Modulating Furnace Information. Warning on Meter Setting - Read First!

Similar documents
E Series CE Approved Intermittent Pilot Ignition Control

Hayward error codes and troubleshooting

G861 Series Integrated Function. Direct Spark Ignition Control

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

SERIES VAC Microprocessor Based Direct Spark Ignition Control with Combustion Blower Relay FEATURES DESCRIPTION

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

G76x Direct Spark Ignition Controls

BLOWER VACUUM SWITCH FAILED OPEN

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

Electronic Products ELECTRONIC MAINTENANCE

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

Application Engineering

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

G72x Series Direct Spark Ignition Controls

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

Application Engineering Europe

G600 Series Replacement Intermittent Pilot Ignition Controls

Subject Underhood G System Error Codes and Symptoms System or Parts affected

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

Troubleshooting Manual

Introduction. System Components

BG1600M Intermittent Pilot Ignition Control

Application Engineering

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Advanced 90% Furnace. Troubleshooting

en Hydronic Surface Heater S 3000 REPAIR MANUAL

burners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive.

Installation instructions for KIT15017, KIT15018, KIT15019, and KIT15020

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

Circuit Board Diagnostics

ADVANCED PID TROUBLESHOOTING

Q35 Series Automatic Vent Damper System

HVF110, 210, 310, 410HD

Visit for more technical information & downloads

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

Start Up Instructions for the Kiln, Page 1 of 2

Service Bulletin. (This bulletin and all other active bulletins are downloadable from our website at

EcoNet and Flash Codes

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

SERVICE MANUAL (INTERNATIONAL)

DD80HS. Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE. Heating Input: 40, ,000 BTU/h

ORDERING INFORMATION SPECIFICATIONS APPLICATION

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

INSTALLER MANUAL USER MANUAL. Contents

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

Primary Controls. Chapter 11. Introduction. Functions of the primary control

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

First Correlating Revision No. 1-NFPA [ Section No ]

Technical Information and Diagnostic Guide

OUTDOOR UNIT CONTROLLER (OUC)

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS?

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

Heater Troubleshooting Guides

DM80SS / DD80SS. Single-Stage, Multi-Speed Gas Furnaces 80% AFUE Heating Input: 40, ,000 BTU/h

TRITON ERROR CODES ERROR CODE MODEL SERIES DESCRIPTION RESOLUTION

N1387 Series Troubleshooting Guide for N Alternators

SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION

SMART DRIVE ELECTRONIC WASHING MACHINE

Series 20 Installation Instructions

Trouble Shooting Guide EWA, 3-phase (D2422)

Series 14R. Installation Instructions and Field Service Checklist

Water Valve Shutoff. WVS Water Valve Shutoff

WARRANTY WILL BE VOID If These Steps are Not Performed Before Installing The Control STEPS TO PERFORM BEFORE CONTROL INSTALLATION

TABLE OF CONTENTS. Understanding the Troubleshooting Instructions...2 Signal Light...2 Harness Connections...2 Inspection...2

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

BGH2UNCNTRLHT-01 Universal Hot Surface Ignition Control

INSTALLATION/OPERATING INSTRUCTIONS MCP

OnCommand Troubleshooting Guide Hayward Industries

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

TurfDefender Electronic Leak Detector Kit Reelmaster 5000, 6000 and 5010 Series Traction Units

Smart 110 with built-in flashlight for 6 240Ah lead-acid batteries

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

SAVANNAH EI & DELUXE SYSTEM TROUBLE SHOOTING GUIDE

VAL6 KBE5S. Service Manual

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)

Eminox Electronic Service Indicator

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified.

CONTROLLER DIAGNOSTIC GUIDE

TABLE OF CONTENTS. Understanding the Troubleshooting Instructions...2 Signal Light...2 Harness Connections...2 Inspection...2

GLM SERIES CONTROL Users Manual Rev:

P0441-EVAP PURGE SYSTEM PERFO... P0441-EVAP PURGE SYSTEM PERFORMANCE

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

Technical Information and Diagnostic Guide RestStar Use this guide with 5700XE RestStar Unit. Western Star 5700XE.

