Verax 75 and Verax VPA Installation Manual

Similar documents
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION

IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:

TubeTrace Tubing Bundles

Spun Bay Installation Standard Version (non dimmable), Hook Mount

MOONRING 1.5 MOONRING 3

INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1

SloanLED THINLED. Constant Current. Installation Guide

VA-4233-AGx Series Electric Valve Actuators

Power Connection Kit installation instructions

BITZER Capacity Controller for CSH Compressors Temperature Sensor

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

Flow Computer Installation

ClassicSeries Compressor Installation

Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series)

Wet Rated Batten LED Luminaire

MODELS 2 & 4 Top Conduit Linears

Lumination TM LED Luminaires LAL Series - Continuous Run Option

GVB-8 (Boost) Manual

GV-10 Manual 10.5A / 140W IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Solar Charge Controllers with Maximum Power Point Tracking

Cable Cubby 1202 and 1402 Installation Guide

CSD Series Current Devices Split Core

PowerAir Compressor Installation

INSTALLATION INSTRUCTIONS LIGHTPLANE 3.5. LP3.5 Suspended LED. A nd Avenue, Unit 1. CA P E W alwusa.

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

MODELS. 2 & 4 Low Profile Linears

SAVE THESE INSTRUCTIONS

LAL SERIES LED LUMINAIRE

Single-Phase Step Voltage Regulators

Lumination TM LED Luminaire RC/LRC/RX/LRX Series - New Construction Frame

I. Pendant Mount Installation

INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit

RAPID SHUTDOWN COMBINER

INSTRUCTION BOOK FOR. Dual Masking Electrol

Installation Instructions

COLUMN DESCRIPTIONS AND FUNCTIONS: COL # LENGTH TUBING TYPE COLUMN DESCRIPTION L1-1A 5M METAL CAP 1.0um MXT-WAX MM METAL CAP L1-1B 60M METAL CAP

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

MODELS SafeSite LED Linear, Class I Div V, 2 & 4 Versions

Switchgear Skid, C1192

poollux Power plx-pw60 & plx-pw100

Operating Instructions

DUST ALERT BinMaster Price Book binmaster.com Subject to change without notice 1

CYCLOPS Z Purge Indicator

WARNING/AVERTISSEMENT. Coupez l alimentation électrique à la boîte de fusibles ou au disjoncteur avant servicing or installing product.

Replacement Parts List

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT

GVB-8 (Boost) Manual

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators

Generator Fire Safety: Generator assemblies should be located outside the building.

IMPORTANT: SAFETY INSTRUCTIONS Important: Instructions de securité

Specification for Heated Instrument Tubing in Process Applications* (March 29, 2007)

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LED RETROFIT ASSEMBLY (LRA) Rev F

Revision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide

30A SMART ENERGY MANAGEMENT SYSTEM TM

INSTRUCTION BOOK FOR. Tensioned Dual Masking Electrol

CYCLOPS Z Purge Indicator

Automatic Changeover Medical Manifold Installation, Operation and Maintenance Manual

RF Point Level Control with Sensor Monitor

Specification Grade Contemporary Wall Mount/Technical Installation Data

Technical Offer. Antek Model 6200 Analyzer Determine Total Sulfur and Total Nitrogen in a single analyzer

C Power Connection Kit

IMPORTANT INSTRUCTIONS INSTALLATION AND STARTUP MODEL GDCP-A CONTROL PANEL

LS1 SERIES IMPORTANT: READ ALL INSTRUCTIONS THOROUGHLY AND CAREFULLY PRIOR TO INSTALLATION OF LINEAR SERIES FIXTURES AND RETAIN FOR FUTURE REFERENCE.

