Security Door Controls

Similar documents
INSTALLATION INSTRUCTIONS 1576DE DELAYED EGRESS EMLOCK

INSTALLATION INSTRUCTIONS E300 SERIES MAGNETIC CABINET/DISPLAY CASE LOCK

SECURITY DOOR CONTROLS 801 Avenida Acaso, Camarillo, Ca (805) Fax: (805)

INSTALLATION INSTRUCTIONS SHEAR LOCKING MAGNET 1561TJ MAX. HOLDING FORCE 2000 lbs.

INSTALLATION INSTRUCTIONS MICRO SHEAR EMLOCKS 1561 & 1562 MAX. HOLDING FORCE 2000 LBS.

2965 Magnetic Shear Lock Installation Instructions

S6100 SERIES REVERSIBLE PANIC/FIRE EXIT RIM DEVICES INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 410/420 SERIES PUSH SWITCH

INSTALLATION INSTRUCTIONS MINI EXIT CHECK DELAYED EGRESS EMLOCK 1581S

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS

INSTALLATION MANUAL. Middle. Def tank. Standard. Middle. Standard. Def tank WARNING. Level of Difficulty CAUTION. Parts List.

DynaLock 705 Emmett Street Bristol, CT Phone:(860) Fax:(860)

MODEL 1200S MAGNETIC LOCK

MODEL 600S 600 POUND SINGLE MAGNETIC LOCK SPECIFICATIONS

MODEL 1200LB 1200 POUND MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR

EMLock 1500 Series. MEA Listed. New Modular Kits. Online System Wizard and Project Manager at

MODEL 1200S MAGNETIC LOCK

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS

cel SECURITY DOOR CONTROLS Value Engineered Access Hardware sdcsecurity.com Power Supplies Exit Switches

EZ-B-10 MAGNETIC BOND SENSOR EZ-T-10 TIMER INPUT MODULE. Modular Kit. Modular Kit. EZ-D-10: DOOR POSITION SENSOR Modular Kit

E-941SA-300RQ. Manual. 300-lb Single-Door Electromagnetic Lock with Reversible Magnet

With LED, Bond Sensor E-941SA-600PQ 600-lb. (272kg) E-941SA-1K2PQ 1200-lb. (545kg) Weatherproof E-941SA lb.

* * M400 Series. Features. Models. Trims. UL Requirements. Single Electromagnetic Locks: M420, M450, M490. Installation Instructions

Excel Series Value Engineered Access Hardware

POWERED RUNNING BOARDS INSTALLATION MANUAL

EMLock 1500 Series. MEA Listed

Electromagnetic Door Holder/Releases

INSTALLATION DESCRIPTION

5000 SERIES POWER SUPPLY/CHARGERS INSTALLATION GUIDE

M670/M680BD MAGNALOCK SERIES Installation Instructions

V2M1200/1290 Series Maglock Installation Instructions

INSTALLATION INSTRUCTIONS DEGR7700 DELAYED EGRESS ALL IN ONE DEVICE

M400 Series Double Locks. Features

XENON POWER SUPPLY 4000 Watt Gladiator IV

HANDLING MECHANICAL INSTALLATION

Applicable to the Following Part Numbers. Notes and Maintenance. Torque Specifications. Metric SAE. Use above torque setting unless otherwise noted

21511 Commercial Light Kit Part # Qty Description

STANDARD / DOUBLE STANDARD MAGNETIC LOCK

MODEL 3002xTJ32 ELECTROMAGNETIC LOCK INSTALLATION INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

KT230 Series Caterpillar 3406 Governor System Installation Kit

MOUNTING INSTRUCTIONS FOR TJ1000 SERIES INSWINGING DOORS ******READ THOROUGHLY BEFORE INSTALLING******

PFadvantage JD 3300/4400/6600/7700; 4420

INDEX Section Page Number Remarks

TROUBLESHOOTING GENERATOR UNITS

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.

