TECHNICAL CATALOGUE BHW Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW 05.16 Ref. 88386 Rev. 104
INDEX INTRODUCTION... 3 DESCRIPTION... 3 CABINET... 3 EXCHANGERS... 3 FANS... 3 AIR FILTER... 3 POWER SUPPLY... 3 OPERATING CONDITIONS... 3 STANDARDS AND CERTIFICATIONS... 3 TECHNICAL SPECIFICATIONS... 4 OPTIONALS... 5 FANS WITH EC MOTOR 3 SPEEDS VERSION... 5 PLENUM TUBULAR IMPULSION... 6 IMPULSION PLENUM... 7 VARIATIONS ON STANDARD MANUFACTURE... 7 DIMENSIONS... 8 BHW 174, 205, 358, 410... 8 BHW 515... 9 BHW 720, 724... 9 04.16 Ref. 88386 Rev.104 2
INTRODUCTION DESCRIPTION The air conditioning units of the series BHW, Fan-Coil type Low profile water-air, are supplied totally finished and ready for its installation after having had a strict final verification. The design and the disposition of the elements that compose it make them adaptable to a high number of practical needs, at the same time that they allow an easy access to the interior of the equipment for its later maintenance. Its low height allows its installation in false ceilings, with the unit supported or suspended. CABINET Manufactured with high quality steel sheet coated with aluminium, zinc and silicon alloy, finished with an electrostatically application and oven polymerized polyester powder. The interior of the set is thermo acoustically insulated. The condensation tray is treated with an asphaltic material. EXCHANGERS Manufactured with copper tubes mechanically expanded on aluminium fins which its special corrugated and wavy surface achieves high exchange performances. OPERATING CONDITIONS COOLING CYCLE TEMPERATURE Indoor air inlet 27ºC, DT / 19ºC, WT Water inlet 7ºC Water outlet 12ºC HEATING CYCLE TEMPERATURE Indoor air inlet 21ºC Water Inlet 50ºC STANDARDS AND CERTIFICATIONS ISO 9001:2008 CERTIFICATION: HIPLUS AIRE ACONDICIONADO S.L always search satisfaction on its costumers, it is accredited in the Quality System ISO 9001:2008 referred to their own productive activity. It is manifested in a continuous commitment to improve the quality and reliability of all our products; commercial activity, design, source materials, production and post sale service, are the way that allows us to accomplish our targets. CE QUALIFICATION: HITECSA units have CE brand in accordance with the expected for the relevant community directive, and its last modifications, as well as for each country's national legislation. FANS Centrifugal type, driven by 3 speeds motors of reduced sound level. They incorporate prelubricated bearings and are statically and dynamically balanced. AIR FILTER Air filter of foamed polyurethane of 10mm of thickness and a special reticulate S-20 of great filtration efficiency, removable and washable. POWER SUPPLY This units work with a voltage of 230V triphasic or 400V triphasic and 50Hz~. 04.16 Ref. 88386 Rev.104 3
TECHNICAL SPECIFICATIONS BHW 174 205 358 410 515 720 724 CAPACITIES Speed I KW 3,1 4,4 6,0 7,9 12,2 Cooling capacity (1) Speed II KW 4,1 5,0 5,9 9,1 13,9 20,2 25,0 Speed III KW 4,5 5,3 8,4 10,8 15,3 Speed I KW 4,5 6,4 8,6 11,1 16,1 Heating capacity (2) Speed II KW 5,8 7,1 9,7 12,6 18,2 26,5 32,7 Speed III KW 6,3 7,5 11,9 14,9 19,7 Speed I KW 7,6 10,8 14,6 18,8 27,2 Heating capacity (3) Speed II KW 9,8 12,1 16,5 21,4 30,8 44,8 55,5 Speed III KW 10,7 12,7 20,1 25,2 33,5 VENTILATION Fan model 146/220 146/220 185/240 185/240 216/236 2 X 9/9DD 2 X 9/9DD Speed I m 3 /h 600 950 1100 1400 2259 Cold air flow Speed II m 3 /h 900 1130 1340 1700 2596 3500 4850 Speed III m 3 /h 1050 1220 1850 2200 2800 Speed I m 3 /h 700 1050 1300 1600 2357 Hot air flow Speed II m 3 /h 1000 1230 1540 1900 2700 3850 5200 Speed III m 3 /h 1150 1330 2070 2400 2900 Available static pressure Speed I Pa 20 25 45 60 30 Speed II Pa 25 30 50 75 40 Speed III Pa 30 40 60 80 55 50 50 Motor fan power KW 0,18 0,18 0,25 0,25 0,55 0,25 0,36 HEAT EXCHANGER Water connections Ø ( ) 3/4 3/4 3/4 3/4 1 1 1/4 1 1/4 Cooling and heating water flow Speed I m 3 /h 0,53 0,76 1,03 1,36 2,09 Speed II m 3 /h 0,69 0,85 1,18 1,56 2,36 Speed m 3 /h 0,76 0,90 1,44 1,85 2,57 III ELECTRICAL SPECIFICATIONS Voltage V / f / Hz 230 / III / 50 3,37 4,19 Nominal power input KW 0,20 0,26 0,36 0,56 0,60 0,81 1,6 Nominal current input A 1 0,5 1,75 2,5 2,75 3,9 7,4 DIMENSIONS Width mm 829 829 915 915 1200 1350 1350 Length mm 791 791 791 791 826 900 900 Height mm 219 258 285 315 352 412 412 Weight Kg 30 34 44 45 62 80 80 (1) Cooling capacity for water temperature of 7ºC. (2) Cooling capacity for water temperature of 50ºC and indoor temperature of 20ºC. (3) Cooling capacity for water temperature of 70ºC and indoor temperature of 20ºC. 04.16 Ref. 88386 Rev.104 4
