Predator VAV with CO2

Similar documents
TEC Controller Constant Volume - Electronic Output. Owner's Manual Building Technologies

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

Laboratory Room Controller

Operations Manual OM

BACnet PTEC Controller VAV Chilled Beam with Demand Control Ventilation (CO2) and Floating or Analog Output Owner s Manual

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet PTEC Controller Dual Duct Two Air Velocity Sensors. Owner's Manual Building Technologies

Operations Manual OM BACnet VAV Actuator. Group: Applied Air Systems Part Number: OM 1063 Date: February 2015

Appendix A: Inputs, Outputs, and Parameters

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3.

LCM-OAVS Room Pressurization with Slowacting Venturi Air Valves (One Exhaust, One Supply) and Hot Water Reheat Owner s Manual

LCM-OAVS Room Pressurization with Slowacting Damper Actuation (One Exhaust, One Supply) and Hot Water Reheat Owner s Manual

LCM-OAVS Room Pressurization Controller with Fast-acting Damper Actuation (One Exhaust, One Supply) and Hot Water Reheat Owner s Manual

HWS Heater (alternative) Electric Heater Stage 2 IQLVAV Electric Heater Stage 1. , P Serial Fan on/off SUPPLY AIR. Parallel Fan

RDG160TU Commercial Thermostat

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

SE7200 Series Installation Guide

EZvav Digital Controls

STRA-24 for chilled beams

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Modbus Integration Integration for Modbus Functionality for VT8600 Series

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

BACnet Fume Hood Controller Vertical Sash with Damper or Venturi Air Valve and 2-Position Constant Volume with Damper.

SE8300 Series Installation Guide 24 Vac Low Voltage

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Metasys Zoning Package Installation

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Air Quality Solutions

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Proportional Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Digital Room Thermostats with Touch Screen LCD

General Information... 2

Excel 10 W7751H3007 VAV ACTUATOR

Installation, Service, and Troubleshooting Instructions

APPLICATION GUIDE. Simplicity LINC GATEWAY OVERVIEW. 24 must be grounded close to the Simplicity LINC

PIR Ready VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications (Issue Date June 12, _R2)

RC-DO. Room controllers with display and manual forced ventilation function

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals.

SMT-150 Installer Manual

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser

Excel 10 W7751B,D,F,H,J VARIABLE AIR VOLUME CONTROLLER

Air Conditioning Clinic. HVAC System Control One of the Systems Series TRG-TRC017-EN

Fume Hood Controller Application 2941 and 2942: Vertical Sash Configuration with Damper or Venturi Air Valve. Start-up Procedures

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

ROOM CONTROLLER STRA-24 TECHNICAL CATALOUGE AND INSTALLATION

Powers TM Controls SW 141 Differential Static Airflow Switches

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals

Temperature Controller (Heat Pumps)

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Ventilation in balance

INSTALLATION INSTRUCTIONS ECOHLX Series Horizontal Economizer and PEHALX Series Economizer with Power Exhaust for York LX Series. Warning.

Distributed Low-Voltage Power System

Description. functions including single duct pressure dependent or pressure independent systems.

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Floating Control

Ventilation in balance

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Polygyr -Compact Exhaust Air Temperature Controller

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

Excel 10 W7751H SMART VAV ACTUATOR BEFORE INSTALLATION INSTALLATION

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

SAX Electronic Valve Actuator

SLIMZONE CLASSIC /

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB

Product Data ZONEKIT4ZCAR. Comfort Zone Residential Zoning System

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

ROOM CONTROLLER STRA-04 TECHNICAL CATALOGUE AND INSTALLATION

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

QUICK START GUIDE VAV CONTROLLERS & WALL SENSORS rue Charles, Suite 100, Mirabel, QC, J7J 1X9

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

STR Circular VAV Terminal Units

Variable Air Volume (VAV) Pressure Independent Control

Powermite 599 MT Series SQS Electronic Valve Actuator, 24 Vac, Floating Control (3-position)

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Optimal Start Time: Precool and Preheat

Powers TM Controls EA 338 Electronic Actuator

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

YCCS TE-6800 Series Temperature Sensors

HVAC Products. Introducing the SED2 Variable Frequency Drives

CP-VL6436A, CP-VL6438N, CP-UL6438 ComfortPoint Programmable, VAV/Unitary Controllers

BAS Construction Checklist

Laboratory Room Single Duct Supply Air Terminal

BT300 Variable Frequency Drives. Redesigned, re-tooled, and ready to meet rigorous demands.

