ODYSSEY Product Catalogue Light Commercial Split System 5-20 Tons TTA/TTH/TWE Models 50 Hz Condensing Models TTK 060 KD TTA 075 RD TTA 100 RD TTA 120 RD TTA 150 RD TTA 180 RD TTA 200 RD TTA 240 RD Air Handling Models TTH 060 BD TTH 075 BD TTH 100 BD TWE 120 CD TWE 160 CD TWE 180 CD TWE 210 CD TWE 240 CD Oct 2007 SSA5-PRC 002-EN
Features and Benefits Feature and Benefits TTA Condensing Units TTK060KD TTA075-120RD TTA150-240RD TTH060-100BD TWE120-240CD Features Powder paint finish. Innovative cabinet design. Refrigerant accessories as standard. Single and dual compressors Optional Copper fin / Blue fin. Manifolding single circuit (for TTA150-240RD). TTH/TWE Air Handler Units Features 500 mm in height (TTH060-100). Excellent drain pan. Belt drive. Factory installed mounting channel (TTH060-100). Quiet operation. Convertible for horizontal or vertical configuration (TWE120-240). Thermal expansion valve. Optional Discharge Plenum. Return air grille (for TWE model only). High static motor. Benefits Full covering of all edges and a uniform paint finish for a smooth, attractive and durable cabinet exterior. The most attractive light commercial condensing unit available. Each unit ships standard with the service valves, hi-low pressure controls, liquid line filter drier. Optimized operation and reduced service time. Designed to provide corrosion protection on sea coast application. More efficiency at part load. Benefits Designed to fit easily into tight ceiling spaces. Specially designed drain pan with a deep pitch to catch and drain water safely away. Fully adjustable airflow for application versatility and ease of servicing. Supports the unit from below, and saves time and money for the installer. Well-insulated cabinet with fire retardent Polyethylene and wide forward curved fans provide quiet operation. Maximum application flexibility without the extra inventory of dedicated models. For maximum application flexibility and performance, capacity modulation provides improved comfort and backup in the event of a malfunction with one circuit. Designed for free blow application. For high static pressure applications. 2 SSA5-PRC 002-EN
Contents Features and Benefits 2 System Performance 4 Model Nomenclature 4 General Data Condensing Units 6 Air Handler Units 9 Application Considerations 11 System Performance Data TTK/TTH 12 TTA/TTH 12 TTA/TWE 14 Evaporator Fan Performance Data TTH 16 TWE 19 Condensing Unit Wiring 24 Air Handler Unit Wiring 29 Condensing Unit Dimensional Data 31 Air Handler Unit Dimensional Data 34 Mechanical Specification 42 SSA5-RPC 002-EN 3
System Performance System Performance Matrix Model Evaporator Total Capacity Sensible Capacity Outdoor Indoor cfm MBH MBH 1,600 57 36 TTK060KD TTH060BD 2,000 60 39 2,400 62 42 2,000 72 45 TTA075RD TTH075BD 2,500 75 49 3,000 78 52 2,700 97 63 TTA100RD TTH100BD 3,400 101 69 4,100 104 73 3,200 116 76 TTA120RD TWE120CD 4,000 121 83 4,800 125 89 4,300 151 107 TTA150RD TWE160CD 5,300 156 118 6,300 162 125 4,800 173 112 TTA180RD TWE180CD 6,000 181 122 7,200 187 132 5,600 198 139 TTA200RD TWE210CD 7,000 205 154 8,400 212 164 6,400 230 142 TTA240RD TWE240CD 8,000 243 153 9,600 253 163 Model Nomenclature Condensing Unit Model Nomenclature T T K 0 6 0 K D 0 0 E A TTK = Cooling Only (Horizontal Discharge) Nominal Capacity (MBh) 060 = 60 MBh Service Digit Minor Design Sequence Factory Installed Options 00 = Std. efficiency w/o expansion device 0E = Std. efficiency with expansion device Electrical Characteristics D = 380-415/3/50 Compressor K = Single Split, Horizontal Discharge 4 SSA5-PRC 002-EN