Cover. L5v2 Plug-In Conversion Module(PCM) Diagnostic Trouble Codes

Section 3 Technical Information

Powertrain DTC Summaries EOBD

GMH8/GDH8. Two-Stage Convertible Multi-Speed Gas Furnaces 80% AFUE

DESCRIPTION & OPERATION

WARNING This manual should only be used by a qualified Service Technician. FinishPro 390/395 Airless/Air-Assisted Sprayer Repair Electrical Manual

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart

Transcription:

Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56 0.75" 1.66 0.80" 1.75 ma DC Firing Rate Temp F Ohms 0.85" 1.84 40 ma 35% 70º 11832 Ω 0.90" 1.94 57 ma 40% 110º 4633 Ω 0.95" 2.03 90 ma 50% 120º 3733 Ω 1.00" 2.13 107 ma 60% 130º 3027 Ω 1.05" 2.22 125 ma 70% 140º 2470 Ω 1.10" 2.31 142 ma 80% 150º 2028 Ω 1.15" 2.41 160 ma 90% 160º 1674 Ω 1.20" 2.50 177 ma 100% 170º 1390 Ω 1.25" 2.59 180º 1160 Ω 1.30" 2.69 1.35" 2.78 1.40" 2.88 1.45" 2.97 Warning on Meter Setting - Read First! When checking a transducer, the meter must be set for DC Volts. If the meter is inadvertantly set to "Ohms", the meter's battery voltage will be applied to the microprocessor on the control board resulting in a failed board. The DC Volt measurement should be taken between the Black and Green wires at the Transducer plug. Modulating Gas Valve Thermostat Settings Electro-Mechanical Heat Anticipator - 0.1 Amps Digital Cycle Rate - 6 Cycles per Hour Pressure Switch Information Operating Max. Operating Points Discharge Air Sensor Cond. Switch 1.50" 3.06 Furnace Switch Close Open 1.55" 3.16 97% 0.67" 0.90" 0.57" 0.20" 1.60" 3.25 80% 0.40" 0.63" 0.30" Pressure Switch Operation: At the beginning of the ignition cycle, the inducer ramps up until the pressure switch closes, which must occur at a pressure no higher than the switch setting plus 0.10" tolerance plus 0.13" hysteresis, or in the case of an 80% modulating furnace with a 0.40" switch, the switch must close before the pressure reaches 0.63". If the switch doesn't close at the correct pressure, the control will display a three red flash error code and will not continue the ignition sequence. After the closing point has been verified, the inducer will ramp down until the switch opens, but no lower than the switch setpoint minus 0.10" tolerance, or in the case of 80% modulating models, it will ramp down until the switch opens, but no lower than 0.30". If the switch doesn't open in a specified time, the control will display a two red flash error code and will not continue the ignition sequence. This checking occurs not just at startup, but at any time during normal ramp up or down that should result in a switch opening or closing. So at any time during the furnace operation, if the switch is open when it should be closed or vice versa, the control will shut the furnace down. Note: The furnace may operate with the pressure switch open if the above checks have been passed.