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

SERVOMEX 335A2014 PURGE ASSY Operator Manual

M Remote Mounting Kit

System 350 S350C Temperature Slave Stage Module

INSTALLATION GUIDE FOR VM-3000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

P66 Series Electronic Fan Speed Controls

Overview. Selection of System Components VT BBK/CWH. Chart LNG Vehicle Tank and Fuel System Installation Guidelines

FOR USE WITH MODEL NUMBERS:

M9109 Series Electric Non-spring Return Actuators

m WARNING! READ m BEFORE INSTALLATION

Rated for use on 110/120VAC 60Hz and 220/240VAC 60Hz applications

Mizer Single Pump and Starter Box

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440

Operations and Service Manual. X30208 Load Bank

Replacement Parts List

HOMELINK DOOR OPENER KIT

OmniAire Omnitec Design, Manufacturing Air Purification Equipment Since 1988

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing

Weather-Proof Thermal Mass Flow Meter for Pipe - Duct

Cable Cubby 1200 and 1400 Installation Guide

Lumination TM LED Luminaires Suspended LED Fixture (Series EP14)

Special Specification 6058 Battery Back-Up System for Signal Cabinets

HTP PTP/ PTJ Power Connection Kit for Pipes

INSTALLATION INSTRUCTIONS

Tetra minimax. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

Installation Instructions: ACCENT SYSTEM

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

IMPORTANT: SAFETY INSTRUCTIONS

Going the Distance - Solving Power Reach Issues With Diverse DAS Solutions

INSTRUCTION BOOK FOR. Tensioned Large Advantage Deluxe Electrol

Lifeline Medical Systems

Idle Timer Controller - A-ITC520-A Ford E Series Ford F250 - F Ford F250 - F550 (*B-ITC520-A) F650/F750

INSTALLATION INSTRUCTIONS

CLIMAGUARD Outdoor Heat Exchangers

Rated for use on 110/120VAC 60Hz and 220/240VAC 60Hz applications

INSTALLATION INSTRUCTIONS

Idle Timer Controller - ITC515-A Ford Transit Contact InterMotive for additional vehicle applications

Transcription:

Verax 75 and Verax VPA Installation Manual JP3 Measurement 4109 Todd Lane Austin TX 78744 512-537-8450 www.jp3measurement.com 1

Table Of Contents: 1. Facilities Requirements page 3 2. Unpacking and Handling page 5 3. Mounting the Control Panel page 7 4. Mounting the Probe Assembly page 9 5. Probe Assembly to Control Panel Connections page 11 6. Z-purge installation (optional) Page 16 7. Heater Blanket for Probes (optional) Page 18 8. Power Up and Commissioning Page 19 2 2

1) Facilities Requirements: Intended Use: The Verax 75 is an optical NIR analyzer for determining the constituents and physical properties of a hydrocarbon fluid stream by using NIR spectroscopy to model the parameter of interest. Contact a JP3 sales representative to discuss the range of analysis available. The Verax 75-Z model incorporates a Z-purge system for mounting in a Class I / Division 2 location. Location Rating: Verax 75 Analyzer is in a Type 4 NEMA Enclosure, and all provided fittings are Type 4 rated. For General Purpose Location, Conforms to ANSI/UL Std 61010-1 For Class I / Division 2 A,B,C,D, T Code- T4 a Type Z- pressurization must be used. With Z-purge, Conforms to NFPA Std 496 Certified to CAN/CSA Std C22.2 No. 61010-1 Operational temperature range: -29C to 50C (-20⁰ F to 122⁰F). Electrical Input Requirements: Per Customer Specification one of the two options below: 100-240V AC, 50-60 Hz, 1.6-0.7 Amp Or, 24V DC, 3.5 Amp The input electrical configuration is indicated on the warning tag below the antenna on the left side of the box (see Figure 3) For surge protection a 20A breaker is recommended as the customer-provide disconnection device Other Facilities Requirements (for Z-purge only): Instrument Air or Nitrogen Supply pressure: 80-120 psig Safe Pressure Set Point: 0.25 water column Safe pressure flow rate: 0.13-3.5 SCFH Exchange Flow Rate: 4 SCFH 3

