Transient Over-Voltage Mitigation and its Prevention in Secondary Distribution Networks with High PV-to-Load Ratio

Similar documents
Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

Solar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011

Grid Management Voltage Control Distribution Grid Voltage Regulation with DER. Michael Sheehan, P.E. IREC Pacific Northwest Solar Partnership

Comments on the Solar Alliance Proposal for Changes to New Jersey Interconnection Rules

Targeted Application of STATCOM Technology in the Distribution Zone

3.0 Radial Distribution Systems

Implementation of Distributed Generation

Renewable Energy Systems 14

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

Control System for a Diesel Generator and UPS

Regenerative Utility Simulator for Grid-Tied Inverters

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Grid Stability Analysis for High Penetration Solar Photovoltaics

Copyright 2003 Advanced Power Technologies, Inc.

Presented By: Bob Uluski Electric Power Research Institute. July, 2011

DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase

Umatilla Electric Cooperative Net Metering Rules

NEDO s Smart Grid Demonstration Projects in the U. S. JUMPSmartmaui Project in Hawaii

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

The Role of Electricity Storage on the Grid each location requires different requirements

Impact of Islanding and Resynchroniza?on on Distribu?on Systems

Photovoltaic Distributed Generation

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Small Electrical Systems (Microgrids)

IEEE Workshop Microgrids

White River Electric Association, Inc. Net Metering Information & Service Requirements

Louisville Gas and Electric Company

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

Definitions. Scope. Customer Generation Interconnection Requirements

Feed-in management with Solar-Log

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements.

Y9. GEH2.3: FREEDM Cost Benefit Analysis based on Detailed Utility Circuit Models

Session 8: Distributed Energy Resources Utility Concerns, Grid Impacts and Mitigation Strategies October 21, 2015 Santiago, Chile

New York Science Journal 2017;10(3)

TECHNICAL BRIEF Americas

IFC Workshop on Distributed Generation, 13 February 2013, Moscow, Russia

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Small Generator Interconnection Program Interconnection Technical Requirements

TRANSMISSION PLANNING CRITERIA

Underpinning Research Power Electronics in Distribution Networks

PV Grid Integration Research in the U.S.

Advanced Active And Reactive Power Control For Mini Grids

Microgrid solutions Delivering resilient power anywhere at any time

Autonomous Voltage and Frequency Control by Smart Inverters of Photovoltaic Generation and Electric Vehicle

Technology from the New Product SANUPS K for a Smart Grid Society

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Model-Based Integrated High Penetration Renewables Planning and Control Analysis

RESILIENT SOLAR CASE STUDY: SUNY New Paltz NYPA Integrated Grid Pilot

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Consumer Guidelines for Electric Power Generator Installation and Interconnection

NET METERING PROGRAM. Technical Interconnection Requirements

PSNH INTERCONNECTION REQUEST

TD-2306B-001, Interconnecting Large 2-20MW Generation Systems. Employees involved with generation interconnection on electric distribution circuits.

Power Conditioning of Microgrids and Co-Generation Systems

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Reliability-related matters from the GREEN Grid project

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

An Integrated Grid Path for Solar. Thomas Key, EPRI Senior Technical Executive. ISES Webinar. April 22, 2016

Using Hosting Capacity Methodology to Develop Simplified Screens for New Solar PV Interconnections

Minnesota Dept. of Commerce, Division of Energy Resources. Distributed Generation Workshop Interconnection Standards

Generator Interconnection System Impact Study For

Power Systems Overview. Summer Programs

Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director

Protection of Power Electronic Multi Converter Systems in AC and DC Applications

Renewable Grid Integration Research in the U.S.

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning

Electrical grid stability with high wind energy penetration

Overview of State Distributed Generation Interconnection Rules

Advanced controls of PV for microgrid applications

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Interconnection System Impact Study Report Request # GI

Backfeed, Safety, and Work Practices

DER101: Distributed Energy Resources basics. May 4, 2017

Distributed Energy Resources

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Residential Smart-Grid Distributed Resources

Distributed Generation Interconnection Policy

Presentation to the PJM NEMSTF Interconnection Issues. Interconnecting Solar Projects on the PSE&G Distribution System

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Productive. Reliable. Smart. Safe. Brandon J. Pierquet. The Impact of Microinverters in Photovoltaic Systems Enphase Energy

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Net Metering Interconnection Requirements

Microgrids Outback Power Technologies

Next-generation SCADA and Control Technologies for Large-scale Use of Photovoltaic Generation on Electric Power Grid

Smart inverter operation in distribution networks with high penetration of photovoltaic systems

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

Recent Trades in Distribution System

ANN Peak Load Shaver.