ELECTRONIC THERMOSTAT: T901

Excel 10 W7751J Smart VAV Actuator

GE Measurement & Control

Engineering Bulletin. Recirculation Energy Recovery Unit Controls CLCH-PRB009-EN

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

MicroTech II Applied Rooftop Unit Controller

MicroTech II Applied Rooftop Unit Controller

IAQ. ROUND DUCT RETROFIT Model ARR

MicroTech Applied Rooftop Unit Controller

Dual Duct Variable Air Volume Terminal (Model TDS)

Transcription:

Predator VAV with CO2 Application Data Sheet Predator VAV with CO2 Controller Configuration Features Demand Ventilation Control that adapts to meet IAQ specification requirements Economizer control of outside air damper that provides energy savings LonMark compliant with space-comfort controller functional profile (8502) PID control minimizes offset and maintains tighter set point control to increase space comfort Standby mode enables energy savings during occupied hours for rooms that are not always used. When occupants are sensed, the controller quickly responds to maintain comfort levels. Diversity control, through a demand limit input, maximizes comfort by maintaining even air distribution to all zones during morning warm-up or pre-cool operation. Conforms to the LonMark interoperability guidelines, enabling information sharing with LonMark products from other vendors. Sequence of Operation In this core configuration, the Predator operates perimeter heat, the reheat coil and the primary air damper to maintain required room temperature and ventilation conditions. Occupied Mode The Predator applies occupied settings for the space temperature setpoints and the primary air flow minimum. The typical result is continuous ventilation, with heating or cooling automatically selected to maintain comfort. Cooling The cooling PID maintains the measured space temperature at the occupied cooling setpoint by modulating the primary air flow setpoint between the maximum cooling flow and the minimum cooling flow. Document No. 588-209 Revision CA December 2008

The ventilation PID calculates ventilation demand in occupied mode by measuring the space CO2 and comparing it to the configured CO2 setpoint. The ventilation demand is used by the flow component to generate a primary air flow setpoint between 0 and the configured maximum cooling flow. If both the cooling and ventilation PIDs are generating demand values, then the component with the larger setpoint value will drive the primary air flow PID. The primary air flow PID maintains the measured air flow to the larger of these two setpoints by modulating the position of the primary air damper. The reheat coil is off. Perimeter heat is off. Heating The heating PID maintains the measured space temperature at the occupied heating setpoint by modulating perimeter heat, the reheat coil and the primary air flow setpoint. The setpoint varies between the maximum heating flow and the minimum heating flow. Relative sequencing of perimeter heat, the reheat coil, and the primary air flow is set according to site specific requirements. The ventilation PID calculates ventilation demand in occupied mode by measuring the space CO2 and comparing it to the configured CO2 setpoint. The ventilation demand is used by the flow component to generate a primary air flow setpoint between 0 and the configured maximum cooling flow. If both the heating and ventilation PIDs are generating demand values, then the component with the larger setpoint value will drive the primary air flow PID. The primary air flow PID maintains the measured air flow to the larger of these two setpoints by modulating the position of the primary air damper. NOTE: Ventilation demand will only operate until the temperature falls a configurable number of degrees below heating setpoint. If the temperature falls below this configured value, then the ventilation loop will be disabled, causing the heating PID to be the sole input to the primary air flow PID. Unoccupied Mode The Predator applies unoccupied settings for the space temperature setpoints and the primary air flow minimum. The typical result is a wide operating band with no HVAC energy consumption, and heating or cooling applied only at extreme conditions. Cooling The cooling PID maintains the measured space temperature at the unoccupied cooling setpoint by modulating the primary air flow setpoint between the maximum cooling flow and the unoccupied minimum flow. The primary air flow PID maintains the measured air flow at the varying setpoint by modulating the position of the primary air damper. The reheat coil is off. Perimeter heat is off. Heating The heating PID maintains the measured space temperature at the unoccupied heating setpoint. Operation of each HVAC device, in response to heating demand is selectable in the unoccupied mode. The behavior of primary air damper and reheat coil may be individually configured. They may be forced on, locked out, modulated or cycled according to the required sequence. Page 2 of 13 Document No. 588-209