Explanation of Warning Labels: The following warning applicable only when using the Z-purge option: WARNING PRESSURIZED INCLOSURE This enclosure must not be opened unless the area atmosphere is known to be below the ignitable concentration of combustible materials or unless all the devices within have been de-energized AVERTISSEMENT : BOÎTIER SOUS PRESSION: Ce boîtier ne doit pas être ouvert à moins que l'atmosphère de la zone ne soit inférieure à la concentration inflammable de matières combustibles ou à moins que tous les dispositifs qui s y trouvent n aient été mis hors tension. The following warning applicable only when using the Z-purge option: WARNING: Power must not be restored after enclosure has been opened and until enclosure has been purged for 3.5 minutes for Verax 75-Z model or 6 minutes for Verax 75M-Z AVERTISSEMENT: L'alimentation ne doit pas être rétablie après l ouverture du boîtier et jusqu'à ce que le boîtier ait été purgé pendant 3,5 minutes pour le modèle Verax 75-Z ou 6 minutes pour le modèle Verax 75M-Z. The following warning applicable to all models: The model and electrical configuration on the warning label are specified with punched holes next to the applicable value. Le modèle et la configuration électrique sur l'étiquette d'avertissement sont spécifiés avec des trous percés à côté de la valeur applicable Figure 1: Warning Label Located on the left side of the analyzer below the antenna port. (see Figure 3) 4

2) Unpacking and Handling: Shipped Materials: Verax Analyzer Control Panel (qty 1) Probe Assembly (qty 1) Antenna (qty 1) Z-purge w/ fittings (optional, 1 set) Handling Instructions: Weight: 51lbs Dimensions: 24 x 30 x 9.35 Mounting Holes: 18 x 31.25 Uncrate and mount the analyzer to unistrut or other mounting surface capable of handling the weight of the unit. Do not drop. 24 18 9.35 31.25 30 Front View Side View Figure 2 Verax 75 Analyzer Control Panel - Dimensions 07/01/2015 Verax Single ChInstallation Manual, Rev H 5

Antenna Fitting Wiring Terminal Blocks Incoming Power Connection Serial # & Warning Label Radio / Modem PC PLC Ethernet Switch (Comm) RTD and Transducer Terminal Block Spectrometer Figure 3 Verax 75 Analyzer Control Panel Front View 6

3) Mounting the Control Panel: Mounting Requirements: Select a location that is easily accessible at grade level. Mounting holes are provided for easy installation. The Probe Assembly must be mounted next to the analyzer separation is limited by 10 linear feet of fiber. Shade is required if mounting outdoors where ambient temps can exceed 90⁰ F. Do not mount the analyzer in such a way to make it difficult to operate the customer-provided electrical disconnect device (witch, breaker or other) Antenna Connection: 1. 16dB Antenna is provided along with a 90 degree fitting. 2. Attach Antenna to the fitting on the upper left of the Analyzer Panel using the 90 degree fitting (see Figure 3 for location of the fitting). 1. Fiber Optic Connection: 2. The Fiber is passed through the flex conduit/liquid tight fittings on the bottom of the analyzer control panel. Customer provides flex conduit. 3. Send Fibers will be labeled with 2 Red Shrink Tube reading SEND. 4. Receive Fibers will be labeled with 2 Yellow Shrink Tube reading RECEIVE. 5. Pull the fibers through the flex conduit, and let the excess hang coiled up under the analyzer until ready to connect to the probe assembly. 6. Leave the caps on the end of the fiber. Do not let the fiber drag on the ground. 7. See Section 5 for instructions to connect the fiber to the probe assembly Figure 4 Fiber Optic Cables installed with the Liquid Tight Fitting and Flex Conduit 7