Modulating Furnace Information Flashes Off Color Red 1 Red 2 Red 3 Red 4 Red 5 Red 6 Red 7 Red 8 Red 9 Red 10 Red 11 Red 12 Red Steady On Red Slow Green Slow Amber 1 Amber 2 Amber 3 Amber 4 Amber 5 Amber 6 Amber 7 Amber Rapid Amber Rapid Green Error Status Codes - 33" Modulating Furnace Condition No Line Power to Control. Flame present with gas off. Pressure switch closed with inducer pressure below allowed tolerance. Pressure switch open with inducer pressure above allowed tolerance. High Limit Switch open, Fuse open, or Sensor temperature above allowed limit. Auxiliary Limit String or Safety Relay open when it should be closed. Modulated Gas Valve current failure. Lockout due to no ignition. (Flame could not be sensed). Lockout due to flame recycles. (Flame is lost after being sensed). Incorrect line voltage polarity. Gas valve circuit is shorted. Main Blower Failure. Identity Plug loose or missing. Control Fault Detected; No 24 Volt Power Normal Operation - No call for heat. Gas Off - Call for Heat. (Control is in ignition process, flame has not been sensed.) Call for Cooling. Gas On - Call for Heat. (Run 1) Gas On - No Call for Heat. (Run 2) Suppressed firing rate due to Soft Limit. Suppressed firing rate due to Low Combustion Air. Heat Pump Heating Operation Compressor ON - No Call for Cooling (Cooling Run 2). Flame sense current is below 1.5 Microamps. Control is in "Test Mode" with no call for heat. Test Mode Test Mode should be used for startup and service procedures. With power on and no call for heat, press the TEST Button. The 'Fault Light' will flash red. When the Test Button is released, the Fault Light will flash Rapid Green. Initiate a call for heat. Upon proving flame, the firing rate will go directly to 100%. After proving flame and with the burners on, pressing the Last Error button 1, 2 or 3 times within 2 seconds will allow you to select a firing rate. 1 press = 35%; 2 presses = 70%; 3 presses = 100%. If left in Test Mode, the last firing rate will be used on each successive call for heat. To exit Test Mode, cycle power off then back on. The control will time out and exit Test Mode after 150 minutes. Run 1 Burners are on with a call for heat. After flame is sensed, the burners modulate down to 35% and operate for 6 minutes. After 6 minutes, firing rate begins a steady modulation upward until full fire (100%) is reached if the call for heat remains on. This takes approximately 16 minutes from 35% to 100% firing rate. If the call for heat is satisfied, the control enters 'Run 2 Mode'. Run 2 Burners are on without a call for heat. When the thermostat satisfies, the furnace continues to fire at a reduced rate, based on what the firing rate was when the thermostat satisfied. 35% thru 54% = Run 2. 55% thru 100% = Extended Run 2. Those are further explained in the Training Manual. Run 2 cannot be initiated unless preceded by a Run 1. The furnace attempts to cycle between Run 1 and Run 2 without shutting off, which results in the greatest efficiency and comfort.

LED INDICATIONS DURING FURNACE TEST MODE: The Test Mode allows the furnace to be tested at low, medium, and high firing rate to verify the modulation range. The Test mode will operate for 150 minutes. After 150 minutes, the furnace will turn off and return to normal operation. Test mode is initiated by: 1. Turn power OFF 2. Depress test button for one second and release. 3. Apply power and turn the thermostat ON. 4. After the unit has completed the initial warm-up, it will fire at the maximum rate. The firing rate can be changed by pressing error button 1, 2, or 3 times (1= low fire, 2= medium fire, 3= high fire). The furnace test mode starts as soon as the button is released and will be indicated by RAPID GREEN FLASHES, followed by a four second pause. The control is then ready to accept a call for heat in the factory test mode. An operator can alternate among three firing rates by pressing the error button one, two, or three times during a two second period (1= low fire, 2= medium fire, 3= high fire). STEADY ON RED: The test button is depressed. RAPID GREEN FLASH: indicates that furnace in factory test mode. 1 GREEN FLASH: indicates a low firing rate heating cycle is underway. 2 GREEN FLASHES: indicates a medium firing rate heating cycle is underway. 3 GREEN FLASHES: indicates a high firing rate heating cycle is underway. INDICATION OF FURNACE FAILURES: While the furnace is in stand-by mode, meaning there is no call from the thermostat for heating, cooling or fan, the operator can retrieve up to the last five failure codes saved by the control by pushing the Error Code button. A failure code is indicated by a number of RED FLASHES follow by a 2-second pause. The last five failure codes will be displayed. For example, code 7 is a sequence of seven (7) red flashes on followed by a 2-second pause and then the next failure code is displayed. A failure code is retained until the system is reset or a new failure is detected. Hold the Error Code button down for 5 seconds to clear all failure code memory; the LED will display three (3) green flashes when clear. If there are no failure codes, the LED will display two (2) green flashes when checked. 2 of 9