Bypass Mode During unoccupied periods, an occupant can put the Predator in the bypass mode by pressing the bypass button on the room temperature sensor. This causes the controller to operate exactly as in the occupied mode, for an adjustable amount of time. Standby Mode Standby mode applies separately adjustable temperature and ventilation setpoints. These may be adjusted to conserve energy, but allow quicker recovery compared to the unoccupied mode. Otherwise, operation is the same as the unoccupied mode. Morning Warmup During unoccupied periods, if the Predator is commanded to warmup mode, it applies the occupied heating setpoint (to restore comfort conditions) and the unoccupied minimum flow (because occupants are not present). Operation of each HVAC device, in response to heating demand is selectable in the warmup mode. The behavior of perimeter heat, the primary air damper and the reheat coil may be individually configured. They may be forced on, locked out, modulated or cycled according to the required sequence. Pre-cool During unoccupied periods, if the Predator is commanded to pre-cool mode, it applies the occupied cooling setpoint (to restore comfort conditions) and the unoccupied minimum flow (because the occupants are not present). The reheat coil is off. Perimeter heat is off. Calibrate (Test) The Predator closes the primary air damper and calibrates the air flow sensor. Once commanded to test mode, the controller remains in this mode (even if it is commanded to another mode) until the recalibration is complete. This process takes approximately two times the damper motor travel time. The reheat coil is off. If perimeter heat is active, it continues to operate. Off The Predator closes the primary air damper, and turns off the reheat coil, and turns off perimeter heat. Document No. 588-209 Page 3 of 13

Occupancy Control Occupancy Mode The Predator controller defaults to the occupied mode of operation. Upon receipt of the 4- state LonMark occupancy override (nvioccmancmd), the controller will switch to the appropriate mode of operation. A brief summary of each mode follows below: LonMark Occupancy State Mode Description (0) Occupied Controller in Occupied mode and uses Occupied setpoints. (1) Unoccupied Controller in Unoccupied mode and uses Unoccupied setpoints. (2) Bypass Controller temporarily in Occupied mode and uses Occupied setpoints until the Bypass Time elapses. Controller then returns to previous occupancy state. (3) Standby Controller in Standby mode and uses Standby setpoints. If a LonMark compatible occupancy schedule input (nvioccschedule) is used, the controller will use the modes and setpoints as shown above. This will allow the Predator controller to utilize the scheduling properties of other devices on the LonTalk Network. The occupancy signal could also come from a time clock, wall switch, or occupancy sensor physically wired to one of the inputs of the Predator controller. This occupancy signal could then be shared with other controllers via the Lon Network. Bypass Mode If enabled (through stptdialen) and the Bypass button on the Predator room sensor is pressed, the controller will be placed in the Bypass mode for the amount of time specified by the controller s configuration parameters (default 60 min. see Table 2). If the button is subsequently pressed again prior to the expiration of the Bypass time, the timer will reset to the initial value and resume counting down. Priorities of Occupancy Control Occupancy overrides are prioritized as follows (listed from highest to lowest): Operator Command A valid occupied command sent from system operator. Bypass Button Button on Talon room sensor, also utilized by occupants of room. Occupancy Sensor/Wall Switch Locally connected or signal via the network. Occupancy Schedule Sent from network. Page 4 of 13 Document No. 588-209

