R231 A.V.R. Installation and maintenance R 231. This manual is to be given to. the end user. Armature 6- Field. Slow-blow fuse 250V 8 A

Similar documents
4291 en /a R220 A.V.R. Installation and maintenance

VOLT POT 1K R220. OPEN FOR 60 Hz STAB A.V.R. R220. Installation and maintenance

R250 A.V.R. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

This manual is to be given to. the end user P.M.G. / ALTERNATORS. Installation and maintenance

A E. P.M.G. range. Low Voltage Alternators - 4 pole. Installation and maintenance

LSA R Air/air heat exchanger - AREP - 4 pole ALTERNATORS - Ex II 3 G. Installation and maintenance. This manual is to be given to.

LSA POLES ALTERNATORS

3946 en / a. This manual is to be given to. the end user. HPM x44. A.C. motor. Installation and maintenance

Users guide and maintenance manual. Leroy Somer Alternators LSA 43.2 / Pole SHUNT AREP - PMG

Low Voltage Alternators - 4 pole LSA 52.3

TAL 042. Low Voltage Alternators - 4 pole. Installation and maintenance. Three-phase 6 and 12-wire Dedicated single-phase 4-wire

LSA 50.2 Low Voltage Alternators - 6 pole

TAL 044. Low Voltage Alternators - 4 pole. Installation and maintenance. Three-phase 6 and 12-wire Dedicated single-phase 4-wire

SM Alternators. Manual and Instruction

TAL 046. Low Voltage Alternators - 4 pole. Installation and maintenance. Three-phase 6 and 12-wire

S.A.E. 5. This manual is to be given to the end user LSA 40-4 POLES ALTERNATORS. Installation and maintenance

LSA Low Voltage Alternators - 4 pole. Installation and maintenance

Low Voltage Alternators - 4 pole

LSA 42.3 Low Voltage Alternators - 4 pole

LSA 52.3 Low Voltage Alternators - 4 pole

LSA 50.1 / LSA Low Voltage Alternators - 4 pole. Installation and maintenance

LSA 46.3 Low Voltage Alternators - 4 pole

PM300E Voltage Regulator Instruction Manual

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

Low Voltage Alternators - 4 pole LSA 44.3

DYNEO Synchronous motors with permanent magnets-drive Commissioning

LSA & 4 POLE ALTERNATORS

EA07. Generator Automatic Voltage Regulator Operation Manual

VoltPro VP4 Automatic Voltage Regulator

LSA 37-2 & 4 POLE - ACC ALTERNATORS

SECTION E I N D E X. Alternator Illustrations General Information Safety Requirements Electrical Checks 6. 4.

ELECTRIC FENCE ENERGIZER SERVICE MANUAL MODEL 950 SERVICE MANUAL FOR OLLI 950 FENCE ENERGIZERS

Installation guide. Mb 3101, Mb Drive systems. Part number: 2910 en / p

LSA POLES ALTERNATOKS

Installation and maintenance guide LSK. D.C. motors. Reference: 5703 en / a

TA-05/C. Instruction and Operation Manual. valid for art.-no.: F-TA-05/C-ISO. (start at modification No. 1601)

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

XR500D-277V Special Voltage Regulator

GEARLEC - TRACTELEC GT3 / TF3 / TM3

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

PLSES 4500 IMfinity Platform. IP23 high-speed induction motors Industrial refrigeration Variable speed Frame size 225 to to 480 kw

XR500B Universal Voltage Regulator

MX431 Generator Automatic Voltage Regulator Operation Manual

CONTROLLING ENERGY IN MOTORISED APPLICATIONS en / a

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

CONTROL FEATURES AVAILABLE OPTIONS

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

MOP1224HD Heavy-Duty Motorized Potentiometer

3664 en / c LSA 37-2 POLE - ACC ALTERNATORS. Installation and maintenance

VoltPro VPBF8 Automatic Battery Flashing Module This Manual Covers Both VPBF8-12 and VPBF8-24 Models

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

Power Supply EL

Réf en /c LSA 37 SHUNT - 2 & 4 POLE ALTERNATORS. Installation and maintenance

ControlReg200/ControlReg200P. Installation and maintenance

MP24 Motorized Potentiometer

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

EG3002. Electronic Engine Governor Controller User Manual

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

FAULT FINDING MANUAL. For Stamford AC Generators

Power Supply EL

EA16. Generator Automatic Voltage Regulator Operation Manual

Hydro Power Synchronous Generators. Power range MW

Operating instructions Rotary actuators M135 M140 M150 M180. June 2012 / / EN

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

AFM500X Automatic Flashing Module

Allegion LCN Benchmark AU9100 Series

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1

SINAMICS DCM. DC Converter. Application SINAMICS DCM as field supply unit. Edition 04-6/2013. SINAMICS drives