Pass-through for Electrical Wires: The Verax Control Panel is shipped without holes or wire ways for most of the incoming electrical service or fiber connections. The only pre-positioned holes are: The Antenna fitting (top left), and Two fittings for the fiber (bottom left) Additional wire pass-throughs will need to be installed by the customer. The placement of these holes is left up to the customer s installation teams in order to provide maximum flexibility to bring the cables and fiber from below or above, and attach them to the Verax Control Panels with a sufficient size conduit or fitting. All connections or fittings chosen by the customer should by rated for Type 4 enclosure. After the wires and fibers are run, all ports and pass-throughs must be plugged with duct putty or some other standard industry practice to assure the sealed integrity of the enclosure. The customer must plan for the following cables when choosing the size and placement of ports on the Verax Control Panel: One Incoming Electrical Cable One Incoming communications Cable One RTD cable from the probe assembly One Transducer cable from the probe assembly Read instructions in Section 6 regarding where these fibers/cables attach inside the control panel before you start cutting holes. The customer is responsible to protect the inside of the control panel when cutting or punching holes for the wire way. DO NOT ALLOW METAL SHAVINGS TO FALL ON THE ELECTRICAL CONNECTIONS OR COMPONENTS INSIDE THE CONTROL PANEL. Contact your local JP3 sales representative to discuss options 8

4) Mounting the Probe Assembly: Placement: The Probe Assembly are typically mounted to a unistrut frame, or other solid structure Probes should be accessible at grade level. Pressure and Temp Rating: All probe windows and probe assemblies are tested to 1500 psi Operational temperature range: -29C to 50C (-20⁰ F to 122⁰F). Bypass Probe Configuration: For a bypass probe assembly, the customer taps into the process stream they want to monitor, plumbs the fluid to the inlet on probe assembly, and back to the process stream. (see Figure 4 on the next page) It is highly recommended that the customer supply a stinger at the inlet and return of the pipe you are monitoring in order to pull fluid from the center of the pipe. Either ½ or ¼ Swagelok fittings are supplied on the inlet and return ports of the probe assembly. Customer supplies ¼ or ½ stainless steel tubing as dictated by the fittings supplied on the probe assembly. ½ is typical for liquids ¼ is typical for gas The customer must assure sufficient flow of liquid or gas over the probe windows by providing a pressure drop of at least 2 inaq (or 20 SCFH) from inlet to outlet. Choosing the correct inlet and return points on the process pipe is critical to assure flow. Often choosing inlet and return points such that flanges, valves, meters or similar instruments are located between these two points is sufficient to provide the necessary bypass pressure differential. Actual Installation details vary by location and application; consult with JP3 Sales representative to discuss options. When using a heater blanket with the probe assembly, 120VAC, 2 Amp service is required. The junction box must be within 4 feet of the probe assembly. 9

P from Inlet to Return must be at least 2 inaq (inches of water) Inlet Stinger to sample from center of the pipe Return Figure 5 Example Probe Bypass Arrangement 36 31.7 Receive Fiber Sealcon Fitting Inlet Port Transducer 21 RTD Service Port DO NOT REOME CAP Send Fiber Sealcon Fitting 13.2 Service Port DO NOT REMOVE CAP Return Port Conduit Housing 4.4 Top-Down View Figure 6 Bypass Probe Assembly 10

5) Probe Assembly to Control Panel Connections Connect Fiber Optics to Probe Assembly: Warning Read Carefully Fiber optic cable is extremely sensitive to sharp bend angles and contamination. Handle very carefully to avoid kinks and keep the ends capped until ready to attach to the probes. Maintain a minimum 7 bend radius when running/routing the fiber from control box to probe assembly It is recommended that the fiber optic cable be run in it s own dedicated conduit, or elevated cable trays. Do not place fiber in ground level open cable trays where it can be stepped on. Keep the fiber ends capped until you a are ready to connect the ends. Attach Fiber to Probe Assembly: 1. Open the conduit housing on the probe assembly 2. Install the fiber using LT50 fittings and flex conduit at either end of the probe assembly (see Figure 6). The flex conduit approach offers the best protection for the fiber. 3. Connect the fiber to the back of the probe inside the conduit housing by screwing the fiber end onto the threaded probe connection. (see Figure 7) 4. DO NOT THROW AWAY THE KNURLED CAPS. These should be left in the conduit housing to be used to protect fiber and probe connections when disconnected during servicing. 5 Replace conduit housing cover Liquid Tight Fitting Figure 7 Fiber Installation on Probe Assembly Fiber/Probe Connection Point 11