Optional Functions Room Temperature Sensor Sharing The Predator Room Temperature Sensor may share its value with other controllers on the LonTalk network via a network binding. This is most commonly done when multiple terminal units serve a room or area. Occupancy Sensor/Wall Switch An optional maintained contact wall switch may be used to control the occupancy mode of a room. Rooms with variable occupancy (conference rooms, etc.) can use this device to control occupancy and the lights with one switch. Another useful option is to utilize an occupancy sensor to control the occupancy mode of the Predator controller. The function of this device would be similar to the wall switch above, but an occupant entering the room would not perform any manual action to put the room into occupied mode. If the schedule is in the occupied mode and the occupancy sensor does not detect people in the room, the room will go into the standby mode enabling energy savings while maintaining occupant comfort. Analog Damper Actuator The standard application is setup to use a Siemens GDE or GLB, or similar 3-point floating actuator for air volume control. Alternatively, A Siemens Open Air TM or similar damper actuator could be utilized if 0-10 VDC modulating control is desired. Perimeter Heat This application also supports the optional control of perimeter heat. The algorithm supports analog, 3-point floating, pulse width modulation, and on/off control of the perimeter heat. Perimeter heat operates independently of terminal airflow or the current state of the terminal fan. Document No. 588-209 Page 5 of 13

Hardware Map VAV with CO2 Sample Hardware Map for the VAV with CO2 Application Configuration Configuration Property instat Inputs outputs Element Input/Output Type Factory Hardware Setting Desired Setting Settings that need to be changed from the factory defaults are shown in BOLD face type. 0 F stattempoffset - 0 F 0 C 0 C statsetptoffset - 0 F 0 F 0 C 0 C stattemp TEMP SPACE_TEMP SPACE_TEMP statsetpt TEMP SPACE_SETPT_OFFSET_TEMP SPACE_SETPT_OFFSET_TEMP statovrd DI STAT_SWITCH_DI STAT_SWITCH_DI IN1 DI, TEMP SPARE2_IN IN_UNUSED IN2 DI, TEMP IN_UNUSED IN_UNUSED IN3 DI, PCT, OCC_SENSOR_DI IN_UNUSED TEMP IN4 DI, PCT, SPACE1_IN IN_UNUSED TEMP IN5 DI, PCT, TEMP SPACE_CO2_PCT SPACE_CO2_PCT IN6 PCT ONBD_PRESSURE_PCT ONBD_PRESSURE_PCT OUTA1 AO FLOW_DMPR_AO OUT_UNUSED OUTA2 AO TRM_H_COIL_AO OUT_UNUSED OUTD1 OUTD2 OUTD3 OUTD4 OUTD5 OUTD6 OUTD7 OUTD8 FLOW_DMPR_ FLOW_DMPR_ TRM_H_COIL_ TRM_H_COIL_ PERIM_H_COIL_ PERIM_H_COIL_ TRM_FAN_DO SPARE1_OUT FLOW_DMPR_ FLOW_DMPR_ TRM_H_COIL_ TRM_H_COIL_ OUT_UNUSED OUT_UNUSED OUT_UNUSED OUT_UNUSED Page 6 of 13 Document No. 588-209

Sample Wiring Diagram for VAV with CO2 Application Configuration Note: Route wiring from either the bottom opening when using a J-box or from the base sides as shown in the picture when flat or din rail mounting. The image above is for illustrative purposes only Wiring Recommendations: IN and AO: DO: Power: LON Network: 20 to 22 AWG 18 to 22 AWG 16 to 18 AWG 22 AWG Level 4 Transformer Requirements: Type: Class 2, 24 VAC, 50/60Hz Predator Wiring Diagrams (Full Point Board Shown) Document No. 588-209 Page 7 of 13

