School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Similar documents
EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

SWITCHBOARDS (LV and MV)

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

Air-insulated switchgear UniGear type ZS1

Pretest Module 29 High Voltage Unit 1

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

Gas Insulated Metal-clad Switchgear, HMGS!

Switchgear and Distribution Systems for Engineers and Technicians

MESG 12 / 17.5 / 24 / 36 KV

Power systems Protection course

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Close-Open (Short-Circuit) Time Results Interpretation

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

NEXT STEP B) SAFETY :

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

COMPACT SUBSTATION GUIDE

Extensible Unit - VCE2a

Medium Voltage Metal-Enclosed Switches

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

UniSafe 36 Product Presentation. ABB Elektrik Sanayi A.S. - Page 1

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

Gas Insulated Switchgear

One-Fit,UFES, Reyrolle LM

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Three days training program (Oct 5-7) on. Substation Earthing, Industrial earthing and Neutral earthing. at IEI Mysore, Karnataka India

HD4. Gas insulated MV circuit-breakers kv A ka

Gas Insulated Switchgear ELK-0. for stations up to 170 kv, 4000 A, 63 ka

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

EMPAC Metal enclosed capacitor bank for wind applications

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

18 Industrial and Commercial P ower System Protection

Horizontal Circuit Switchers

ZX-Family Gas-insulated medium voltage switchgear

The specialist in Medium Voltage

ABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems. Generator Circuit- Breaker Systems

ABB AG - Calor Emag Medium Voltage Products OEM Products Medium Voltage Products. ABB OEM Products 1

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Chapter 6 Generator-Voltage System

B kv Gas-insulated Substations

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Medium Voltage Metal-Enclosed Switches

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

High-voltage high-breaking capacity VV fuse-links

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Advance 27 ANSI 27 kv switchgear

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

SPEN, Rasmus Larsson, High Voltage Breakers Innovative breaker solutions Substation design

Metal Clad Switchgears

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

MAGNETIC MOTOR STARTERS

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Safe, fast HV circuit breaker testing with DualGround technology

Substation Committee K2 TF1 of the GIS Subcommittee GIS/GIL/SF 6 -Tutorials

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K Catalogue EN

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

Substation Concepts for the Future

Power IT Air Insulated Cubicle Uniswitch

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.

OHB Outdoor sulphur Hexafluoride circuit-breaker

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group April 17, 2009 Slide 1

PASS M0. Innovative solutions for distribution substations up to 170 kv

Small wonder. Station service voltage transformers for small power requirements

Pankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers. Technical Seminar: PLN

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

Circuit Breaker Prepared By :

Unitole UP kv Primary substations Motor control centres

123/145kV SF6 Gas-Insulated Switchgear incorporating VCB. 145kV-1250~2000A-31.5kA

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram:

Unitole UP kv Primary substations Motor control centres

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group May 15, 2013 Slide 1

UniGear. Technical Guide

Accelerate your grid modernization with smart RMUs. Ring main units with smart grid-ready feeder automation

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Vacuum Generator Circuit Breaker - A trend-setting power plant technology

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

Distribution transformers Efficiency over life-cycle

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

Standards, Procedures and Policies for Grid Connection

ZX2 Gas-insulated medium voltage switchgear

Transcription:

University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering

ELEC 5205 - High Voltage Engineering 3. Switchgear

Types of Power System Switchgear Only fuses and circuit breakers are designed to interrupt shortcircuit currents Source: ref 2

Source CT and VT Connection To load

Circuit Breaker and Relay Wiring Schematic (1 of 3 phases) Source: Ref 1

Power System Protection Relays Power system protection relays accept signals representing the fault current and voltages (derived from measuring transducers known as current and voltage transformers) and then analyse these signals and send a trip signal to a circuit breaker if an abnormal condition is detected. The main types of relays are (for short-circuits): Over current Distance (impedance) Unit (differential) Other relay types are Thermal, over and undervolts, Buchholz, neg ve sequence, etc

Protection Relays and Circuit Breakers Upon detection of a fault, protection relays provide the trip signals for the circuit breakers. These are switching devices designed to be able to carry and interrupt safely the often very high currents, which flow during faults. Modern high capacity circuit breakers are capable of interrupting currents of up to 60 000 amps at a nominal voltage of 750kV within 40 milliseconds. The purpose of the circuit breakers is To disconnect the faulty element or circuit, leaving the rest of the power system intact To prevent other healthy equipment from being damaged by the fault currents they must carry. To reduce damage at the point of fault, important because the less damage caused by the fault the greater the probability of successful repair.

Circuit Breaker Ratings Rated load current the normal load current it can carry indefinitely without thermal damage Rated voltage the rated voltage it can withstand indefinitely without insulation breakdown Breaking current the short circuit current it can safely interrupt without damage Making current the maximum short-circuity it can close onto (assuming an upstream device can interrupt the current) Eg 630A, 11000 volts, 21 ka Load current Rated voltage Breaking current

Steady-State or Asymmetric Current? Transmission system protection is designed to clear faults very quickly (sub-second), so asymmetric current is relevant Distribution system protection is often much slower and transients have usually decayed away - so steady state may be more applicable.