The control puts the system in lockout mode and displays the last failure code when a failure is detected. See LOCKOUT STATE for description for details. The failure code identifies the system error detected, but not exact cause of failure. For any failure code, the technician should check for short and open wires, hoses, ducts, filters, protection switches such as primary, rollout and pressure switches, temperature sensor, air measurement hoses, loose mounting, wrong wiring and installation. 1 Red Flash Improper Flame Sensed Flame is sensed when gas valve is commanded off. A. Flame remains lit in Off cycle. 1. Gas valve leaks - check wiring to remove continuous 24V to gas valve. 2. Gas valve is stuck open remove, repair or replace gas valve. 2 Red Flashes Pressure switch contacts are closed when they should be open. The control validates combustion air comparing the pressure switch and pressure sensor values. If they do not agree, the unit locks out. NOTE: Item C does not apply to 40 furnaces as the sensor is mounted on the board. A. Faulty wiring or connections. B. Faulty pressure switch. C. Faulty pressure Sensor. 1. Check pressure switch wiring. 2. Check remote pressure sensor wiring. 3. Check inducer wiring. 4. Check for broken or disconnected air tube hoses. 5. Check air inlet and outlet for blockage. 6. Check inlet stack length. 1. Replace pressure switch. 1. Replace pressure sensor. D. Faulty board. 1. Replace board. 3 of 9

3 Red Flashes Pressure switch contacts are open when they should be closed. 4 Red Flashes Over temperature in heat exchanger. The control validates combustion air comparing the pressure switch and pressure sensor values. If they do not agree, the unit locks out. NOTE: Item C does not apply to 40 furnaces as the sensor is hard wired to the board. This is caused by open primary limit string or temperature sensor located in plenum heat exchanger. A. Faulty wiring or connections. B. Faulty pressure switch. 4 of 9 1. Check pressure switch wiring. 2. Check remote pressure sensor wiring. 3. Check inducer wiring. 4. Check for broken or disconnected air tube hoses. 5. Check air inlet and outlet for blockage. 6. Check inlet stack length. 1. Replace pressure switch. C. Faulty pressure sensor 1. Replace pressure sensor. D. Faulty board 1. Replace board. A. Improper inlet airflow. 1. Check filter / replace if dirty. 2. Check for improperly sized duct system. 3. Check for faulty blower motor. 4. Check for faulty wiring. 5. Check for temperature sensor connection, reconnect or replace temperature sensor. 6. Check for any open primary limit string switch. 7. Check primary wiring on pins 1 & 2 at Board location J4. B. Fuse is blown 1. Check and replace fuse on the board. C. Temperature Sensor probe not connected. 1. Check Temperature Sensor Probe connection.

5 Red Flashes Auxiliary limit (flame roll-out switch) is open. This indicates flame roll out into the combustion vestibule has been detected. Be sure to reset the rollout switch after correcting the failure condition, if it is open. A. Improper combustion air. B. Defective roll out switch or temperature switch on the inducer. 1. Check for proper combustion air. 2. Check for proper inducer operation. 3. Check for primary heat exchanger failure. 4. Check for burner problem. 5. Check for faulty wiring. 1. Check if rollout switch or inducer temperature switch has failed open. 2. Replace roll out switch. 3. Check auxiliary wiring on pins 3 & 4 at Board location J4. 6 Red Flashes Modulation failure. Indicates an improper ratio of gas and air in the combustion burner has been detected. A. Faulty gas valve. 1. Check for faulty gas valve wiring. 2. Replace modulating gas valve. B. Improper airflow in combustion burner. 1. Check for proper airflow in combustion burner due to inducer. 2. Check air inlet pipes. 3. Check measurement hoses. 4. Check pressure switch. C. Faulty air pressure sensor. 1. Check air pressure sensor on the control and reconnect hoses. 2. Replace board if air pressure sensor on the board is broken. 5 of 9

7 Red Flashes Flame could not be established. This fault code indicates that the flame could not be established during the time provided. This no-light condition occurs after 4 attempts (3 retries) during an initial call for heat. Then the furnace is locked out for one hour and will automatically reset. A. Insufficient gas line pressure. B. Gas valve control turned OFF. C. No ignition from hot surface igniter. 1. Insure gas supply is connected to furnace and check for proper line pressure. 1. Turn gas valve to the ON position. 1. Check igniter voltage and wiring. 2. Replace hot surface igniter. D. Faulty gas valve. 1. Check for faulty gas valve wiring. 2. Replace modulating gas valve. E. Insufficient manifold pressure, gas valve ON at 100% fire. 1. Check 24 VAC to gas valve. 2. Check for 170 190 mamps to gas valve. 3. Check inlet gas pressure. 4. Adjust valve for proper manifold pressure at 100% rate. 5. If gas valve will not adjust, replace gas valve. F. Burners do not light. 1. Check for proper mounting and placement of hot surface igniter. 2. Check for proper mounting of the burner assembly. G. Burners light and remain lit for about 5 seconds. 1. Check flame rod wiring and connections. 2. Check for proper alignment of flame rod. 6 of 9