Ideal Material Solution Tag Description Product # A Predator VAV with CO2 5IN, 8 2AO, 1 DPS, 1RTS 588-518 Predator Full Point Wiring Base 587-175 Predator VAV Actuator 2301* 588-524 B Predator Room Sensors: Sensing Only 587-180 Override 587-181 Setpoint 587-182 Temperature Display** 587-183 Setpoint and Override 587-184 Override and Temperature Display** 587-185 Setpoint and Temperature Display** 587-186 Setpoint and Temperature Display** 587-187 With terminal blocks and warmer/cooler setpoint adjustment 587-188 With terminal blocks, warmer/cooler setpoint adjustment & occ. override 587-189 With term. blocks, warmer/cooler stpt adjustment, occ. ovrd & LCD dsply 587-196 Predator Room Sensors without Logos No Logo Sensing Only 587-550B No Logo Setpoint 587-552B No Logo Setpoint and Override 587-554B No Logo Setpoint, Override and Temperature Display 587-557B Mylar Tabs 20 pack (covers RJ-11 opening for 4 conductor cables) 544-634P20 Flush Mount 10K Room Sensor 536-994B C Predator Room Sensor RJ-11 Pre-terminated 6 Conductor Plenum Rated Cables 25 Foot 588-100A 50 Foot 588-100B 100 Foot 588-100C Predator RS RJ-11 Pre-terminated 4-Conductor (no network connection) Plenum Rated Cables 25 Foot 588-101A 50 Foot 588-101B 100 Foot 588-101C D IAQ Sensor for CO2 & VOC IAQ CO2/VOC Sensor with LED Display CO2 Sensor Duct Mounting Kit QPA63.1 QPA63.2 ARG64 E Floating damper actuator 44 lb. In. GDE.131.P F Floating valve actuator SSB81U Outside Air Temperature 10K Thermistor -40 to 120 F 587-692 * Predator VAV Actuator does not need separate wiring base. ** Sensors will display Fahrenheit or Celsius *** Analog valve is only supported on Full Point 587-135 Page 8 of 13 Document No. 588-209

Configuration Table The following table lists all of the configuration properties (CPs) available with this application. For more information on how to set these properties, please consult the Predator VAV with CO2 Application Guide. Configuration Properties VAV with CO2 Configuration Property Language-dependent Name actdisplay Actuator Display Selection airtermtype Type of Air Terminal bypasstime Bypass Time clgdmdctrb PID Controller Gain of the Cooling Controller Element Programmatic Name Pb Ti Factory Value command no_fan 60 minutes 2.78 C (5.0 F) 2000.0 seconds co2sensrng Space CO2 Sensor Range ductarea Trm Duct Area fanunocchtg Unocc Heat Fan Operation fanwarmup Warmup Operation for Fan flowdmprmotr Trm Flow Damper Motor flowdmprsat Trm Flow Damper Saturation Td 0.0 seconds 0 ppm 1.076 ft 2 (0.1 m 2 ) modulate on TravelTime 90.0 sec Reverse SyncDirection Close SaturationLoad 110% PrctDeadband 2% TimeDelay 10 min flowfanrq Flow Setpoint Deadband flowunocchtg Unoccupied Heat Flow Operation flowvav Flow VAV Element flowwarmup Warmup Operation for Flow PercentOn 110.00% PercentOff 100.00% modulate Enable TRUE DmdAtMin 0.00% DmdAtMax 100.00% Off hcoilfanrq Heat Coil Fan Request PercentOn 3.00% Document No. 588-209 Page 9 of 13

Configuration Property Element Factory Value Language-dependent Name hcoilunocc Unocc Operation for Htg Coil hcoilwrmup Warmup Operation for Htg Coil hstagecyc Staged Heat Cycle Time htgclgswit Heating Cooling Switchover Logic Programmatic Name PercentOff 0.00% Cycle Cycle 10 minutes DmdDeadband 1.0% TmpDeadband 0.9 F (0.5 C) htgdmdctrb PID Controller Gain of the Heating Controller TimeDelay Pb 3 minutes 10.0 F (5.56 C) htgdmdfanrq Heating Demand Fan Request htgfandelay Staged Heat Fan Delay htgswitmeth Switching Method for Staged Heat maxflow Trm Max Flow Clg maxflowhotpri Trm Max Flow Htg w/hot Primary maxflowheat Trm Max Flow Htg minflow Trm Min Flow Clg minflowheat Trm Min Flow Htg minflowstby Trm Min Flow Stby minflowunoc Trm Min Flow Unocc numhstages Number of Terminal Heat Stages numperimstgs Number of Perimeter Heating Stages occsensprior Occ Sensor Operating Priority occsensoren Local Occupancy Sensor Enable perimhunocc Unocc Operation Perim H Coil perimhwrmup Warmup Operation Perim H Coil Ti Td 1000.0 seconds 0.0 seconds PercentOn 110.00% PercentOff 100.00% 2 minutes deadband 1180 l/s (2500 cfm) 1180 l/s (2500 cfm) 401 l/s (850 cfm) 212 l/s (450 cfm) 283 l/s (600 cfm) 212 l/s (450 cfm) 165 l/s (350 cfm) 0 0 unoccupied modulate cycle perimhtgcoil Perimeter Heating Coil Element Enable Page 10 of 13 Document No. 588-209

