Installation, Maintenance, & Repair Series 995 Reduced Pressure Zone Backflow Preventers

Similar documents
Series 867 Reduced Pressure Zone Assemblies

Installation, Maintenance, & Repair Series 919 and LF919

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

Series 009. Reduced Pressure Zone Assemblies. Installation Service Repair Kits Maintenance. Sizes: 8 80mm. 80mm 009LF RP/IS-009-AUS

Series 007. Double Check Valve Assembly. Installation Service Repair Kits Maintenance. Sizes: 1 2" 3" Watts 3 4" 007M3QT RP/IS-007

Installation Service Repair Kits Maintenance RP/IS-774/774DCDA/774X/774XDCDA

Series 957, 957N, 957Z, 957RPDA, 957NRPDA, 957ZRPDA

Series 990/990RPDA. Reduced Pressure Zone Backflow Preventer. Sizes: 4", 6", 8" (100mm, 150mm, 200mm)

Colt Series C400, C500

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

4000SS. For other repair kits and service parts, send for Ames Repair Parts Price List, PL-A-RP-BPD.

Installation, Maintenance, & Repair Series 4000CIV

Installation, Maintenance, & Repair Series 909, LF909, 909RPDA, LF909RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies

Series 995/995RPDA. Sizes: 3" - 6" Reduced Pressure Zone Backflow Preventer/ Reduced Pressure Detector Assemblies RP/IS-995/995RPDA

Installation, Operation and Maintenance Manual

THIS WARRANTY IS IN LIEU

Installation, Operation and Maintenance Manual

Watts Series CSM-61. Flow Measurement/Balancing Valves Sizes: 1 1 4", 1 1 2", 2", 2 1 2", and 3" (32, 40, 50, 65 and 80mm) Installation Instructions

Watts Series CSM-91. Grooved/Flanged Flow Measurement/Balancing Valves. Installation and Operating Instructions. Table of Contents. 1.

Digital Print-out Test Kit for Backflow Preventer Assemblies

TERMS OF USE TERMS AND CONDITIONS. Plumbing and Heating Products (PL-WR)

Maintenance Manual Double Check and Double Check Detector Assemblies Series 850, 856, 870V & 876V 2 1 /2" - 10" (65 250mm)

Installation Instructions

Installation, Operation, and Maintenance Manual Series LFF113FP Wireless Smart Universal Flood Protection ACV System with SentryPlus Alert Technology

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION & MAINTENANCE MODEL mm

2 ½ 12. Model RP 4A Model RPDA 4A Model RPDA2 4A. Installation, Operation, and Maintenance Manual

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

Technical Instructions

AMES 2016 Price List. Backflow Prevention Products and Repair Kits and Parts. Effective February 29, 2016

2 ½ 12. Installation, Operation, and Maintenance Manual. Reduced Pressure Principle Backflow Preventer. Reduced Pressure Detector Assembly

Sanitary Yard Hydrant Installation Instructions

FOR TECHNICAL ASSISTANCE

Sanitary Roof Hydrant Installation Instructions

RSV16 Retro-Fit Cartridge Acorn Controls SV16 Valve Cartridge

Price List. Backfl ow Prevention Products, Repair Kits, and Parts. Effective July 2, AmesFireWater.com 2018 AMES FIRE & WATERWORKS PRICE LIST

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

FOR TECHNICAL ASSISTANCE

Maintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10"

STOP CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL

MULTI-STAGE FILTRATION SYSTEM INSTALLATION INSTRUCTIONS

SP40 Submersible Sewage Ejector Pump

HALLMARK INDUSTRIES INC

GARDEN HOSE UTILITY PUMP

Installation, Maintenance, & Repair Series 994/994RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies

LEAD FREE * PVS-7000 Engineered Flood Protection Valve Station with SentryPlus Alert

DC-501 Double Check Backflow Preventer OPERATIONS, MAINTENANCE AND TROUBLESHOOTING GUIDE

ESE Series Cast Iron Sewage Pumps

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

Dual/Triple Manifold Water Filtration Systems Instruction Manual

Price List. Backflow Prevention Products and Repair Kits. Effective Date October 30, FEBCOonline.com 2017 FEBCO PRICE LIST

UV PROCESS SUPPLY, INC. CON-TROL-CURE ½ DIAPHRAGM PUMP INSTRUCTION MANUAL PART # J

Price List. Backflow Prevention Products and Repair Kits. Effective Date July 2, FEBCOonline.com 2018 FEBCO PRICE LIST

HR-20P Pneumatically Controlled Pressure Regulator

Installation Instructions To ensure that your installation proceeds smoothly--please read these instructions carefully before you begin.