CP-1TT Remote System

KT145 Series John Deere 6076 with Nippondenso Inj. Pump

EMLock Magnetic Locks

Vertical Housing EMLock Discount Code GK LIST. Retrofit Kit for Discontinued Locknetics 390+ PLUS

8. Do not install this product on the exterior of buildings. 9. Do not use as a doorstop. This will void warranty. Installation Instructions

RECESSED MAGNALOCK MODEL M34R SERIES INSTALLATION AND OPERATING INSTRUCTIONS

Installing the gate post bracket with the cardboard arm template

AL600ULX Series. Power Supply/Charger Installation Guide

WIRING DIAGRAMS FB4C FE4A/FE5A FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL

* * M400 Series Double Locks. Double Electromagnetic Locks: M422, M452, M492. Installation Instructions. Mounting Bracket (2)

1-3/4" MOUNTING INSTRUCTIONS: 1150 SERIES SURFACE MOUNTED 1500 LB. ELECTROMAGNETIC LOCK

Installing the gate post bracket with the cardboard arm template

Package Contents. Mounting Hardware

Installation Instructions

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

ASVC2 OWNER S MANUAL. Vane Cutter PART # MACHINERY DIVISION

EQ73 Parts list Reference Value Qty Description Marking Dim Manuf. YEL-VIO-BLK-GLD-BRN RED-RED-BRN-BRN RED-RED-BLK-BLK-BRN GRN-BLU-BRN-BRN

Electromagnetic Locks DORMA EML

Features Block Diagram Specifications Typical Wiring Diagram Connection and Adjustment Locations...3 4

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel. Model Installation Guide

SHEAR ALIGNING MAGNALOCK MODEL SAM2-24 INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

HYDRAULIC TUBE CUTTER

APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1

Service and Parts Manual. NO LONGER IN PRODUCTION Some service parts may not be available for this product. Otolaryngology Chair.

Proper installation of this product requires the installer to have a good understanding of automotive electronics, systems and procedures.

Installation Instructions for ROFU Key Hole Mount Magnetic Locks

SECURITY DOOR CONTROLS

LPT50BRD (8x11x3 Enclosure)

Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel. Model N Installation Guide

Norcal Power/SWR Meter Assembly & Operating Manual. Revision 1D 10/15/2008

Commercial Debris Blower. Parts Manual. Patent Number 7,841,004,B1

Invensys Energy Solutions 1354 Clifford Avenue (Zip 61111) P.O. Box 2940 Loves Park, IL United States of America

Portable Generator Familiarization & Troubleshooting Guide Section 3 Generator Diagnostics and Adjustments

TRAC-3 TENSION READOUT AND CONTROL

INSTALLATION AND OPERATING INSTRUCTIONS For Model M38 and M68 Magnalocks (Versions L, S and LS with D and T Options)

Installation Instructions for Slide Mount Magnetic Locks

KT101 Series Governor System Installation Kit Cummins 4B(T) / 6B(T) With CAV/DPA Pump

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Automotive: Sirens/Switches

Detroit Speed, Inc. Selecta-Speed Wiper Kit Mustang P/N:

Locking Devices. Electromagnetic Locks. Security Door Controls 8 SECURITY DOOR CONTROLS

3143 Production Drive Fairfeild, Ohio Model HA Installation and Service Manual

User's Manual 1035D. 2 Axis Step Motor Driver. motors drives controls

Proper installation of this product requires the installer to have a good understanding of automotive electronics, systems and procedures.

Instructions for 2-row monitoring only

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

Spectra Class. N6000 Series Exit Devices SECURITY DOOR CONTROLS. N6100 Rim Mount Exit Device. N6200 Surface Vertical Rod Exit Device.

