HR25 Solo. Installation and User Instructions. Through the Wall Heat Recovery Ventilators

Similar documents
Single Phase Electronic Speed Controllers

HRE 350 & HRE 350B. Heat Recovery Unit. Installation and User Instructions. 230V~50Hz

XS Fans Switches & Sensors

MRXBOX-VSC Visual System User Control Installation and Maintenance

Car Battery Charger Instructions for Use

Vent-Axia Roof Units Range Energy Recovery Ventilation (ERV) Range

DX Ceiling Fan Kit 50Hz/60Hz Supply / Extract Units Installation and Maintenance

INSTALLATION, OPERATION & MAINTENANCE INSTRATIONS

Java Basin Mixer Range

Java Basin Mixer Range

Flue installation instructions. Air flue duct for use with ecomax and ecotec boilers. For the installer

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

1901 Thermostatic Shower Mixer

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

HD18F2M1.

Installation manual wall-mounted distributor

Sieve Shaker 200mm/300mm - 8/12 inch SV003

MAGNETO REPLACEMENT. Pre-Unit Twin Cylinder Motorcycles. ELECTRONIC IGNITION SYSTEM For 4 Stroke. With 12 VOLT Electrics, POS/ NEG Ground

TWIN FAN CONTROLLER. Models:- ITC and ITC-DS Maximum load : V 50Hz ~ 9A and V 50Hz 3 ~ 9A

The following lighting types are NOT compatible with the TT- 402Wireless Inline Dimmers:

Technical Data. 13 Amp Fused Connection Units

K25000 & KD25000 Series

VT Oil-Free Range Operators Handbook

MAINTAINED LED DOUBLE SIDED SUSPENDED CEILING MOUNTED EMERGENCY LIGHT

RELAY BOX PRODUCT MANUAL IMPORTANT

Shelbourne header monitor kit Up to 2004

PSU EN54-4 Power Supplies

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

Q-AIRE-V125, EV125F & EV125FH 125mm diameter Filtered Inlet/Extract Air Valve. n Low profile. n Adjustable for commissioning purposes

INFO. SHEET: E1:1 INSPECTION & TESTING OF ELECTRICAL EQUIPMENT

ATM Lighting sp. z o.o

Eazipole Cordless. Installation & Set Up Instructions. Electric Blinds & Curtains

RUSH WALL TOP ASSEMBLIES EXT D 15MM PRODUCT CODE: FINISH: RU067 MB MATTE BLACK 3/4 TURN OPERATION PREMIUM FINISHES

Warning. Document ref: A October 2015

NALTF & NALTRF Belt Drive Roof and Plantroom Twinfans

Element C8.3 Installation, Use and Inspection of Electrical Systems

MAINTAINED LED EMERGENCY CEILING MOUNT SPOTLIGHT

MPS14 Rack Mount Power Supply

ZonePlus Z322 zone valve Installation and commissioning instructions

LED AC DRIVERLESS FLOODLIGHTS WITH PIR FOR MODEL: FLAC10BPIR, FLAC20BPIR, FLAC30BPIR & FLAC50BPIR

Chapter 5 Part B: Ignition system - transistorised type

DX Window Fan Kit 50Hz/60Hz Supply / Extract Units Installation and Maintenance

Curvare Tap Range. Fitting Instructions & Contents List

Drimaster365. Low Energy Positive Input Ventilation Unit. Installation and Maintenance Details. 150mm dia. Flexible Ducting

ACE. CORNER ENTRY Installation and User Guide. These instructions must be left with the user W2-B

ACE. DOUBLE DOOR QUADRANT Installation and User Guide. These instructions must be left with the user W2-E

New Options Bath Shower Mixer

OPERATION & MAINTENANCE INSTRUCTIONS

Contents. Overview. Safety Instructions. Before Installation. Installation. Operation. Maintenance. Replacement Parts. System Specifications 8 01

VIVID SLIMLINE FLOOR MOUNTED BATH MIXER PRODUCT CODE: FINISH: VS745 CHR CHROME STYLISH PREMIUM FINISH CONTEMPORARY DESIGN PHOENIX WARRANTY

BENCH GRINDER MODEL CBG6RP OPERATING & MAINTENANCE INSTRUCTIONS 0101

GLOSS WALL BATH SET PRODUCT CODE: FINISH: GS783 CHR CHROME CONTEMPORARY DESIGN PHOENIX WARRANTY STYLISH PREMIUM CHROME FINISH MATCH WITH...