Model Nomenclature TTA = Cooling Only Condensing Unit Nominal Gross Cooling Capacity (MBh) 075 = 75 MBh 100 = 100 MBh 120 = 120 MBh 150 = 150 MBh 180 = 180 MBh 200 = 200 MBh 240 = 240 MBh Condensing Unit Model Nomenclature T T A 0 7 5 R D 0 0 P A Service Digit A = First Parts list Minor Design Sequence M = First Design Sequence P = Second Design Sequence Factory Installed Options # 2 0 = No option E = Copper Fin F = Blue Fin G = Manifolded Compressor S = Special request to be defined and aproved/field Installed Accessories Factory Installed Options # 1 0 = With Service Valve A = With Access Valve Electrical Characteristics D = 380-415/3/50 Refrigerant Type R = R22 Air Handling Unit Model Nomenclature T W E 1 2 0 C D 0 0 A A TTH = Cooling Only Air Handling Unit (Horizontal Discharge) TWE = Cooling Only and Heat Pump Air Handling Unit (Convertible) Nominal Gross Cooling Capacity (MBh) 060 = 60 MBh 075 = 75 MBh For TTH model 100 = 100 MBh 120 = 120 MBh 160 = 160 MBh 180 = 180 MBh For TWE model 210 = 210 MBh 240 = 240 MBh Major Design Sequence A = First Design B = Second Design C = Third Design Service Digit A = First Parts list Minor Design Sequence A = First Design Sequence B = Second Design Sequence C = Third Design Sequence Factory Installed Options # 2 0 = No Options A = Discharge Plenum (Horizontal for TTH and vertical for TWE) B = Return Air Grille (TWE model only) C = Discharge Plenum and Return Air Grille (TWE model only) S = Special request to be defined and approved Factory Installed Options # 1 0 = No Options A = 1 HP Fan Motor B = 2 HP Fan Motor C = 3 HP Fan Motor D = 5 HP Fan Motor E = 7.5 HP Fan Motor Electrical Characteristics D = 380-415/3/50 SSA5-RPC 002-EN 5
General Data General Data - Condensing Units UNIT MODELS TTK060KD TTA075RD TTA100RD TTA120RD POWER CONNECTION V/ph/Hz 380-415/3/50 MCA 1 A 11.97 18.06 27.29 29.83 SYSTEM DATA No. Refrigerant Circuits 1 1 1 1 Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant 2 R22 Suction Line OD 3 in (mm) 1 1/8 (28.6) 1 1/8 (28.6) 1 3/8 (34.9) 1 3/8 (34.9) Liquid line OD 3 in (mm) 3/8 (9.5) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) COMPRESSOR Compressor Type Hermetic Scroll No. Used 1 1 1 1 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 RLA/LRA 8.8/77.0 13.6 / 98 20.7 / 130 22.9 / 145 COIL Face Area sq ft (m 2 ) 11.67 (1.08) 15.1 (1.40) 20.0 (1.86) 25.0 (2.32) Tube Size OD in (mm) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) Rows 2 2 2 2 Fins per inch 21 16 16 16 FAN Fan Type Propeller Propeller Propeller Propeller No. used 2 1 1 1 Diameter in (mm) 18 (457.2) 28 (711) 28 (711) 28 (711) Drive Type Direct Direct Direct Direct Nominal Airflow cfm (cmh) 2660 (4520) 4885 (8300) 5768 (9800) 6828 (11600) MOTOR No. of Motor 2 1 1 1 Motor Output Watt 110 290 420 300 No. of Speed 1 1 1 1 Motor Speed rpm 930 750 830 875 V/ph/Hz 220/1/50 380/3/50 380/3/50 380/3/50 RLA/LRA 0.97/1.76 1.06 / 2.27 1.41 / 3.53 1.2 / 2.8 DIMENSION (HxWxD) Uncrated (Net) mm 1254 x 988 x 350 1050x950x1060 1050x950x1060 1050x1050x1260 WEIGHT Uncrated (Net) kg 105 164 189 240 1 MCA - Minimum Circuit Ampacity. 2 Refrigerant is R22 holding charged. 3 Piping connections of TTK060KD are 7/8 inch suction line and 1/2 inch liquid line for Thailand. 6 SSA5-PRC 002-EN