INDEX Section Page Number Remarks

Monocellular centrifugal electro-pumps

Euclid Full Voltage Magnet Controller

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

INSTRUCTION MANUAL. I/P Converter DSG BXXY3Z DSG BXXY4Z

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3

INDUSTRIAL GENERATOR SERVICE

Series 2330MKII. Single-Phase. Adjustable-Speed. DC Motor Controllers (1/6 3 HP) BOOK 0958-B

Powerdrive FX Ultra compact regenerative drive solution

1 THE WOLVERTON SYSTEM OF TRAIN LIGHTING.

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029

ELECTROMAGNETIC VIBRATORY FEEDER INSTRUCTION AND MAINTENANCE MANUAL

Open Chassis Star-Delta Starter User Guide

Installation and maintenance guide D.C. MOTORS. Reference: 5702 en / a

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

Outdoor UPS. User Manual. Contents. Please read carefully this manual before installing and using this product. 1 Introduction Safety...

MODEL ELC-12/40-CVM-D BATTERY CHARGER

A48 / A48B (base plate) BATTERY CHARGER

Operating Instructions Pedestrian Turnstile Type MPT 33

20 Working Days Manufacturing Lead Time Commitment. Selection of IMfinity motors & options Low to High Power Ready to ship in 20 Working Days

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS

Boston Gear Ratiotrol

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator

A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

Transcription:

Armature 6- Field This manual is to be given to the end user F1 Slow-blow fuse 250V 8 A 110 0V E+ E- 75 mm 140 mm P1 P2 Voltage Stability R 231

This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. By following certain important points during installation, use and servicing of your, you can look forward to many years of trouble-free operation. SAFETY MEASURES Before using your machine for the first time, it is important to read the whole of this installation and maintenance manual. All necessary operations and interventions on this machine must be performed by a qualified technician. WARNING Warning symbol for an operation capable of damaging or destroying the machine or surround-ing equipment. Our technical support service will be pleased to provide any additional information you may require. The various operations described in this manual are accompanied by recommendations or symbols to alert the user to potential risks of accidents. It is vital that you understand and take notice of the following warning symbols. Warning symbol for general danger to personnel. This can be incorporated in a machine marked C.E. Warning symbol for electrical danger to personnel. Note: LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. The information contained in this document may therefore be changed without notice. 2

CONTENTS 1 - SUPPLY...4 1.1 - SHUNT excitation system...4 2 -...5 2.1 - Characteristics...5 2.2 - AVR option...5 3 - INSTALLATION - COMMISSIONING...6 3.1 - Electrical checks on the AVR...6 3.2 - Settings...6 3.3 - Electrical faults...7 4 - SPARE PARTS...8 4.1 - Designation...8 4.2 - Technical support service...8 All such operations performed on the should be undertaken by personnel trained in the commissioning, servicing and maintenance of electrical and mechanical components. Copyright 2005 : MOTEURS LEROY-SOMER This document is the property of : MOTEURS LEROY-SOMER It may not be reproduced in any form without prior authorization. All brands and models have been registered and patents applied for. 3

1 - SUPPLY 1.1 - SHUNT excitation system R 231 voltage regulator operats with a dedicated single phase shunt alternator. The regulator monitors the exciter excitation current according to the alternator out put voltage. The R 231 is a R 230 with a specific excitation ceiling set for the dedicated single phase alternator. SHUNT SYSTEM MAIN FIELD STATOR : 4 wires (marked T1 to T4) T1 T3 Varistor Armature 5+ 6- Field T2 T4 75 mm F1 Slow-blow fuse 250V 8 A 110 0V E+ E- 140 mm 4 x holes Ø 5.8 x 50 x 75 mm P1 P2 Voltage Stability R 231 P3 Underspeed ST4 Option Potentiometer for remote voltage adjustment ST3 Frequency 50Hz 60Hz 4