ASSA ABLOY MPI (Infinite Hold Open Range) Support Unit Models. Multi-Point Electromechanical Overhead Concealed Closer Holder Releasing Device

UNIT VIBRATOR MODELS 60U AND 70U

INSTALLATION 8310/8320

Model: ACP-12 AUTO COMPRESSOR PUMP SYSTEM 12 VDC INSTALLATION & OPERATION MANUAL. Phone:

Transcription:

Security Door Controls 801 Avenida Acaso, Camarillo, ca. 930 (805) 494-0622 Fax: (805) 494-8861 www.sdcsecurity.com E-mail: service@sdcsecurity.com 1575-1576 EMLOCK R INSTALLATION INSTRUCTIONS During installation, care must be taken to assure full electro-magnet and armature contact. The Emlock and armature should be handled carefully. Any damage to the surface such as paint, burrs and dirt will hinder full holding power. Although all SDC Emlocks are provided with the best possible plating for corrosion resistance, the continued impact of the armature against the Emlock may cause eventual wear of the plating. If wear causes rust to occur, clean the surface using a fine abrasive pad. Do not use coarse material to clean surfaces. After cleaning, do not touch the Emlock face or armature with your hands. A rust inhibitor such as M1 manufactured by Starret, or LPS3 manufactured by LPS Laboratories (available at most hardware stores) may be applied. Mount the Emlock to a fence post or similar structure. The armature is mounted to the gate. The fabrication of additional mounting plates and angle brackets may be required by the installer. Due to various gate and fence designs, there is not a standard or recommended method of installation. Emlocks are fail-safe (locked when energized) devices and require power to remain locked. A power supply with battery backup is required when power outages may interfere with desired security. INSTALLATION: 1. Inspect the gate and post to determine if any mounting plates or angle brackets are required. Install mounting hardware as required. 2. Mark the mounting surfaces per the template. Be sure the centerline of the armature template matches the centerline of the Emlock template. Drill and tap holes as indicated. 3. Mount the armature to the gate. Determine the proper hardware (provided) see Figure 1. DO NOT SUBSTITUTE ARMATURE MOUNTING HARDWARE AND DO NOT WELD THE ARMATURE DIRECTLY TO THE MOUNTING SURFACE. When properly mounted, the armature will pivot slightly around the mounting screw. REINFORCEMENT TUBE 5/8 DRILL STEEL WASHER RUBBER WASHER 5/- x 2 FIGURE 1 5/- x 1-½ 3/8" WASHER Add as required RUBBER WASHER SEXNUT 1/2 DRILL ARMATURE ARMATURE SPACER 1-3/4 HOLLOW METAL DOOR From Sexnut side of door, drill exactly 1/2 hole thru one metal thickness only. From armature side of door, drill 5/8 hole to insert reinforcement tube. Press in sexnut and reinforcement tube all the way and mount armature to door using hardware provided. 3/8 MIN METAL MOUNTING SURFACE Drill and tape for 5/ machine screw. Mount armature to door with hardware provided. P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\INST-1575-76U.vsd REV B 08- Page 1

INSTALLATION (CONT.): 4. Mount the Emlock with hardware provided (See pages 3 & 4). 5. Tighten all screws. Install anti-tamper plugs over socket head mounting screws. 6. Install 1/2 or 3/4 conduit. A conduit outlet box must be provided within 15" of the lock for wire connections. 7. Make all wire connections to a fused power source with the power off. WIRING DETAILS: * ACCESS CONTROL(S) To Properly Fused DC Power source RED BLU BLK BRN VDC CONFIGURATION 1575-76 EMLOCK VDC @450mA BOND SENSOR (BAS) WIRING WIRE COLOR CONTACT YEL GRN ORG N/O COM N/C DESCRIPTION GOOD BOND COMMON NO/POOR BOND * ACCESS CONTROL(S) RED BLU To Properly BLK Fused DC Power BRN source 24VDC CONFIGURATION 1575-76 EMLOCK 24VDC @225mA DOOR POSITION SENSOR (DPS) WIRING WIRE COLOR CONTACT WHT GRY VIO N/O COM N/C DESCRIPTION ACTIVATE WHEN DOOR OPEN COMMON ACTIVATE WHEN DOOR CLOSED To determine the correct wire gauge to use on a single circuit the following information is required: 1. The quantity, voltage and current draw of all lock(s) to be connected to the circuit. 2. The distance in feet from the power supply to the furthest lock on the circuit. Add together the current draw (amps) of all locks on the same circuit. Using the AWG Chart below, cross reference the total amps with the distance between the power source and the furthest lock to determine the wire gauge required. A single circuit describes a pair of wires run from the power supply to one or more locks that are wired in parallel. The distance from the power supply to the furthest lock in the circuit must not exceed the distance number shown in the chart below and is based on your selected wire gauge. If the distance shown in the chart is inadequate for your application, divide your locks up into 2 or more separate circuits and use the chart to check each circuit independently. Fewer locks on each circuit may allow you to use a smaller gauge wire or will allow you to increase the maximum distance between the power supply and the furthest lock on the circuit. More than one circuit can be connected on the same power supply as long as the combined current required from all connected circuits does not exceed the power supply rating. NOTE: All wiring must be installed in accordance with all state and local codes. Minimum Wire Gauge For Volts AC or DC Minimum Wire Gauge For 24 Volts AC or DC AMPS 0.25 0.50 0.75 1.00 1.50 2.00 3.00 3.50 AMPS 0.25 0.50 0.75 1.00 1.50 2.00 3.00 3.50 25 25 DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE 50 75 100 150 200 250 300 400 500 DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE 50 75 100 150 200 250 300 400 500 1000 1000 P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\INST-1575-76U.vsd REV B 08- Page 2