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Transcription:

Transient Over-Voltage Mitigation and its Prevention in Secondary Distribution Networks with High PV-to-Load Ratio Dr. Volker Schwarzer, Dr. Reza Ghorbani Department of Mechanical Engineering for Hawaii Natural Energy Institute, University of Hawaii at Manoa 1680 East West Road, POST 109 Honolulu, HI 96822 E-mail: volkers@hawaii.edu Submitted to: Dr. David Block Florida Solar Energy Center University of Central Florida 1679 Clearlake Road Cocoa, FL 32922 E-mail: block@fsec.ucf.edu Purchase Order Number: 291166 Report Number: HNEI-02-15 February 2015 The contents of this report reflect the views of the authors, who are responsible for the facts and the accuracy of the information presented herein. This document is a project report issued and disseminated under the sponsorship of the University of Central Florida and the U.S. Department of Transportation s University Transportation Centers Program. The U.S. Government assumes no liability for the contents or use thereof.

Transient Over-Voltage Mitigation and its Prevention in Secondary Distribution Networks with High PV-to-Load Ratio Volker Schwarzer, Reza Ghorbani February 2015 1. Abstract Recent report of utility providers have shown that under certain conditions the integration of renewable energy sources might cause damaging transient over-voltages (TOVs) in the power grid. TOVs are short, rapid rises in voltage along the electric lines of the grid that can occur when the generated power of a distribution circuit exceeds its load while the circuit is isolated. The described scenario can cause permanent damage to utility equipment or personal electric household devices. This report introduces various methodologies that can mitigate TOVs in distribution networks, or reduce the probability of their occurrence. 2. Transient Over-Voltage Mitigation As the amount of small-scale distributed generation (DG) units within secondary distribution networks, such as photovoltaic power stations or rooftop wind turbines, are on the rise, a lack of proper network protection may cause network instabilities under certain load conditions [1]. Transient over-voltages (TOVs) are impulses and supersynchronous oscillations which last less than a couple of cycles. They will arise when the DG power within a secondary network exceeds its load while the network is isolated, as illustrated in Figure 2.1. Figure 2.1: Isolated Island with transient over-voltages. 1

Typical causes of TOVs include switching procedures by the utility provider, failure of protective equipment, or lightning. TOVs are not temporary over-voltages. Temporary over-voltages are oscillatory over-voltages, which persist for many cycles or even seconds. Causes of temporary over-voltages could be load rejections, single-phase faults, or ferroresonance. By comparison, the phenomenon of temporary over-voltages is well studied and solutions to prevent them are available. This is not the case for transient overvoltages (and thus the subject of this report). TOVs can cause damage to network components and to electric devices of individual consumers. Hence, finding effective mitigation procedures is crucial to guarantee reliability of the grid and minimize compensation claims. 2.1. Fundamentals of Secondary Network Distribution Systems In order to evaluate the applicability and efficiency of TOV mitigation methods, it is necessary to understand the interconnection of DGs with secondary network systems. This section provides an overview of the characteristics and requirements of interconnected secondary networks based on IEEE and ANSI standards [2,3,4,5]. 2.1.1. Electrical Distribution Systems Ideally, network systems are based on redundancy. Failure of a single component should not result in a power outage of the entire network. Hence, networks should be served by at least two primary feeders [6]. Network units consist of a disconnect- or groundingswitch, a network protector (with master relay, phasing relay and fuses), and a network transformer (typically between 300-2,500kVA). Protector specifications are defined by the standard IEEE C57.12.44. However, their ratings vary depending on manufacturer, type of protector, and the secondary voltage. Continuous current ratings range from 800-6,200A at 216-600V, interrupting current ratings range from 30,000-85,000A, and latch ratings range from 25,000-65,000A. Secondary distribution networks are divided into three types [7]: radial distribution loop distribution network distribution Radial networks are the cheapest to build due to their simple, tree-like setup. Most often, they are only connected to one power source. Hence, power failures typically affect the entire network connected to the power line. Radial networks are mainly used in rural and sparsely populated areas. Figure 2.2 illustrates a simplified radial distribution system. 2