2-2.1 - Characteristics - Voltage regulation: around ± 0.5%. - Voltage supply/sensing range 85 to 139 V (50/60 Hz) - Rapid response time (500 ms) for a transient voltage variation amplitude of ± 20% - Voltage setting P1 - Stability setting P2. - Power supply protected by 8 A fuse, slowblow action (tolerates 10 A for 10 s) - Frequency: 50 Hz with ST3 jumper - 60 Hz without ST3 jumper - Factory-set underspeed protection P3. 2.2 - AVR option Potentiometer for remote voltage adjustment, 1000 Ω / 0.5 W min: adjustment range ± 5%. - Remove the ST4 jumper. 5

3 - INSTALLATION - COMMISSIONING 3.1 - Electrical checks on the AVR - Check that all connections have been made properly as shown in the attached wiring diagram. - Check that the ST3 frequency selection jumper is on the correct frequency setting. - Check whether the ST4 jumper or the remote adjustment potentiometer have been connected. 3.2.2 - Special type of use WARNING Excitation circuit E+, E- must not be left open when the machine is running : AVR damage will occur. 3.2.2.1 - field weakening (SHUNT) 3.2 - Settings 110 0V E+ E- The machine is tested and set at the factory. When first used with no load, make sure that the drive speed is correct and stable (see the nameplate). After operational testing, replace all access panels or covers. The only possible adjustments to the machine should be made on the AVR. 3.2.1 - R 231 settings (shunt system) Initial potentiometer settings - P1 potentiometer (AVR voltage adjustment): fully anti-clockwise. - Remote voltage adjustment potentiometer: centre position. Run the alternator at its rated speed. If the voltage does not increase, the magnetic circuit should be remagnetized (see section 2.3). - Turn the AVR voltage adjustment potentiometer P1 slowly until the output voltage rated value is obtained. - Adjust the stability setting using P2. - Sealed potentiometer P3 is factory set at 48 Hz for 50 Hz and 58 Hz for 60 Hz The exciter is switched off by disconnecting the AVR power supply (1 wire - 0 or 110V). Contact rating : 16A - 250V alt. 3.2.2.2 - field forcing 110 0V E+ E- (400V - 10A) - + Battery (B Volt) Battery must be isolated from the earth. t Exciter field Diode Exciter field may be at line potential. 6

3.3 - Electrical faults Fault Action Effect Check/Cause No voltage at no load on start-up Voltage too low Voltage too high Voltage oscillations Voltage correct at no load and too low when on load (*) Connect a new battery of 4 to 12 volts to terminals E- and E+, respecting the polarity, for 2 to 3 seconds Check the drive speed Adjust AVR voltage potentiometer Adjust AVR stability potentiometer Run at no load and check the voltage between E+ and E- on the AVR The alternator builds up and its voltage is still correct when the battery is removed. The alternator builds up but its voltage does not reach the rated value when the battery is removed. The alternator builds up but its voltage disappears when the battery is removed Correct speed Speed too low Adjustment ineffective If no effect : try normal / fast recovery modes (ST2) - Lack of residual magnetism - Check the connection of the voltage reference to the AVR - Faulty diodes - Armature short-circuit - Faulty AVR - Field windings disconnected - Main field winding open circuit - check the resistance Check the AVR connections (AVR may be faulty) - Field windings short-circuited - Rotating diodes burnt out - Main field winding short-circuited - Check the resistance Increase the drive speed (Do not touch the AVR voltage pot. (P2) before running at the correct speed.) Faulty AVR - Check the speed : possibility of cyclic irregularity - Loose connections - Faulty AVR - Speed too low when on load (or U/F bend set too high) - Check the speed (or U/F bend set too high) - Faulty rotating diodes - Short-circuit in the main field. Check the resistance - Faulty exciter armature. (*) Caution : For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to the operating terminals Voltage disappears during operation Check the AVR, the surge suppressor, the rotating diodes, and replace any defective components The voltage does not return to the rated value. - Exciter winding open circuit - Faulty exciter armature - Faulty AVR - Main field open circuit or short-circuited Warning : after operational testing, replace all access panels or covers. 7

4 - SPARE PARTS 4.1 - Designation Description Type Code R 231 AEM 110 RE 008 4.2 - Technical support service Our technical support service will be happy to provide any information you require. When ordering spare parts, you should indicate the complete machine type, its serial number and the information indicated on the nameplate. Part numbers should be identified from the exploded views and their description in the parts list. Our extensive network of "service stations" can dispatch the necessary parts without delay. To ensure correct operation and the safety of our machines, we recommend the use of original manufacture spare parts. In the event of failure to comply with this advice, the manufacturer cannot be held responsible for any damage. 8