Excel Wall and Deck Mounted Bath Shower Mixers Installation and User Guide

CSA CERTIFIED Conforms to UL 507

10W LED Die Cast Small Rectangle Bulkhead Light

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

Installation & Operating Instructions

Cellwatch Electrical Installation

PIL0478 ISSUE 01/ 07/16

OPERATION & MAINTENANCE INSTRUCTIONS

ATM Lighting sp. z o.o

8000 / 10,000 / 12,000

RUSH SHOWER/BATH DIVERTER MIXER PRODUCT CODE: FINISH: RU791 CHR CHROME CONTEMPORARY DESIGN PHOENIX WARRANTY STYLISH PREMIUM CHROME FINISH

ATM Lighting sp. z o.o

Clos-o-Mat Lima Lifter installation & user guide

DC-AC Power Inverter SAM Manual. Please read this manual before installing your inverter

To the Fitter: Ensure all relevant personnel read the points listed below and that a copy is passed on to the end user.

NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT

For reference, there is a photograph of a completed upgrade on the last page of this document, refer also to drawing that is attached.

Battery Charger JCB-FCH20LI2

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

ORIGINAL INSTRUCTIONS

Guidance to Installers of Viridian EV Charging Stations

Rescue Pac. Please read and fully understand the instructions in this manual before operation. Keep this manual safe for future reference

RMHDT90SS/ - RMHDT100SS/ - RMHDT110SS/ Instructions Manual.

Duo water control system

Battery Charger JCB-FCH12Li

LEIHDS110SC/ LEIHDS110BC/ Instructions Manual.

PHV V NT VERTICAL AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

AXIAL FANS Axis / Tubo OPERATION MANUAL

BENCH GRINDER MODEL CBG6RZ OPERATING & MAINTENANCE INSTRUCTIONS

MAGNETO REPLACEMENT TWIN CYLINDER MOTORCYCLES ELECTRONIC IGNITION SYSTEM FOR 4 STROKE WITH 6 VOLT ELECTRICS, POS/ NEG EARTH SYSTEM TYPE: PAMT1-6

Installation, Operating & Maintenance Instructions. Norbro J-Switch FM 00707

Technical Data. Dimmer Switches - Push Type 881P/885P 882P 883P 884P

The Gallery System DIRECTIONS. Components of the System

Self Closing Tap. Fitting Instructions & Contents List. Please keep these instructions for future reference and request of replacement parts

VANDAL RESISTANT FITTINGS VR105, VR125, VR145 (VR106, VR115 Export only) PRODUCT MANUAL IMPORTANT

FORD TERRITORY TOWBAR FITTING INSTRUCTION Part # VEHICLE YEARS OF MANUFACTURE - From May

Features: Concealed installation. Compact design. Available in electric, LPHW or ambient.

MAINTAINED LED CIRCULAR EMERGENCY CEILING LIGHT

Operating instructions in the back. PD1420LP

GL1200T Cut & Seal. (GL1200 Seal only)

82V LITHIUM-ION BATTERY CHARGER GC 400

SOLAR BOLT CHARGING SYSTEM INSTALLATION GUIDE

Uniprep 2 Rotary scraping tool for pipes mm

C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Operating instructions in the back. PD1820LF

VOLKSWAGEN AMAROK TOWBAR FITTING INSTRUCTION

Transcription:

abc GB HR25 Solo Installation and User Instructions Models:- HR25 Solo HR25 Solo L HR25 Solo H HR25 Solo LH Through the Wall Heat Recovery Ventilators PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTION 1

Contents Section Page 1.0 Introduction 3 2.0 Site Requirements 4 3.0 Installation 5 4.0 Maintenance 11 5.0 Spares list 12 2

1.0 Introduction 1.1 Description 1. The Vent-Axia HR25 Solo range of products are through the wall heat recovery ventilators for use in areas such as bathrooms and WCs. 2. The units are fitted with a 24V DC motor and are supplied with a Switch Mode Power Supply (S.M.P.S.). On normal setting the power consumption is 2 Watts. A 5m cable is provided for fixed wiring of the unit to the S.M.P.S. 3. The twin impeller and heat exchanger arrangement simultaneously supplies and extracts air while transferring heat from the stale exhaust airflow to the fresh intake airflow. This provides up to 84% heat recovery from the stale extracted air. 4. The range of products is as follows:- HR25 Solo The HR25 Solo is fitted with a pull cord switch which provides a twin speed control function. Fig.1 HR25 Solo H The HR25 Solo H is fitted with an adjustable humidity sensor which automatically switches between low and high speeds depending on the relative humidity in the room of installation. HR25 Solo L & HR25 Solo LH These are extended versions of the above models. They are designed for installations where the wall thickness is between 311mm and 425mm. 3