COIL BOND DPS SENSOR SENSOR #1/4-20 x 2 MODEL 1575 FOR 1/2 OR 3/4 (.7) (19.05) 8.66 (220) 7.64 (194).453 (11.5).5 (13) 4.33 (110) 7.283 (5) 0.63 () 1.6 (41) MODEL 1576 FOR 1/2 OR 3/4 (.7) (19.05) COIL BOND DPS SENSOR SENSOR.63 () 2.4 (61) #1/4-20 x 1-½ 8.66 (220) 7.638 (194).5 (13) 4.33 (110) 7.283 (5) 1.772 (45) 1.6 (41).63 () 2.4 (61) P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\inst-1575-76U.vsd REV B 08- Page 3

1576 GATE EMLOCK MOUNTING ACCESSORIES 1576-BK MOUNTING BRACKET FOR 1576 1576-MP MOUNTING PLATE FOR 1576 P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\INST-1575-76U.vsd REV B 08- Page 4

TROUBLE SHOOTING 1575-1576 EMLOCK PROBLEM CAUSE SOLUTION Residual magnetism. The lock releases slowly. Poor holding power Control switch wired on the AC side of the power source Armature installed rigidly. Insufficient voltage The access control switch must be wired on the DC side of the power supply. When an AC transformer and a bridge rectifier are used, the access control switch must be wired between the rectifier and the Emlock. The armature must pivot loosely from its center mounting point to permit full armature contact. Check for proper voltage at the Emlock input. If the voltage is low, determine if the correct wire gauge is being used to prevent excessive voltage drop. Check the power supply load capacity. It must meet or exceed the combined current rating of the Emlocks on the circuit. No magnetic power. Door does not lock. AC voltage output No power Input polarity reversed. Open circuit in lock coil. Coil short. Emlocks require DC input voltage. When an AC transformer is used, a bridge rectifier must be installed to convert the AC output of the transformer to DC. Check the input voltage at the Emlock. If the voltage is zero or a low reading, double check all wire connections. Note Polarity: VDC Config.: RED/BLU Positive, BRN/BLK Negative 24VDC Config.: RED Positive, BRN Negative Check the Emlock coil continuity with OHM meter. If the reading is high or open, replace the magnet. A coil short or incorrect wiring will blow fuses. Measure the coil for correct resistance. If the coil reading is zero or low, replace the magnet. If the coil resistance is correct, check the field wiring for shorts. Locate and repair the short in the field wiring. BAS Option does not show lock secure. Insufficient voltage Armature installed rigidly or misaligned. Check for proper voltage at the Emlock input. If the voltage is low, determine if the correct wire gauge is being used to prevent excessive voltage drop. The armature must pivot loosely from its center mounting point to permit full armature contact. Surface of magnet or armature rusted or pitted. Clean the armature and surface of the lock (see Page 1) P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\INST-1575-76U.vsd REV B 08- Page 5