Installation Instructions

Dual Flow Manifold Systems Instruction Manual

Pump Installation and Service Manual SP40 Submersible Sewage Ejector Pump

Installation, Operation and Maintenance Manual

Air Control Kit INSTRUCTIONS-PARTS LIST. Table of Contents HIGH VOLUME. 250 psi (1.7 MPa, 17.2 bar) Maximum Air Inlet Pressure

Artesian2 Owners Manual

Owner s Manual GLASSLINED PUMP TANK

DRAIN WATER TEMPERING KIT

BC Brake Caliper. (i) MEX (55) QRO (442) MTY (81) DIST. AUTORIZADO

Scale Feeder Manifold Water Filtration System Instruction Manual

Installation Manual DIAPHRAGM WELL TANK

W/D/V-A1. Submersible Sump Pump. Pump Installation and Service Manual W-A1 V-A1 D-A1

Cascade Owners Manual

Pump Installation and Service Manual SK60 Submersible Sewage Ejector Pump

LEAD FREE * LFF113FP. Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology. Materials NOTICE NOTICE ES--LFF113FP

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

AMES 2015 Price List. Backflow Prevention Repair Kits and Parts. Effective March 30, Includes Our. Product Offering.

Dual Port Manifold Water Filtration Systems Instruction Manual

Cash-Flo. Operation & Maintenance Manual. BackFLOW PREVENTERS. A Division of the Reliance Worldwide Corporation

Artesian Owners Manual

READ THIS MANUAL CAREFULLY BEFORE USING THE PUMP

BFMM DC4A SBF EFFECTIVE AUGUST 1, 2016

MODEL 900 IMPELLER-TYPE FLOW METER

INSTRUCTIONS AND SERVICE MANUAL WITH PARTS LIST

MODELS 108 and 138 CRAWL SPACE PUMPING SYSTEM PREINSTALLATION CHECKLIST

INSTALLATION & SERVICE INSTRUCTION MANUAL W.A. KATES FLOW CONTROLLERS FC VALVE MODELS E THRU M

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.

AMES 2013 Price List. Backflow Prevention Products. Effective April 1, 2013

AUTOMATIC SUBMERSIBLE UTILITY PUMP

Installation Instructions

Single Post Caliper Brake VC500

INSTALLATION AND SERVICE MANUAL MSKV50 Submersible Sewage Ejector Pump

Air Control Kits INSTRUCTIONS-PARTS LIST. Table of Contents HIGH VOLUME. 250 psi (1.7 MPa, 17.2 bar) Maximum Air Inlet Pressure

StormPro BA Series Sump Pump

JET METER INSTRUCTIONS

DeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1

4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause

OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

PUMP PRIMING INSTALLATION CHECK MOTOR ROTATION PUMP START-UP MOTOR REPLACEMENT DISASSEMBLY ELECTRICAL HOOKUP ASSEMBLY

SUPER PUMP OUT SYSTEM

PRESSURE REDUCING CONTROL VALVE

Transcription:

Installation, Maintenance, & Repair Series 995 Reduced Pressure Zone Backflow Preventers RP/IS-995 Sizes: 2" through 2" (5-50mm)! WARNING Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment. Keep this Manual for future reference.! WARNING Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation. If the information provided here is not consistent with local building or plumbing codes, the local codes should be followed. This product must be installed by a licensed contractor in accordance with local codes and ordinances. Watts 995 shown! WARNING Need for Periodic Inspection/Maintenance: This product must be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. If installed on a fire suppression system, all mechanical checks, such as alarms and backflow preventers, should be flow tested and inspected in accordance with NFPA 3 and/ or NFPA 25. All products must be retested once maintenance has been performed. Corrosive water conditions and/or unauthorized adjustments or repair could render the product ineffective for the service intended. Regular checking and cleaning of the product s internal components helps assure maximum life and proper product function. For Australia and New Zealand, line strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer. Testing For field testing procedure, refer to Watts installation sheets IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on watts.com. For other repair kits and service parts, refer to our Backflow Prevention Products Repair Kits & Service Parts price list PL-RP-BPD found on watts.com. For technical assistance, contact your local Watts representative.