50mm minimum 2.0 Site Requirements 2.1 Information 1. The unit is designed for installation in external walls with a thickness of up to 310mm. For wall thicknesses above 310mm, the L version of the appropriate model must be used (see page 12 ). The L models are suitable for wall thicknesses up to 425mm. 2. The unit must be sited and connected by a suitably competent person and be in accordance with current U.K. Building Regulations and I.E.E. Wiring Regulations (BS 7671). 50mm minimum 3. The unit must be installed in conjunction with the separate power supply enclosure supplied, which is intended for permanent connection to the mains electrical supply. The unit and the power supply enclosure are intended for fixed wiring installation. Fig.2 4. The power supply enclosure requires free air circulation for effective operation It must not be recessed into the mounting surface or covered with any form of insulation, which might be used in a ceiling or roof void. 5. Wiring to the unit in the U.K. must be via the switched fused spur supplied as part of the power supply enclosure. 6. The spur supplied is designed with a minimum contact gap of 3mm in all poles. 7. Ensure that the mains electrical supply is compatible with the rating label attached to the product. Ceiling 8. The unit must be sited such that the ambient temperature will not exceed 40 C. 300mm minimum 125mm minimum 300mm minimum 9. Screwdriver access must be provided to the left of the power supply enclosure for the removal of the cover screw (Fig. 2). 10. Do not site the appliance in the vicinity of excessive levels of airborne oil or grease. or directly over a cooker. 11. If the unit is installed in a room containing a fuel burning appliance, the installer must ensure that air replacement is adequate for both appliances. 12. The unit must not be installed at a level below 500mm from the floor. Fig.3 13. The internal grille surround must be sited at least 125mm away from the room ceiling (Fig. 3). and 300mm away from any adjacent vertical surface. 14. The external cowl of the unit must be sited at least 500mm away from any flue of gas or solid fuel appliances. This is to avoid back flow of gases entering the room. 15. All safety regulations and requirements must be strictly followed to prevent hazards to life and property both during and after installation and during subsequent maintenance or servicing. 16. Ensure the mains electrical supply is switched off before commencing installation or maintenance. 2.0 Site Requirements 4

Outside Inside 3.0 Installation 3.1 Initial Preparation 1 o The unit is designed for installation in a 152mm (6 ) core drilled hole. All installation can be undertaken from inside the building except for fixing of the external bezel if required. 1. After considering the site requirements (see previous section), select a suitable position for the unit and power supply enclosure (5m maximum between unit and power supply). 2. Mark the position of the mounting hole. Fig.4 3. Cut the mounting hole to a diameter of 152mm (6 ) using a core drill. Ensure that there is a slight fall on the hole, from inside to outside (Fig. 4). 4. Remove the unit from the carton 5 Release cover using the two release clips (Fig 5) Unplug the sensor cable from the PCB if present 6 Using the mounting plate on the product. Mark the position of the four mounting holes, and then put product to one side. Drill and plug the holes 7. Install the fixed cable runs using mini trunking or via concealed installation. A 3-core red, white and black low voltage cable is supplied for connections between the unit and the power supply. 8. Ensure the cable to the unit extends sufficiently from the mounting hole to enable the required connections within the control enclosure. Fig.5 5

3.0 Installation 3.2 Installing the Power Supply Unit 1. Remove the power supply unit assembly from the carton. 2. Remove the power supply unit packaging. 3. Remove isolator and power supply covers (Fig. 6). 4. The mains input to the power supply unit must be routed via the rear or side of the enclosure behind the switched connection unit. NOTE: Mains wiring must be kept separate from the S.M.P.S. side of the enclosure. The mains connection is to the input side of the isolator unit. 5. Remove one of the cable knockouts and feed the 3-core cable through the power supply enclosure (Fig. 7). 6. Mark the fixing hole positions then Drill and plug the wall to secure the power supply enclosure using the fixing screws provided. 7. Connect the 5m cable supplied to the red, white and black low voltage supply via the terminal block. Route it via one of the exit holes (Fig. 7) Fig.6 8. Ensure that the mains wires from the S.M.P.S. run through the slot in the divider wall (Fig. 6). 9. Fit the power supply cover using the small self tapping screw through the side of the power supply enclosure (Fig. 6). 10. Make the feed connections from the mains supply to the rear of the isolator unit. Connect live to L IN terminal, neutral to the N IN terminal and earth to the brass earthing terminal. 11. Fit the isolator unit to the power supply enclosure using the screws provided (Fig. 5). Isolator unit section Fig.7 6