General Data General Data - Condensing Units UNIT MODELS TTA150RD TTA180RD TTA200RD TTA240RD POWER CONNECTION V/ph/Hz 380-415/3/50 MCA 1 A 32.72 35.00 49.40 53.93 SYSTEM DATA No. Refrigerant Circuits 2 2 2 2 Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant 2 R22 Suction Line OD 3 in (mm) 1 1/8 (28.6) 1 3/8 (34.9) 1 3/8 (34.9) 1 3/8 (34.9) Liquid line OD 3 in (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) COMPRESSOR Compressor Type Hermetic Scroll No. Used 2 2 2 2 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 RLA/LRA 13.6 / 98 14.3 / 130 20.7 / 130 22.9 / 145 COIL Face Area sq ft (m 2 ) 30.2 (2.81) 40.0 (3.72) 40.0 (3.72) 42.5 (3.95) Tube Size OD in (mm) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) Rows 2 2 2 2 Fins per inch 16 16 16 16 FAN Fan Type Propeller Propeller Propeller Propeller No. used 2 2 2 2 Diameter in (mm) 28 (711) 28 (711) 28 (711) 28 (711) Drive Type Direct Direct Direct Direct Nominal Airflow cfm (cmh) 9770 (16600) 11536 (19600) 11536 (19600) 13537 (23000) MOTOR No. of Motor 2 2 2 2 Motor Output Watt 290 420 420 300 No. of Speed 1 1 1 1 Motor Speed rpm 750 830 830 875 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 RLA/LRA 1.06 / 2.27 1.41 / 3.53 1.41 / 3.53 1.2 / 2.8 DIMENSION (HxWxD) Uncrated (Net) mm 1050x2200x1050 1050x2200x1050 1050x2200x1050 1050x2200x1050 WEIGHT Uncrated (Net) kg 382 420 432 462 1 MCA - Minimum Circuit Ampacity. 2 Refrigerant is R22 holding charged. 3 Piping connections of TTK060KD are 7/8 inch suction line and 1/2 inch liquid line for Thailand. SSA5-RPC 002-EN 7
General Data 8 SSA5-PRC 002-EN
General Data General Data - Air Handler Units UNIT MODELS TTH060BD TTH075BD TTH100BD TWE120CD POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 MCA 1 A 1.8 2.5 4.6 4.6 SYSTEM DATA Refrigerant Type R22 R22 R22 R22 No. Refrigerant Circuits 1 1 1 1 Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Suction Line OD in (mm) 1 1/8 (28.57) 1 1/8 (28.57) 1 3/8 (34.93) 1 3/8 (34.93) Liquid Line OD in (mm) 3/8 (9.53) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) COIL Face Area sq.ft. (m 2 ) 4.22 (0.39) 5.06 (0.47) 6.67 (0.62) 9.6(0.89) Tube Size OD in (mm) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) Rows 3 3 3 3 Fins per inch 15 15 15 14 Refrigerant Flow Control CAP. TUBE EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE Drain Connection Size in (mm) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) Drain Connection Type STEEL PIPE - MPT FAN Fan Type DOUBLE INLET CENTRIFUGAL WITH FORWARD CURVED WHEEL No. used 1 1 2 1 Diameter in (mm) 10 (254) 10 (254) 10 (254) 15 (381.0) Width in (mm) 10 (254) 10 (254) 8 (203.2) 15 (381.0) Drive Type BELT - ADJUSTABLE DRIVE MOTOR No. of Motor 1 1 1 1 Motor hp hp (kw) 3/4 (0.55) 1 (0.75) 2 (1.5) 2 (1.5) No. of Speed 1 1 1 1 Motor Speed rpm 1360 1400 1405 1405 V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 RLA / LRA 1.4-5.2 1.99-11.0 3.66-21.0 3.66-21.0 FILTER Type WASHABLE ALUMINUM AIR FILTER No. used 2 2 3 4 Size (WxLxD) mm 520x440x25 600x440x25 520x440x25 355 x 635 x 25 DIMENSION (HxWxD) Crated (Shipping) mm 673x1,410x970 673x1,410x970 673x1,778x970 1651x1499x724 Uncrated (Net) mm 520x1,312x841 520x1,312x841 520x1,680x841 1523x1410x635 WEIGHT Uncrated (Net) kg 86.7 91.3 135.4 154 1 MCA - Minimum Circuit Ampacity SSA5-RPC 002-EN 9