Configuration Property Element Factory Value Language-dependent Name perimhtgmotr Perimeter Htg Coil Motor sensconstvav Trm Flow Gain seriesstdelay Series Fan Start Delay sourcetemplim Heating Cooling Limits spaceco2stpt Space CO2 Setpoint spare1in spare2in spare1out spare2out statswitchen Local Occupancy Switch Enable stptdialen Local Temperature Setpoint Dial Enable stptoffstspan Spc Temp Stpt Offset Span tempstptlim Space Temperature Setpoint Dial Limits trmcoolsat Terminal Cooling Saturation Programmatic Name DmdAtMin 0.00% DmdAtMax 100.00% TravelTime 125 seconds Reverse SyncDirection close 1 0.0 seconds NeededToCool 18.0 C (64.4 F) NeededToHeat 25.0 C (77.0 F) 0 ppm 2.0 C MinTemp 19.0 C (66.2 F) MaxTemp 25.0 C (77.0 F) saturationload 110% tempdeadband 10 C (18 F) trmflowctrb Trm Flow Cntr Band trmheatsat Terminal Heat Saturation trmhtgcoil Terminal Heating Coil Element trmhtgenrgy Energy Source for Terminal Heating Coil timedelay Pb 4 Ti Td 10 min SaturationLoad 110% TempDeadband TimeDelay Enable 12.0 seconds 0.0 seconds 2 C (3.6 F) 10 min DmdAtMin 0.00% DmdAtMax 100.00% Hot Water Document No. 588-209 Page 11 of 13

Configuration Property Language-dependent Name trmhtgmotr Terminal Heating Coil Motor Element Programmatic Name Factory Value ventdmdctrb Ventilation Demand Cntr Band venttempdb Ventilation Disable Temp DBand TravelTime 125.0 seconds Reverse SyncDirection Close Pb 0.00 Ti 0 seconds Td 0 seconds 1.11 C * Available on some models of the Predator Room Temperature Sensor. Network Configuration Inputs (nci) NV Name Language-dependent Name Element Programmatic Name Factory Value nciproffset Pressure Offset ncisetpnts Occupancy Temperature Setpoints Occupied Cooling Setpoint (occupied_cool) Standby Cooling Setpoint (standby_cool) Unoccupied Cooling Setpoint (unoccupied_cool) Occupied Heating Setpoint (occupied_heat) Standby Heating Setpoint (standby_heat) Unoccupied Heating Setpoint (unoccupied_heat) 0.00% 73.4 F (23.0 C) 77.0 F (25.0 C) 82.4 F (28.0 C) 69.8 F (21.0 C) 66.2 F (19.0 C) 60.8 F (16.0 C) Page 12 of 13 Document No. 588-209

Control Mode Interaction Table VAV/CV Notice: Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Credits: Raptor, Predator, and TALON are trademarks of Siemens Building Technologies, Inc. Niagara Framework is a registered trademark of Tridium, Inc. Other products and company names herein may be the trademarks of their respective owners. Siemens Building Technologies, Inc. HVAC Products 1000 Deerfield Parkway Buffalo Grove, Illinois 60089 Phone 847-215-1000 SBT_technical.editor.us.sbt@siemens.com Copyright 2008 by Siemens Building Technologies, Inc. Document No. 588-209 Page 13 of 13