3.0 Installation 3.3 Installing the HR25 Solo Outer cover 1. Remove the bezel and fixing pack from the carton. 2. Measure the total wall thickness. The outer of the two rubber seals is adjustable and should be set in a position that is 25mm in from the outer face of the external wall (Fig. 10). 4. Secure the rubber seal to the unit using the adhesive provided. External bezel 5. Locate the unit in the mounting hole, but do not push it fully in. 6. Route the low voltage cable from the power supply enclosure to the unit. Heat exchanger 7. Pass the low voltage cable through the cable entry grommet at the top of the unit (Fig. 12). Release clips 8. Secure the unit to the wall using the four fixing screws provided. 25mm Outside wall Rubber seal Fig.10 9. Strip the low voltage cable sheath back 40mm from the end and separate the three individual wires stripped to 6mm. 10. Connect the wires to the terminal block. Connect red to red, white to white and black to black (Fig. 11 and 12). 11. Reassemble in reverse order 13. A bezel is provided to neaten the appearance of the outside wall around the unit. If required this should be fixed in place using a suitable silicone/mastic sealant. Fig.11 Cable entry Motor wires Wiring label Low voltage terminal block Black motor lead termination Pull switch Fig.12 Red motor lead termination 3.0 Installation 7

3.0 Installation Outer cover Sensor Connection cable PCB 3.4 Installing the HR25H Solo 1. Remove the bezel and fixing pack from the carton. 2. Measure the total wall thickness. The outer of the two rubber seals is adjustable and should be set in a position that is 25mm in from the outer face of the external wall (Fig. 13). External bezel 4. Secure the rubber seal to the unit using the adhesive provided. 5. Locate the unit in the mounting hole, but do not push it fully in. Heat exchanger 6. Route the low voltage cable from the power supply enclosure to the unit. 7. Pass the low voltage cable through the cable entry grommet at the top of the unit (Fig. 15). Release clips 25mm Rubber seal 8. Secure the unit to the wall using the four fixing screws provided. 9. Strip the low voltage cable sheath back 40mm from the end and separate the three individual wires striped by 6mm. Outside wall 10. Connect the wires to the terminal block. Connect red to red, white to white and black to black (Fig. 14). Fig.13 11. The HR25H Solo unit is factory set to switch between low and high speed. O/L O/H L/H Position jumpers for low/high speed setting SPEEDS Terminal Block Low / High speed (continuously running) 12. The switching point of the unit can be adjusted between 60% - 90% humidity. It is factory set to operate at 70% humidity at 25 C. O/L O/H L/H BLK WT Outer cover Sensor Cable entry grommet 13. To adjust the humidity level, rotate switch (A) as follows (Fig. 14) :- BLK RED RED a) For the unit to operate at a lower humidity level, turn switch (A) anti-clockwise (Min. 60%). CON 4 b) For the unit to operate at a higher humidity level, turn switch (A) clockwise (Max. 90%). Switch (A) 14. Reassemble in reverse order ensuring the humidity sensor cable is plugged into CON 4. 15. A bezel is provided to neaten the appearance of the outside wall around the unit. If required this should be fixed in place using a suitable silicone/mastic sealant. Fig.14 Fig.15 8

3.0 Installation Motor wires 3.6 Installing the HR25L Solo & LH Solo Wiring label For wall thicknesses between 311mm & 425mm Low voltage terminal block Black motor lead termination Fig.21 Red motor lead termination Pull switch Motor housing 1. Disconnect the red and black motor wires (Fig. 21). 2. Carefully withdraw the heat exchanger from the unit (Fig. 22). 3. Slide the inner tube out of the unit by pushing the motor housing (Fig. 23). 4. Remove the plastic ring and rubber seal from the outer tube (Fig. 24). Heat exchanger Fig.22 Chassis Inner tube Fig.23 Rubber seal Outer tube Fig.24 Plastic ring 9

