 2016 edition with immediate effect to ensure their products remain state of the art and constructed in accordance with principles of good engineering practice. As with the 2014 study, the primary safety concern is that such products could pose a risk of electric shock or fire if the extra-low-voltage parts of the USB power supply are not sufficiently segregated and separated from the low voltage (240V) parts of the product or from the fixed wiring installation of the property in which the product is installed. As previously stated, socket-outlets incorporating USB ports are now covered within the scope of BS 1363 Part 2, but it is recognised that the new USB requirements were in draft form at the time of this investigation and by and large unknown to many manufacturers. However, the samples selected for screening were all readily available on the consumer market, and as such, would need to meet the essential safety requirements of the Electrical Equipment (Safety) Regulations, primarily by conformity to applicable and current safety standards. For this exercise, nine different products from different manufacturers were chosen, ranging from a completely unbranded socket outlet to well-known industry leaders.

Overall Summary of Testing Key: F = Fail, P = Pass, IR = Partial Fail / Improvement Recommended Test Criteria 1 Markings, labelling & instructions Sample Number A B C D E F G H J IR IR IR IR IR F F IR F 2 Construction P P P P P F F P F 3 Accessibility of live parts 4 Terminals & terminations 5 Internal wiring / separation 6 Screws, current carrying parts & connections 7 Creepage distances, clearances & distances through insulation 8 Overcurrent & earth fault protection P P F P P P F P F P P P P P P P IR F F P F P F F F F F P P P P P P P P F P P F P F F F F F P P P P P P P F P 9 Mechanical strength P P P P P P P IR P 10 Insulation resistance / P P P P F P P F F electric strength./ leakage current 11 Provision for earthing P P P P P P P P F 12 Output voltage, no load F F F F F F F F F & under load (Not a current requirement) Total Failed Criteria 3 2 5 2 4 5 6 6 10 Of the socket outlets tested, the unbranded socket outlet (J) performed the worst, only passing two of the 12 criteria. Many of the branded products failed to meet all the test criteria in our screening, including the new markings requirements, and every socket-outlet tested failed to meet the required USB output voltage range required by BS EN 62680-1-1 for dedicated charging ports. The best performing sockets were samples B and D, which are products from major manufacturers.

Overall, the results are concerning with three of the sockets tested failing due to accessible live parts, and 7 (77%) of the sockets failing due to inadequate internal wiring and insufficient separation, with some samples failing on this count due to the use of solder alone for both mechanical and electrical connection, and one sample (the most expensive) failing due to completely inadequate separation between the mains input and USB output just 1.74mm against a required 4mm. In detail criteria discussed: Marking, labelling and instructions (Clause 7 & Annex I of BS1363-2) Visual inspection of the purchased products revealed that this was the most common failing, with none of the products meeting the criteria adequately in terms of existing and the new requirements. However, six of the products only partially met the requirements as some of the required markings were not visible once installed correctly. Construction (Clause 13 of BS1363-2) Image above: Detail of markings on rear of sample Three products failed this criteria, with two on the grounds of failing to meet the required dimensions for the pin apertures. Sample J, however, was found to have poor construction throughout, to the extent that the product did not allow sufficient space for the required fixed wiring, potentially making the product impossible to install safely.

Images above: Details of internal arrangement of two samples, showing the great difference in design and construction across the sample range. Accessibility of live parts (Clause 9 of BS1363-2) Three of the products failed this criterion with live internal parts being contactable through one or other of the socket outlet apertures with the specified test probes, with sample J being found to have accessible live parts on both of the double sockets. Image above: Unbranded sample J undergoing testing for access to live parts Terminals and terminations (Clause 11 of BS1363-2) The overall worst performer, sample J, was the only product to fail this criteria outright, due to poor design obstructing the earth terminal fastening. Sample H is recorded as a partial failure as during operation the terminals distorted. Internal wiring / separation (BS EN 60950-1:2006) Seven of the samples failed this criterion, with only samples B and D passing. The most common failures were the reliance on solder only for mechanical and electrical connection

and breaches of the isolation barrier. Sample J was again one of the worst example, with basically insulated secondary wiring being in direct contact with the capacitor cases in the primary circuit, and the primary capacitor was so poorly positioned that it could make direct contact with a USB output connector. Image above: Detail of sample showing distance between busbar and transformer core Screws, current carrying parts and connections (Clause 21 of BS1363-2) Only sample J failed this criteria, reflecting the overall poor quality of this product, with the design relying on the plastic enclosure for maintaining contact pressure. Creepage and clearance distances through insulation (BS1363-2, Clause 8, BS EN 60950-1 Clause 2.10)) As electronic circuits rely upon insulation and/or physical separation to prevent the risk of electric shock, excess heat and/or fire, the laboratory checked that the components, including the transformer and the conductive tracks of the PCB, complied with the safety requirements set out in the product standards. Six of the samples failed this test, on the same grounds of failure found when testing the internal wiring and separation distances. Overcurrent and earth fault protection in primary circuits (Clause 1.3.2, Annex I of BS1363-2) Only one product failed this criteria, sample H, as the protection in place did not appear to operate during testing, leading to the external surface of the product reaching a recorded temperature of 80 C, exceeding the maximum permitted temperature rise of 52 K. Mechanical Strength (Clause 20 of BS1363-2) All samples passed, with one recorded as improvement recommended as the casing had cracked during a previous test, making a full mechanical strength test impossible. Insulation Resistance / Electric Strength / Leakage Current (Clause 15 and Annex I clause 1.3.2.2 of BS1363-2) Samples E, H and J failed this criteria, whereby an electric strength test was carried out between the Line and Neutral terminals and the output of the USB circuit, which is required

Conclusion to have double or reinforced insulation. In all three cases a flashover occurred after 1 second at levels between 2600 and 2900V, which indicated a breakdown of the insulation. Provision for earthing (Clause 10 of BS1363-2) The worst overall performer, sample J, was the only product to fail this criteria, with no connection being detected between the earth terminal and a plug pin inserted in the opposite socket-outlet. The resistance between the earth terminal and plug pin was also found to be far in excess of the maximum allowed. Output voltage, no load and under load (Clause 4.4 of BS EN 62680-1-1) All samples failed this performance test, with output voltages measured and found to be outside the required range. As is clear from the results of this limited investigation and its predecessor, several safety risks and other non-compliances are present in socket outlets incorporating USB power supplies. In particular it should be noted that based on the selected samples this was not limited to unbranded or the lower price end of the market. A key point of the results, however, is that many of the issues identified are basic failings with the conventional areas of the socket, rather than limited to the USB port(s), which is of significant concern. As with all our previous product safety investigations, the findings of our research will be shared with the manufacturers and suppliers concerned to make them aware of the nature and extent of the electrical safety failures we have identified. Where deemed appropriate, our findings will also be shared with Trading Standards to assist them with their market surveillance activities and enforcement duties. The laboratory test reports (redacted) will be made available to view in full in the Electrical professionals section of our website.