OPTIONALS FANS WITH EC MOTOR 3 SPEEDS VERSION BHW 174 205 358 410 515 720 724 CAPACITIES Speed I KW 3,1 7,9 12,2 Cooling capacity (1) Speed II KW 4,1 9,1 13,9 Speed III KW 4,5 10,8 15,3 Speed I KW 4,5 11,1 16,1 Heating capacity (2) Speed II KW 5,8 12,6 18,2 Speed III KW 6,3 14,9 19,7 Speed I KW 7,6 18,8 27,2 Heating capacity (3) Speed II KW 9,8 21,4 30,8 Speed III KW 10,7 25,2 33,5 VENTILATION Fan model EC082 EC 145 EC 208-240 Speed I RPM 851 832 635 Turning speed Speed II RPM 844 888 730 Speed III RPM 846 967 800 Speed I m 3 /h 600 1400 2250 Air flow Speed II m 3 /h 900 1700 2596 Speed III m 3 /h 1050 2200 2800 Speed I Pa 35 120 30 Available static pressure Speed II Pa 30 110 40 Speed III Pa 20 80 60 Motor fan power KW 0,08 0,25 0,25 HEAT EXCHANGER Type Water coil with copper tubes and aluminium fins. Speed I m 3 /h 0,53 1,36 2,09 Cooling and heating water flow Speed II m 3 /h 0,69 1,56 2,36 Speed III m 3 /h 0,76 1,85 2,57 Water connections Ø( ) 3/4 3/4 1 04.16 Ref. 88386 Rev.104 5
BHW 174 205 358 410 515 720 724 ELECTRICAL SPECIFICATIONS Voltage V / f / Hz 230 / I / 50 Speed I KW 0,06 0,13 0,14 Nominal power input Speed II KW 0,06 0,18 0,22 Speed III KW 0,06 0,21 0,32 Speed I A 0,44 0,80 0,98 Nominal current input Speed II A 0,44 0,94 1,49 Speed III A 0,45 1,19 2,13 SOUND LEVEL (4) Speed I db(a) 63 68,5 69,8 Sound power Speed II db(a) 64 69,8 71,8 Sound presure (a 2m) Speed III db(a) 64,8 71 74,5 Speed I db(a) 43,98 48,48 49,78 Speed II db(a) 43,98 49,78 51,78 Speed III db(a) 44,78 50,98 54,48 DIMENSIONS Width mm 829 915 1200 Length mm 791 791 826 Height mm 219 315 352 Weight Kg 30 45 62 (1) Cooling capacity for water temperature of 7ºC. (2) Cooling capacity for water temperature of 50ºC and indoor temperature of 20ºC. (3) Cooling capacity for water temperature of 70ºC and indoor temperature of 20ºC. (4) Sound pressure level with supply and return jacks free discharge, measured 2 meters away, in free field. PLENUM TUBULAR IMPULSION Discharge plenum through tubular mouthpieces, built in "aluzinc" steel sheet. MODEL A B C 174 160 219 829 205 200 258 829 358 200 285 915 410 250 315 915 04.16 Ref. 88386 Rev.104 6
IMPULSION PLENUM Plenum para descarga directa. Esta construido en chapa de acero aluzinc. Incorpora rejilla de salida en aluminio anodizado. MODEL A B C 174 100 219 829 205 100 258 829 358 100 285 915 410 100 315 915 515 200 350 1198 720-724 200 410 1348 VARIATIONS ON STANDARD MANUFACTURE Heating coils by electric resistances. Hot water coils by boiler. Vertical impulsion. For other special requirements, please consult. 04.16 Ref. 88386 Rev.104 7
DIMENSIONS BHW 174, 205, 358, 410 CONSTRUCTIVE DETAILS 1. Plenum tubular mouthpiece 2. Plenum impulsión 3. Coil 4. Turbine 5. Motor turbine 6. Power supply input 7. Water outlet (connection 3/4 ) 8. Water inlet (connection 3/4 ) 9. Drainage 3/4 male 10. Air filter MODEL A B C D E F G H I J K L 174 mm 829 789 877 127 433 219 183 200 122 28 156 315 205 mm 829 789 877 70 490 258 221 160 159 30 194 320 358 mm 915 875 963 213 347 285 249 128 194 25 221 355 410 mm 915 875 963 213 347 315 279 80 230 30 251 324 04.16 Ref. 88386 Rev.104 8
BHW 515 CONSTRUCTIVE DETAILS 1. Plenum impulsión 2. Turbine 3. Motor turbine 4. Water outlet (connection 1 ) 5. Water coil 6. Water inlet (connection 1 ) 7. Electrical coil 8. Air filter 9. Drainage 3/4 male BHW 720, 724 CONSTRUCTIVE DETAILS 1. Plenum impulsión 2. Motors turbines 3. Turbines 4. Water outlet (connection 1 1/4 ) 5. Water coil 6. Water inlet (connection 1 1/4 ) 7. Electrical coil 8. Air filter 9. Drainage 3/4 male 04.16 Ref. 88386 Rev.104 9
04.16 Ref. 88386 Rev.104 10
04.16 Ref. 88386 Rev.104 11
HIPLUS AIRE ACONDICIONADO S.L. Masia rrents, 2 Tel. +34 93 893 49 12 Fax. +34 93 893 96 15 08800 Vilanova i la Geltrú Barcelona, Spain www.hitecsa.com 04.16 Ref. 88386 Rev.104 12 We reserve the right to make modifications without prior notice. This document is a translation from the original document in Spanish.