Figure 2.2: Simplified radial distribution system Loop distribution systems are usually connected to alternate power sources. The power lines loop through the service area and return to the original point. In case of an outage, power can be redirected via switches from other connected power sources. Hence, loop distribution systems offer improved system reliability and are often used for commercial buildings and shopping centers. Figure 2.3 shows a schematic loop distribution network with two power sources. Figure 2.3: Simplified loop distribution system Network distribution is commonly found in big cities because it is the most reliable of the three. It can be described as a connection of interlocking loop systems operating at utilization voltage. Multiple power supplies feed the network and thereby increase reliability. Numerous cable connections enable multiple current paths from every network unit to every load. In case of failure of a power source, other sources can be utilized without interruption. Most cables are protected by limiters. Secondary voltages typically are 208y/120V, or in some cases 480y/277V. Figure 2.4: Simplified network distribution system 3

2.1.2. Protection of Secondary Distribution Systems Network protectors consist of air power breakers, mechanisms to operate the breakers, network relays, and control equipment. They are typically designed for a X/R ratio of 6 to 8. The number of cables per phase within a secondary network depends on the load and ranges anywhere from one to twelve. Cables sizes are typically between 4/0- and 750- kcmil. The cables itself and the cable connections to the buses are protected by cable limiters. However, small 4/0-kcmil cables are often times not protected by limiters, since it is assumed that they are small enough to burn clear. Customer service points are usually protected by a main breaker or by fuses. Isolating a faulty feeder in a network distribution system is achieved by opening the feeder's medium-voltage circuit breaker (MVCB) and all other circuit breakers at the network transformers. The network protection relays are controlled by two power functions: 1. The reverse-power flow function trips if real power flows from the network to the faulty feeder, to its network units, or to supply the core losses of the network transformer. 2. The minimum voltage difference function determines when the re-closing of the network protector is permitted. The protection relays are poly-phase devices responding to the net effect of power flow on all three phases. Unbalanced feeder faults in the presence of load power flow may not result in a net reverse power flow through the relay [6]. Transformer power losses are usually in the range of 0.1-1% of the rated transformer power, which is relatively small. As a result, the reverse-power functions of the master relays are very sensitive. If DGs are incorporated in a secondary network, very small reverse-power flows (less than 3 cycles) may open all network protectors and create an island. Large DG loads might substantially reduce the real power load of the network for short periods of time. During that time, a temporary reversal of moderate amounts of power flow can occur. To avoid unnecessary tripping of the network circuit breakers, the implementation of a time delay within the power function might be beneficial. However, this time delay should only be effective for low levels of reverse-power flow. For high level reverse-power flows, such as power flows caused during feeder faults, instantaneous tripping is still desirable. This two-level control strategy helps to prevent unwanted islanding of secondary networks with integrated DGs. 4

Figure 2.5: Network distribution system fed from a single substation with typical protection setup (source: [6]. Network transformers are served by different primary feeders. 2.2. Prevention of Transient Over-Voltages in Secondary Networks 2.2.1. Inverter Controlled Switch-Off Solutions DG sources should not energize sections of the distribution system that are isolated from the utility's main supply (islanding) [8]. Hence, DGs should feature islanding detection systems to de-energize or disconnect within a certain period of time. Otherwise, TOVs and frequency fluctuations could cause unsafe and damaging conditions. Even very short duration islands lasting just a few cycles may cause equipment damage. Hawaiian Electric Company (HECO) has proposed two mitigation options utilizing currently available technology to minimize the potential for TOVs to occur [9]. Both options include switching off the photovoltaic (PV) system instantaneously when TOVs are detected and before voltage spikes can damage utility or customer equipment. Option 1: Utilization of PV inverters with the ability to switch off the power supply once voltage transients are detected. Many modern inverters already feature this capability. 5