Basic Installation Instructions 2" - 2" (5-50mm) Indoor Installation For indoor installations, it is important that the assembly be easily accessible to facilitate testing and servicing. If it is located in a line close to wall, be sure the test cocks are easily accessible. A drain line and air gap should be piped from the relief valve connection as shown, where evidence of discharge will be clearly visible and so that water damage will not occur. Therefore, never install in concealed locations. Outside, Above Ground Installation Must take precaution to protect against freezing. Temperatures below 32 F can lead to damage or property loss. Indoor Installation Meter Strainer " Watts 995QT with Air Gap 2" In areas where freezing conditions do not occur, Series 995 can be installed outside. The most satisfactory installation is above ground. In areas where freezing conditions can occur, Series 995 should be installed above ground in an insulated enclosure. Series 995 must be installed in an accessible location to facilitate testing and servicing. A discharge line should be piped from the air gap at the relief valve connection making sure that there is adequate drainage. Never pipe the discharge line directly into a drainage ditch, sewer or sump. Series 995 should never be installed where any part of the unit could become submerged in standing water. Backflow preventers should never be placed in pits unless approved by local codes. In such cases, a modified pit installation is preferred. Parallel Installation Two or more smaller size assemblies can be piped in parallel (when approved) to serve a large supply pipe main. This type of installation is employed where increased capacity is needed beyond that provided by a single valve and permits testing or servicing of an individual valve without shutting down the line completely. The number of assemblies used in parallel should be determined by the engineer's judgement based on the operating conditions of a specific installation. For parallel valve installations, the total capacity of the assemblies should equal or exceed that required by the system. Outdoor Installation WattsBox Indoor Installation Watts 995QT Min. 2" Now available. WattsBox Insulated Enclosures, for more information, send for ES-WB or ES-WB-T. 995QTS 2

Basic Installation Instructions 2" - 2" (5-50mm)! WARNING Depressurize valve before servicing. A. Series 995 must be installed in a horizontal position. B. The 995 should always be installed in an accessible location to facilitate testing and servicing (See page 2). Check the state and local codes to insure that the backflow preventer is installed in compliance, such as the proper height above the ground. C. We recommend a strainer be installed ahead of 995 series assemblies to protect the internal components from unnecessary fouling.! CAUTION Do not install with strainer when backflow preventer is used on seldom-used water lines which are called upon only during emergencies, such as fire sprinkler lines. Start Up: The downstream shutoff should be closed. Open upstream slowly and fill valve. When valve is filled, open the downstream shutoff slowly and fill the water supply system. This is necessary to avoid water hammer or shock damage. D. Water discharge from the relief valve should be vented in accordance with code requirements. The relief valve should never be solidly piped into a drainage ditch, sewer or sump. The discharge should be terminated approximately 2" (300mm) above the ground or through an air gap piped to a floor drain. Relief Valve Discharge Rates The installation of an air gap with the drain line terminating above a floor drain will handle any normal discharge or nuisance spitting through the relief valve. However, floor drain size may need to be designed to prevent water damage caused by a catastrophic failure condition. Please refer to Figure No. for maximum relief valve discharge rates, size and capacity of typical floor drains. Do not reduce the size of the drain line from the air gap fitting. Pipe full line size. E. After initial installation, a discharge from the relief valve opening may occur due to inadequate initial flushing of pipe lines to eliminate dirt and pipe compounds. If flushing will not clear, remove the first check valve and clean thoroughly. Periodic relief valve discharge may occur on dead end service applications, such as boiler feed lines or cooling tower makeup lines due to fluctuating supply pressure during a static or no flow condition. To avoid this discharge, install a spring-loaded check valve ahead of the backflow assembly to lock-in the downstream pressure. F. Backflow preventers should never be placed in pits unless absolutely necessary and then only when approved by local codes. In such cases, provision should be made to always vent above flood level or for a pit drain to insure an adequate air gap below the relief port. G. It is important that Series 995 backflow preventers be inspected periodically for any discharge from the relief valve which will provide a visual indication of need for cleaning or repair of check valves. Also testing for proper operation of the device should be made periodically in compliance with local codes, but at least once a year or more often, depending upon system conditions. Send for IS-TK-9A, IS-TK-DP/ Flow Rate gpm DL, S-TK-99E and IS-TK-99D instruction manuals for test procedures. Relief vent will discharge water when, during no-flow periods, () the first check valve is fouled or (2) the inlet pressure to the device drops sufficiently due to upstream pressure fluctuations. Otherwise, such relief (spitting) can occur when the second check is fouled during emergency backflow or resulting from a water hammer condition. For trouble shooting guide send for S-TSG. Special considerations are necessary when testing assemblies installed on Fire Prevention Systems. Fire Protection System Installations: The National Fire protection Agency (NFPA) Guidelines require a confirming flow test be conducted whenever a main line valve such as the shutoff valves or a backflow assembly have been operated. Certified testers of backflow assemblies must conduct this confirming test. Figure Relief Valve Discharge Rates 2" - 2" 995 80 60 40 20 00 80 60 40 20 0 0 0 20 30 40 50 60 70 80 90 00 50 * Zone Pressure psi 2" 3 4" " 4" X 2" 2" Typical Flow Rates as sized by floor drain manufacturers: 2" 55 gpm 3" 2 gpm 4" 70 gpm 3