Fully Offset Fault Current

Calculation of Fully Offset Fault Current Source: ref 2

Short- Circuit Equiv Cct Source: ref 4 The total source and line R and L will determine the DC transient time constant τ = L tot /R tot

CB Symmetrical Interrupting Capability For CBs < 120 kv, a proportionally higher breaking capacity may be possible at reduced voltages ( K factor)

Circuit Breaker Fault Clearance

Circuit Breaker Fault Clearance.. 2

Current Choppin g

Circuit Breaker Types OIL Oil is vaporised and gas extinguishes arc Old technology maintenance intensive Explosion and fire risk AIR Arc shute designed to lengthen arc and extinguish Used for LV <1100V Air-Blast High pressure air extinguishes arc Used for HV AC and DC SF 6 Low maintenance. Soft switching Gas disposal issue VACUUM Maintenance free. Suitable for MV < 36kV Hard switching voltage transients Can t monitor vacuum condition

330 kv Switchgear - TransGrid Liverpool 330/132kV Substation 330kV busbars 330kV CTs 330kV Air-Blast CBs

132 kv Switchgear - Energy Aust 132kV Substation 132 kv low oil volume CBs The author in front gives an idea of size at these sorts of voltages.

HV, MV and LV CBs Voltage very much dictates size and type of circuit breaker Low Voltage >120 V and < 1.1 kv AC - Encased, Air CBs are the main type Medium Voltage > 1.1 kv and < 52 kv - Vacuum (<36 kv) and SF6 main types. - Many designs are indoor High Voltage > 52 kv - SF6 the main design. SF6 GIS switchgear up to 400 kv now available for indoor applications - Oil, low volume oil, and air-blast older types for high voltage.

Typical CB Ratings 120 kv Load 800-2000 A; S/C 12.5-40 ka 300 kv Load 1250-3150 A; S/C 16-50 ka 800 kv Load 2000-4000 A; S/C 40 ka

Oil CBs

SF 6 CB - Operation Source: ref 4 Arc quenching process in a puffer type SF6 CB

SF 6 Dielectric Properties Source: ref 4 SF 6 is a heavy largely inert gas and has superior dielectric and arc quenching properties compared to air and oil. Most SF 6 switchgear operates at a pressure of about 5-6 bars.

Source: Ref 4 Air-Blast CBs

Source: Ref 4 LV Air CBs

LV Magnetic Arc Extinction Source: Ref 4

Vacuum CBs Becoming very popular for voltages up to about 15 kv (eg motor contactors). Basically maintenancefree. Issues with hard arc extinction (current chopping) and

Indoor or Outdoor? Originally, most switchgear, right down to 11 kv, was placed outdoors, designed for use with aerial busbars, for both technical and cost reasons, especially at high voltages. The advent of SF 6 gas insulation has enabled the use of switchgear to 400 kv indoors. Inner city substations use indoor gear for aesthetic and space-saving reasons. Indoor subs may cause earthing design problems - why?

Source: ref 4 Outdoor CBs

Source: ref 4. A 440 kv packaged substation. The CBs are in the front and busbars at the rear. An incoming circuit is on the top right. HV GIS Switchgear

Other CB Design Issues Insulation level - set by system BIL Transient voltage withstand - 3 phase CBs do not open all 3 poles precisely at the same instant - over-voltages of ~1.5 times on other phases may occur.

CB Maintenance Traditional CB maintenance has been based on duty cycles - so many switching operations, so many fault clearing operations, etc. Normally minor maintenance interwoven with major maintenance. The latter involving complete stripping down of gear, and replacement of contacts. Newer concepts based on condition monitoring.

Condition Monitoring Refers to the actual amount of wear and tear a CB has experienced, and using this to determine the timing and nature of next CB maintenance. Uses sensors and microprocessors to log actual operational behaviour. Vibration analysis to monitor wear of CB contacts and operation mechanisms Oil analysis to determine amount of carbonisation caused by arcing, etc.

Switchgear Testing Manufacturers tests - R & D testing, type testing Commissioning tests - voltage pressure tests, tripping/closing tests, dielectric tests, etc Routine maintenance tripping tests.

Substation Layouts - Full Mesh Source: ref 4. Used on HV transmission substations where deliberate redundancy in current paths ensures maximum reliability.

Substation Layouts - Breaker and Half

Substation Layouts - Simple Single Bus NB: The X s are CBs and the switches are isolators.

HV Switchyard & Earth Grid Source: ref 4. Layout A design for a simple 132 kv sub with one incoming 132 kv feeder and 2 transformer CBs and isolators, and switchroom with the lower voltage side switchgear being indoor. Note the denser earth grid under the switchroom. The earth grid must keep voltage rise due to fault current inflow to acceptable levels.

Earth Grid Resistance

Earth Ground Rod Resistance Source: ref 4 The earth grid resistance will be specified in the substation design (usually < 0.5 ohm). Actual grid resistance tests are done as part of the commissioning tests of a new substation, by direct current injection.

Step and Touch Potentials

Allowable Human Body Currents Electrocution is caused by currents flowing through a body and interfering with the operation of key organs eg lungs, heart Body resistance varies with voltage and dryness Up to 900 ma acceptable for very short (<0.05 sec) periods; only 80 ma at 1 second and <50 ma continuous

Allowable Touch Potentials Source: ref 4. For example, for a 1-second fault duration, touch potential should be 60 volts, or less.

Typical Computer Model of Step & Touch Potentials Source: ref 4.

Source: ref 4. Switchyard Spacings

IEC Phase Clearances Source: ref 4.

Source: ref 4. IEC Safe Working Distances