Option 2: PV inverters that do not have automatic switch-off capabilities can be upgraded with a fast-acting automatic transfer switch (ATS) to operate as described in option 1. Furthermore, HECO requires that both solutions trip the equipment within the duration of one cycle or when the voltage exceeds 120% of the nominal voltage. However, the IEEE 1547 and the UL-1741 islanding protection requirements require a 2 second response time [10,11]. Hence, they are not compatible with high speed utility re-closing practices. HECO also demands a time delay of 30 seconds or more before resetting an ATS, and 5 minutes or more for inverter-based solutions to avoid exacerbating any lingering line voltage issues and prevent short-cycling. 2.2.2. DG Regulation The addition of DG, such as PV solar inverters, to a distribution system may have significant impacts on the power quality, reliability, and equipment safety [8]. The amount of installed DG within the distribution system is often times correlated to the occurrence of excessive fault currents, voltage and frequency excursions, and TOVs during uncontrolled islanding. Hence, preventing unintentional islanding of DGs within an isolated secondary network is crucial. Inverter-based switch-off mechanisms might not be fully sufficient, since failures within the inverter's anti-islanding protection system have been reported to occur [12]. However, if islanding does occur, the risks of TOVs become smaller the larger the Minimum Load to Generation Ratio (MLGR) is. MLGR is the annual minimum load on the relevant power system section divided by the aggregate DG capacity on the power system section as illustrated in Figure 2.6. If the DG penetration cannot fully support the system load, many DGs will shut down based on their inherent protection systems. Figure 2.6: Calculation of Minimum Load to Generation Ratio (MLGR), source: [11]. 6

Table 2.1 shows suggested penetration level ratios and their respective risks. Utility providers can regulate the MLGRs accordingly under consideration of network topology, the DG Stiffness Factor (available utility fault current divided by DG rated output current), and the Fault Ratio Factor (available utility fault current divided by DG fault contribution). Table 2.1: Penetration risk levels depending on MLGR. The minimum load is the lowest annual load on the line section of interest. Power factor is assumed to be 0.9 inductive. In cases with high power factor, a slightly higher ratio may be needed [13]. 2.2.3. Reactive Power Control The main purpose of solar inverters is to output real power from the solar irradiance on the PV panels (DC source) [14]. However, solar inverters can also be controlled to output reactive power to regulate the voltage. Hence, it is possible to lower the power factor and temporarily reduce the MLGR if needed. Small changes in power factor can significantly decrease the voltage in the network. The impact of power factor control on the distribution system has been discussed in the literature [15,16,17]. Various options to control the Var output of the inverter exist: A maximum Var threshold can be set to limit the ratio of minimum load to active power. A schedule can be defined to vary the Var output by time of the day according to past solar irradiance and network load data. The Var output can be significantly reduced when critical network conditions are detected. 2.2.4. EV Charging Stations As the number of EVs connected to secondary networks via private and commercial charging stations is rapidly rising, grid-connected EV batteries can potentially be utilized to temporarily increase the load within the network. TOVs occur when the integrated DG power exceeds the network load while being isolated. If islanding or TOVs are detected, EV batteries can quickly be connected to the distribution system to act as additional loads. Furthermore, if the power flux of all available EV batteries within the secondary network is larger than the difference between DG power and network load, TOVs can be mitigated. Even if this condition is not met, small additional loads will reduce TOVs and their associated risks. This concept is illustrated in Figure 2.7. 7

Figure 2.7: EV batteries can potentially be utilized to temporarily increase the load within an isolated network to mitigate TOVs. EV charging stations need to include fast-switch capabilities. The power flux of the available batteries should be larger than the difference between DG power and the network load. EV charging stations need to fulfill several technical requirements to enable TOV mitigation: fast TOV and islanding detection, or constant communication with external detection system established secure connection to EV including acquisition of current charging state and maximum charging capabilities of the battery pack fast-switch capabilities within 1 cycle specific communication protocol for TOV mitigation in addition to existing charging protocols It must be noted that the availability of interconnected EV batteries within secondary networks is unstable. It is solely dependent on the operator of the vehicle and his schedule. Even multiple charging stations within a distribution system cannot guarantee the availability of an interconnected EV at all times. Furthermore, connected EVs could already be charging at maximum rate when islanding occurs and therefore might not be able to act as an additional load when needed. Hence, EV charging stations should not be used as the primary TOV mitigation option for a distribution system if 100% reliability is required, but rather as a secondary backup. Inverter failures that interfere with anti-islanding protections have been reported [12]. EV charging stations could then serve as a secondary layer of protection for critical distribution systems. Furthermore, during normal network operations, EV charging stations can function to reduce the risk of TOVs by optimized scheduling of the EV charging process. This methodology is similar to peak load leveling in V2G systems. The charging station schedules the entire charging process or parts of it during periods of the day with 8