Servicing the Relief Valve 2" - 2" (5-50mm) Test Cock No. Test Cock No. 2 st Check Cover Test Cock No. 3 Cover Bolt (2) Cover Test Cock No. 4 Sensing Hose 2nd Check Cover Relief Valve Cover Nut Relief Valve Stem/ Diaphragm Relief Valve Seat Seat Spring. Remove the relief valve cover nut by turning the nut counterclockwise 2. Remove the relief valve cover, stem/diaphragm assembly, and relief valve spring. 3. Inspect the relief valve diaphragm for wear and replace as needed. 4. The relief valve seat is located inside of the body and can be removed, if necessary, for cleaning/inspection. The seat is pressed into the body cavity and can be removed by inserting a finger in the center of the seat and pulling outwards. Inspect seat for nicks and replace as needed. 5. Inspect the disc rubber and clean or replace if required. The disc can be removed by screwing the white washer counterclockwise. 6. To reassemble the relief valve, press the seat firmly into place in the body, snap the spring onto the relief valve stem, center the spring on the seat, and insert the cover and stem/ diaphragm assembly as a unit, into the body bore. The locating pin in the relief valve cover should be aligned with the corresponding locating notch in the top of the relief valve body. 7. Install relief valve cover nut and tighten. For repair kits and parts, refer to our Backflow Prevention Products Repair Kits & Service Parts price list PL-RP-BPD found on watts.com. 4

Servicing the First and Second Check Valves 2" - 2" (5-50mm) Cover Bolts Test Cock No. 3 Cover First Check Cage Cover Second Check Cage Seat Seat Disc Spring Test Cock No. 2 Seat Seat Disc Spring 2nd Check Removal Test Cock No. Test Cock No. 4 Shutoff No. Shutoff No. 2 Figure Sensing Hose Stem/Diaphragm Seat Relief Valve Body Cover Nut Cover Stem Spring Seat Relief Valve Body. Close shutoff valves and open test cocks No. 2, 3 and 4 to relieve pressure from the body of the valve. Loosen cover bolts and remove cover. The check valve modules can now be removed from the valve by hand or with a screwdriver. Note: The first and second check assemblies are not interchangeable and the first check assembly must be removed prior to removing the second check assembly. 2. The check assemblies are threaded into the valve body. To remove the first check assembly, rotate the check module by hand counterclockwise. 3. The second check assembly is removed by inserting the blade of a screwdriver into two opposing slots of the seat as shown in Figure and rotate the check assembly counterclockwise. 4. The check seats are attached to the cage with a bayonet type locking arrangement. Holding the cage in one hand, push the seat inward and rotate clockwise against the cage. The seat, cage, spring and disc assembly are now individual components. If the cage disengages prematurely, simply use the cage as a tool to screw the check valve seat from the valve body. 5. The disc assembly may now be cleaned and reassembled or, depending on its condition, it may be replaced with a new assembly from a repair kit. Seat should be inspected and replaced as necessary. 6. Reassemble the check module in the reverse order. Install the check modules into the valve body hand-tight. Replace the cover. For repair kits and parts, refer to our Backflow Prevention Products Repair Kits & Service Parts price list PL-RP-BPD found on watts.com. 5