JP3 Measurement Fiber Optic Cable Specification JP3 uses a custom optical fiber assembly, design and characterized to maximize the characteristics of the optical loop from laser to probe and back to the detector. The following are specifications important for handling and installation of the fiber: 600um-core multimode fiber with a Kevlar jacket. 5.5mm black PVC weather proof furcation jacket, UV resistant Outdoor rated construction, and all components nonconductive (most similar to OFNR indoor construction) Weight = 22 lbs/1000 feet Max Installation Tension, 180 lbs (800N) Max Operating Tension, 90 lbs (400N) Installation Temp Range, 15⁰ F to 176⁰ F (-20 to 80 C) Operational temp range, -20⁰ F to 122⁰ F (-29C to 50C) Minimum Bend Radius = 7 Male SMA connections on both ends. Each end will be labeled as below: Figure 8 Fiber Assembly dimensions and labeling 12

Wire the Probe Assembly to the Control Panel: 1. The Analysis Points on the RTD and Transducer terminals are numbered 1-2 from top to bottom 2. Run the RTD and transducer cables through customer-provide wire pass through port and route to the terminal blocks on the left side of the panel. 3. Connect the RTD cable to number 1 on the RTD terminal block, as shown in Figure 9: one red wire to the top terminal tier the other red wire to the middle terminal tier the white wire to the bottom terminal tier 4. Connect the transducer cable to number 1 on the transducer terminal block as shown in Figure 9: Red wire on the top terminal tier Black on the second terminal tier Brown on the third terminal tier Gray on the bottom terminal tier Figure 9 RTD and Transducer Wiring Instructions 13

Connect the Ethernet Communications Cable: 1. Run the Ethernet communications cable through customer-provide wire pass through and route to the Ethernet switch on the right side of the analyzer control panel. ( See Figure 3) 2. Connect to any available Ethernet port Connect Main Power: For 24V DC Power Configuration 1. Run the power cable through customer-provide wire pass through port and route to the terminal blocks on the upper right side of the analyzer control panel. ( See Figure 3) 2. Connect hot wire to 24V fuse 3. Connect neutral wire to 0V terminal Figure 10 Main 24VDC Power Wiring Instructions Components shown inside dotted line only included with100-240v AC option 14

Connect Main Power: For 100-24VAC Power Configuration 1. Run the power cable through customer-provide wire pass through port and route to the terminal blocks on the upper right side of the analyzer control panel. ( See Figure 3) 2. Connect hot wire to 100-240V fuse 3. Connect neutral wire to 0V terminal 4. Connect ground wire to the green/yellow ground terminal Figure 11 Main 100-240VAC Power Wiring Instructions Components shown inside dotted line only included with100-240v AC option 15

6) Z-Purge Installation (optional): Warning Read Carefully You must install the Z-purge if the Verax 75 will be in a Class I / Division 2 Hazardous location. Installation: Mounting Configuration and Pipe Routing are shown below in Figures 11 and 12. All fittings are ¼ Figure 12 Pipe Fitting Schematic, (Viewed from back of Verax Panel) 16

Figure 13 Z-Purge Hardware Configuration. 17

7) Probe Heater Blanket (optional): Installation: Heater blankets are designed to wrap around the sample cell cross to keep the probes warm and free of paraffins. Electrical: Heater blankets use Thermon self-regulating 12W/ft heating tape 2Amp, 120V AC electrical service A 5 pigtail is provided using ½ flex conduit. Figure 14 Heater Blanket 18

8) Power-up and Commissioning: Power Up Sequence: To Engage Power engage the fuses in the following order 1. 100-240V fuse (if applicable for the AC configuration only) 2. 24V fuse (Power to PLC, Switch) 3. 12V fuse (Powers PC and Radio) 4. 12V fuse (Powers Spectrometer) Figure 15 Power up sequence 4th 3rd 2nd 1st At this point the Verax 75 Analyzer is ready to be commissioned. Contact JP3 Field Service team to complete installation and commissioning. Contact JP3 Field Service team for all maintenance and servicing needs service@jp3measurement.com 512-537-8450 19