typically high DG levels and low load levels, which is when TOVs are most likely to occur. It thereby increases the generation to load ratio and reduces the risks of TOVs during potential islanding. The scheduling of the charging process is based on past load and generation data. However, it would be conceivable to re-adjust the charging schedule in real-time when unexpected DG or load levels occur. 3. Conclusion Due to quickly increasing PV-to-load-ratios in power grids, TOVs might become a more prevalent phenomena in the near future. Hence, the development and evaluation of efficient strategies for TOV detection, mitigation, and prevention must be facilitated. While basic strategies such as inverter controlled switch-off solution do exists, it might be beneficial to investigate the TOV mitigation potential of other smart grid components, such as EV charging stations. The existing processing architecture might be co-used for grid monitoring, stabilization and advanced control. Thus, more stable network operations can be achieved compared to simple switch-off solutions. 4. Acknowledgements This report was funded under a sub-award to the Hawai i Natural Energy Institute, University of Hawai i at Manoa, from the Florida Solar Energy Center, University of Central Florida, through a grant from the US Department of Transportation s University Transportation Centers Program, Research and Innovative Technology Administration. 5. References [1] T. Aziz, T.K. Saha, and N. Mithulananthan. Analysis and mitigation of transient overvoltage with integration of small scale power-electronic interfaced dg. In Power and Energy Society General Meeting, 2012 IEEE, pages 1 8, July 2012. [2] ANSI C57.12.40-2000, ANSI requirements for secondary network transformers, Subway and vault types. [3] IEEE standard C57.12.44-2000, IEEE standard requirements for network protectors. [4] IEEE standard C37.108-1994, IEEE guide for the protection of network transformers. [5] IEEE standard 1547-2003, IEEE standard for interconnecting distributed resources with electric power systems. [6] S. Horgan M. Behnke, W. Erdman. Secondary network distribution systems background and issues related to the interconnection of distributed resources. Technical report, National Renewable Energy Laboratory, July 2005. [7] Cutler-Hammer. Learning module 3: Fundamentals of electric distribution. Technical report, Eaton, 1999. 9

[8] Yury Tsimberg Nicolas Wrathall, Stephen Cress. Technical review of hydro one s anti-islanding criteria for micro-fit PV generators. Technical report, Hydro One, November 2011. [9] Hawaiian Electric Company. Transient over-voltage mitigation: Explanation and mitigation options for inverter-based distributed generation projects < 10kw. Technical report, 2014. [10] Philip Barker. Experiences in integrating PV and other DG to the power system (radial distribution systems), 2012. Presentation. [11] Philip Barker. Distributed solar integration experiences, 2013. Presentation. [12] ESA. Distributor safety bulletin - embedded generation safety (bulletin dsb-07/11). Technical report, Electrical Safety Authority, 2011. [13] Thomas Allen Short. Electric Power Distribution Handbook, Second Edition. CRC Press, 2014. [14] M.J. Reno, R.J. Broderick, and S. Grijalva. Smart inverter capabilities for mitigating overvoltage on distribution systems with high penetrations PV. In Photovoltaic Specialists Conference (PVSC), 2013 IEEE 39th, pages 3153 3158, June 2013. [15] J.W. Smith, W. Sunderman, R. Dugan, and B. Seal. Smart inverter volt/var control functions for high penetration of PV on distribution systems. In Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES, pages 1 6, March 2011. [16] M. Braun, T. Stetz, T. Reimann, B. Valov, and G. Arnold. Optimal reactive power supply in distribution networks - technological and economic assessment for PV-systems. 24th European Photovoltaic Solar Energy Conference, 2009. [17] T. Stetz, W. Yan, and M. Braun. Voltage control in distribution systems with high level PV-penetration. In 25th European PV Solar Energy Conference, 2010. 10