3.0 Installation 3.6 Installing the HR25L Solo & LH Solo (cont) Fig.25 5. Measure the wall thickness and add 25mm. This is dimension X (Fig. 25. 6. Mark off dimension X on the outer tube, measuring from the rear of the chassis. Cut off the excess material (Fig. 26). 7. Remove any burrs from the tube. (X) 8. Measure the waste from the outer tube and cut the same amount off the base of the divider board (Fig. 26). 9. Replace the rubber seal 50mm in from the end of the tube and secure using the adhesive provided. 10. Refit the plastic ring using the adhesive provided. Fig.26 Waste Divider board Joint clip Outer tube Chassis 11. Subtract 1.5mm from dimension X. This will be dimension Y. 12. Mark off dimension Y from the motor housing end of the inner tube, and scribe a line around the inner tube. Peel the two motor wires away from the wiring tunnel beyond the scribed line to prevent damage. Carefully cut the excess off the tube (Fig. 27). 13. Remove any burrs from the tube. 14. Reassemble the tubes in reverse order ensuring that the two motor wires are located back in the wiring tunnel, and that the tunnel is aligned with the wiring slot in the chassis (Fig. 28). Fig.27 15. Replace the heat exchanger according to the Inside/Outside labels. The recess in the heat exchanger outer must be aligned with the wiring tunnel on the inner tube to ensure the divider slot is vertical (Fig. 28 and 29). 16. Cut the two motor wires to size and reconnect to their respective terminals (Refer to the relevant unit instructions - see pages 7-8). Fig.28 Wiring tunnel Continue installing the unit from paragraph 7 onwards in the relevant unit instructions - see pages 7-8. Divider slot Heat exchanger Recess Fig.29 10

Outer cover 4.0 Maintenance Filter 4.1 Cleaning the Unit (all models) Fig.30 Release clips Filter Apart from removing odours, providing fresh air and recovering heat, this unit extracts airborne impurities such as dust, dirt and grease. These gradually build up and diminish the efficiency and detract from the appearance of the unit. To maintain efficiency the unit should be cleaned at least every six months, or more regularly if a high level of contamination is experienced. 1. Isolate the mains power supply. 2. Unclip the removable front cover from the unit and remove the 2 filters. (Fig. 30). 3. Slide out the heat exchanger (Fig. 31). 4. Wash the outer cover, filters and heat exchanger in warm water using a mild detergent and dry thoroughly. Recess NOTE: Keep water away from all electrical components and wiring within the unit. Wiring tunnel Heat exchanger Fig.31 Divider slot If it is not possible to fully clean the filter, it must be replaced (see short parts list on page 12 for part number). 6. Reassemble in reverse order. NOTE: Follow the top Inside/Outside instruction labels on the heat exchanger and ensure that the divider slot is vertical as shown (Fig 31) 7. Switch the power supply on and check the operation of the unit. 11

1 2 5.0 Spares list 5.1 Spares List Key No. Description Part No. 3 4 1 Cover/Filter Assy 435739 2 Filter (pack of 2) 435740 3 Heat Exchanger 452914 4 Transformer power pack 372208 5 Rubber seal 371297 6. Pullcord/switch 435741 7. Humidity PCB 436391 8. Humidity sensor 435812 9 Motor assembly 436393 5 6 7 8 9 5ort Parts List 12

VENT-AXIA SALES CENTRES ENGLAND & WALES NATIONAL CALL CENTRE Newton Road, Crawley West Sussex RH10 9JA Telephone: 01293 530202 REPUBLIC OF IRELAND Fax: 01293 565169 Vent-Axia Ventilation Ltd. 921 Western Road Industrial estate Naas Road, Dublin 12. Telephone: (01) 450 4133 ` Fax: (01) 450 4570 Did you find these instructions easy to use? We value your comments, contact us via : Email: info@vent-axia.com The Vent-Axia Guarantee Applicable only to products installed and used in the United Kingdom. For details of the Guarantee outside of the United Kingdom contact your local supplier. Vent-Axia guarantees this product for two years from the date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company s discretion the product will be replaced without charge, provided that the product: 1). Has been installed and used in accordance with the instruction given with each unit. 2). The electricity supply complies with the rating label. 3). Has not been misused, neglected or damaged. 4). Has not been modified or repaired by any person not authorised to do so by Vent-Axia. IF CLAIMING UNDER THE TERMS OF THE GUARANTEE Please return the complete product, carriage paid to your original supplier by post or in person. Please ensure that it is adequately packed and accompanied by a letter clearly marked Guarantee Claim stating the nature of the fault and providing proof of the date and source of purchase. 434731B 0507 1.0 Introduction abc 13