8 Red Flashes Lost flame signal after flame is established with call for heating. This indicates that the flame sensor signal has been lost after flame is established during a call for heating. A. Flame sensor coated. 1. Clean flame rod sensor. B. Flame sensor improperly mounted or grounded. C. Unstable flame pattern. 1. Check flame sensor wiring and connections. 2. Re-install / replace flame sensor. 1. Check that all burner assembly components are properly installed. 2. Check that all seals between the vestibule area and the heat exchanger area are tight. 3. Insure that the combustion door gasket is in place and the door is properly installed. D. Low gas pressure. 1. Check for low inlet gas pressure. 2. Replace modulating gas valve. E. Flame sensor too hot, shorts to ground. 1. Replace flame sensor. 9 Red Flashes Reverse line voltage polarity or grounding problem. 10 Red Flashes Gas valve circuit shorted to 24 VAC or ground. Furnace ignores call for heating or cooling. The control allows the gas on only with call for heating or when in Run 2 modulation in the heating stage. Run 2 is indicated by three AMBER flashes. A. Polarity is reversed or faulty. A. Faulty gas valve wiring. 1. Line voltage polarity at furnace or branch circuit serving the furnace is reversed. 2. Check furnace grounding. 1. Check gas valve wiring. 2. Re-install / replace gas valve. B. Control Board 1. Check wiring and connections into the J5 location on the control board. 2. Replace board. 7 of 9

11 Red Flashes Main blower failure. This indicates that there is an over temperature condition in the heat exchanger that is not cleared after 5 minutes. A. Failed blower motor. After 5 minutes in this condition, the control puts the furnace in a continuous lockout. 1. Check wiring to blower. 2. Check blower wheel/re-install. 3. Replace blower motor. 12 Red Flashes Identity Plug Furnace does not operate. A. Furnace Identity Plug is loose or not connected. 1. Check that ID Plug wires are all connected to the proper pin. 2. Connect furnace ID plug to board at J11 location. 3. Obtain the proper ID Plug from manufacturer. Steady Red On Firmware has detected an error. The control has detected a system failure. This means that a component is on, or off, when it should not be. A. Transformer 1. Check 24-volt transformer for correct output. 2. Check connections and wiring to control board and other components connected to the 24 volt source. 3. Replace if necessary. B. Control Board 1. Re-try ignition sequence and see if the system responds. 2. Replace control board. 8 of 9

Rapid Amber Flash No Light / LED off Flame rod is below 1.5 microampere No light indication on LED. Measure flame rod terminals at the control board test points. 1 Volt corresponds to 1 microampere at the test point. This indicates a problem with power to the control board. A. Loose or incorrect flame rod connections or positioning. B. Flame rod dirty or corroded. A. Check the 120V path to the control board. 1. Check flame rod wiring and connections. 2. Re-install / replace flame rod. 1. Clean and re-install. 2. Replace flame rod. 3. Correct condition causing corrosion. 1. Check the 120V path to the board including external circuit breakers, disconnects, wires, connections, and furnace door safety switch. 2. Replace control board. LOCKOUT STATES WITH AUTOMATIC RESET AFTER LOCKOUT. Any time that a failure occurs, the control brings the furnace to a lockout state. The control will automatically reset itself under these conditions: a. If the airflow problem is detected after pre-purge and is cleared within 30 seconds with no other pending failures, the system will attempt to re-start b. When an overheating condition in the heat exchanger is cleared, no failures are detected for duration of at least 10 seconds, and there are no requests for cooling and heating the system will attempt to restart. c. After a 1-hour reset, if all active failure conditions are cleared during the reset period. To clear the 1-hour reset period immediately, turn the power off and then back on. HARD LOCKOUT STATES REQUIRING MANUAL RESET AFTER LOCKOUT. Detection of a main blower failure puts the furnace into a continuous lockout state. This lockout requires that the furnace power to be turned off and then back on to reset the control and allow an attempt to re-start. 9 of 9