Test Procedure Test Procedure for Reduced Pressure A. All needle valves must be closed on test kit. B. Open test cock No. 4 and flush test cocks Nos., 2 and 3 on reduced pressure assembly then close test cock No. 4. C. Attach hoses as shown. Bleed air from kit, close No. 2 shutoff. Bleed Valve A Bleed Valve B Low (Blue) High (red) Bypass (yellow) No. 2 Shutoff 995 shown Test No. - Check Valve No. 2 Purpose: To test check valve No. 2 for tightness against reverse flow. Requirements: Valve must be tight against reverse flow under all pres-sure differentials. Step Slowly open the needle valve A high side (red) and C bypass (yellow). Keep the B low (blue) closed. Step 2 Open test cock No. 4. Open test cock No. 2 and test cock No. 3 after opening test cock No. 4. Step 3 Indicated pressure differential will decrease slightly. If pressure differential continues to decrease (until the vent opens ) the No. 2 check valve is reported as leaking. Test No. 2 - Shutoff Valve No. 2 Purpose: To test shutoff valve No. 2 for tightness. Step After passing Test No., continue to test No. 2 by closing test cock No.2. Step 2 The indicated pressure differential will decrease slightly. If pressure differential continues to decrease (approaching zero ) the No. 2 shutoff valve is reported to be leaking. Note: A leaking No. 2 shutoff will give a false reading in tests No. 3 and 4 Test No. 3 - To test No. Check Valve Purpose: To test check valve No. for tightness. Requirements: Valve must be tight against reverse flow under all pressure differentials. Step Close needle valve A high side (red) and open test cock No. 2. Step 2 Close test cock No. 4. Disconnect bypass hose (yellow) at test cock No. 4. Step 3 Open needle valve B low (blue) and C bypass (yellow), bleeding to atmosphere, then closing needle valve B (blue) restores the system to a normal static condition. Step 4 Observe the pressure differential gauge. If there is a decrease in the indicated value, the No. check valve is reported as leaking. Test No. 4 - Pressure Differential Relief Valve Purpose: To test operation of pressure differential relief valve. Requirements: The pressure differential relief valve must operate to maintain the zone between the two check valves at least 2 psi less than the supply pressure. Step Close needle valve C bypass (yellow). Step 2 Open needle valve A high side (red). Step 3 Open needle valve B low (blue) very slowly until the differential gauge needle starts to drop. Step 4 Hold the valve at this position and observe the gauge reading at the moment the first discharge is noted from the relief valve. Record this as the opening differential pressure of the relief valve. It is important that the differential gauge needle drops slowly. Step 5 Close test cocks Nos. 2 and 3. Remove hose from test cocks Nos. 2 and 3. Step 6 Use bypass hose (yellow) to relieve pressure from test kit by opening needle valve A, B and C and bleed valves A and B. Step 7 Remove all test equipment and open No. 2 shutoff valve of the device. 6

Notes 7

WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: www.watts.com/prop65 Limited Warranty: Watts Regulator Co. (the Company ) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT. A Watts Water Technologies Company USA: Tel: (978) 689-6066 Fax: (978) 975-8350 Watts.com Canada: Tel: (905) 332-4090 Fax: (905) 332-7068 Watts.ca Latin America: Tel: (52) 8-00-8600 Fax: (52) 8-8000-709 Watts.com RP-IS-995 444 EDP# 95236 204 Watts