General Data General Data - Air Handler Units UNIT MODELS TWE160CD TWE180CD TWE210CD TWE240CD POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 MCA 1 A 6.4 6.4 10.0 10.0 SYSTEM DATA Refrigerant Type R22 R22 R22 R22 No. Refrigerant Circuits 2 2 2 2 Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Suction Line OD in (mm) 1 1/8 (28.57) 1 3/8 (34.93) 1 3/8 (34.93) 1 3/8 (34.93) Liquid Line OD in (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) COIL Face Area sq.ft. (m 2 ) 12.7 (1.18) 14 (1.47) 16.3 (1.51) 18(1.67) Tube Size OD in (mm) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) Rows 3 3 3 3 Fins per inch 14 12 15 15 Refrigerant Flow Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE Drain Connection Size in (mm) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) Drain Connection Type PLASTIC - FEMALE PIPE FAN Fan Type DOUBLE INLET CENTRIFUGAL WITH FORWARD CURVED WHEEL No. used 1 1 2 2 Diameter in (mm) 18 (457.2) 18 (457.2) 15 (381.0) 15 (381.0) Width in (mm) 18 (457.2) 18 (457.2) 15 (381.0) 15 (381.0) Drive Type BELT - ADJUSTABLE DRIVE MOTOR No. of Motor 1 1 1 1 Motor hp hp (kw) 2 (1.5) 3 (2.2) 3 (2.2) 5 (3.7) No. of Speed 1 1 1 1 Motor Speed rpm 1405 1425 1425 1440 V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 RLA / LRA 3.66-21.0 5.08-34.0 5.08-34.0 8.03-63 FILTER Type WASHABLE ALUMINUM AIR FILTER No. used 4 4 4 4 Size (WxLxD) mm 927x400x25 927x400x25 555x727x25 555x727x25 DIMENSION (HxWxD) Crated (Shipping) mm 1867x1702x939 1867x1702x939 1867x2299x794 1867x2299x794 Uncrated (Net) mm 1751x1613x850 1751x1613x850 1751x2210x702 1751x2210x702 WEIGHT Uncrated (Net) kg 275 285 355 361 1 MCA - Minimum Circuit Ampacity 10 SSA5-PRC 002-EN
Application Considerations Clearance Requirements The recommended clearances identified with unit demensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane Representative. MIN. 850 mm. Figure 1 Space requirement for TTH model MIN. 850 mm. MIN. 850 mm. 900 mm. 850 mm. 850 mm. 850 mm. 850 mm. Figure 2 Space requirement for TWE model - Horizontal Type 850 mm. Figure 3 Space requirement for TWE model - Vertical Type Recommended Interconnecting Lines - Condensing Units Length of Interconnecting Line (feet) Model 0-20 21-40 41-60 61-80 Liq. Suct. Liq. Suct. Liq. Suct. Liq. Suct. TTA075RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 TTA100RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8 TTA120RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8 TTA150RD00 1 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 TTA180RD00 1 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8 TTA200RD00 1 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8 TTA240RD00 1 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8 TTA150RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 TTA180RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 TTA200RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 TTA240RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 3/4 1 5/8 Notes: 1. TTA150-240 RD00 are required for dual circuits. 2. For line lengths over 80 linear feet and 15 feet liquid line riser, consult your local Trane representative. SSA5-RPC 002-EN 11
System Performance Data Table 1 Gross Cooling Capacities (MBH) - TTK060KD Condensing Unit with TTH060BD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 52.4 37.8 59.1 31.8 66.3 24.3 50.3 36.6 56.9 30.7 64.0 23.5 48.0 35.4 54.4 29.5 61.4 22.6 45.6 34.1 51.8 28.2 58.7 21.7 1600 80 52.4 43.0 59.2 37.1 66.4 30.8 50.3 41.9 57.0 36.0 64.0 29.7 48.0 40.6 54.5 34.8 61.5 28.5 45.6 39.4 51.9 33.5 58.7 27.3 85 52.4 48.2 59.2 42.3 66.5 36.1 50.3 47.1 57.0 41.2 64.1 35.0 48.0 45.9 54.5 40.0 61.5 33.8 45.7 44.7 51.9 38.8 58.8 32.6 90 53.3 53.3 59.3 47.6 66.5 41.4 51.6 51.6 57.0 46.5 64.2 40.3 49.9 49.9 54.5 45.2 61.6 39.1 48.0 48.0 51.9 44.0 58.8 37.9 75 54.1 39.3 60.9 33.0 68.2 25.1 51.9 38.4 58.6 31.8 65.8 24.3 49.5 37.2 56.1 30.6 63.1 23.4 46.9 35.9 53.3 29.3 60.3 22.4 1800 80 54.1 45.3 61.0 38.7 68.3 31.8 51.9 44.1 58.7 37.6 65.8 30.7 49.5 42.9 56.1 36.4 63.2 29.5 46.9 41.6 53.4 35.1 60.3 28.3 85 54.2 51.0 61.0 44.5 68.4 37.6 51.9 49.9 58.7 43.3 65.9 36.5 49.7 48.7 56.1 42.1 63.2 35.3 47.4 47.4 53.4 40.8 60.4 34.1 90 55.8 55.8 61.1 50.2 68.4 43.4 54.0 54.0 58.7 49.1 66.0 42.2 52.1 52.1 56.1 47.8 63.3 41.1 50.2 50.2 53.4 46.6 60.4 39.9 75 55.5 41.3 62.4 34.0 69.8 25.8 53.2 40.1 60.0 32.9 67.3 25.0 50.7 38.8 57.4 31.6 64.5 24.0 48.1 37.5 54.6 30.3 61.6 22.9 2000 80 55.6 47.5 62.5 40.3 69.9 32.7 53.2 46.3 60.1 39.1 67.3 31.6 50.7 45.0 57.5 37.9 64.6 30.4 48.1 43.7 54.6 36.6 61.6 29.2 85 55.7 53.7 62.6 46.5 69.9 38.9 53.5 52.6 60.1 45.3 67.4 37.8 51.2 51.2 57.5 44.1 64.6 36.7 49.2 49.2 54.6 42.8 61.7 35.4 90 58.0 58.0 62.7 52.6 70.1 45.2 56.1 56.1 60.2 51.5 67.5 44.1 54.2 54.2 57.5 50.3 64.7 42.9 52.1 52.1 54.7 49.0 61.7 41.7 75 56.8 42.8 63.7 35.0 71.1 26.4 54.4 41.6 61.3 33.8 68.5 25.6 51.8 40.3 58.6 32.6 65.7 24.5 49.1 39.0 55.7 31.3 62.7 23.2 2200 80 56.8 49.5 63.8 41.7 71.2 33.5 54.4 48.3 61.4 40.5 68.6 32.4 51.8 47.0 58.6 39.3 65.8 31.2 49.1 45.6 55.7 38.0 62.8 30.0 85 57.1 56.2 63.9 48.4 71.3 40.2 54.9 54.9 61.4 47.2 68.7 39.1 52.9 52.9 58.7 45.9 65.8 37.9 50.7 50.7 55.7 44.6 62.8 36.7 90 59.9 59.9 64.0 54.9 71.5 47.0 58.0 58.0 61.4 53.8 68.8 45.8 56.0 56.0 58.7 52.6 65.9 44.6 53.8 53.8 55.7 51.3 62.8 43.4 75 57.8 44.3 64.8 35.9 72.2 27.0 55.4 43.1 62.3 34.7 69.6 26.0 52.7 41.7 59.6 33.5 66.8 24.8 49.9 40.4 56.6 32.2 63.7 23.5 2400 80 57.9 51.4 64.9 43.0 72.3 34.3 55.5 50.1 62.4 41.9 69.7 33.2 52.7 48.8 59.6 40.6 66.8 32.0 50.0 47.5 56.6 39.3 63.7 30.7 85 58.4 58.4 65.0 50.1 72.5 41.5 56.5 56.5 62.5 48.9 69.8 40.3 54.4 54.4 59.7 47.7 66.9 39.1 52.2 52.2 56.7 46.4 63.8 37.9 90 61.7 61.7 65.2 57.1 72.7 48.6 59.7 59.7 62.5 56.0 69.9 47.5 57.6 57.6 59.7 54.8 66.9 46.2 55.4 55.4 56.7 53.4 63.8 45.0 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity Table 2 Gross Cooling Capacities (MBH) - TTA075RD Condensing Unit with TTH075BD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 67.2 47.9 75.7 40.6 85.0 31.2 63.2 45.7 71.4 40.6 80.4 29.6 58.7 43.3 66.7 36.1 75.4 27.8 53.9 40.8 61.6 33.7 69.9 25.9 2000 80 67.3 54.3 75.8 47.1 85.1 39.5 63.2 52.1 71.5 44.9 80.5 37.3 58.8 49.7 66.8 42.6 75.4 35.1 54.0 47.2 61.7 40.1 70.0 32.7 85 67.3 60.6 75.9 53.5 85.2 45.9 63.2 58.4 71.5 51.3 80.6 43.8 58.8 56.0 66.8 49.0 75.5 41.5 54.3 53.7 61.7 46.5 70.0 39.2 90 67.8 67.2 76.0 59.9 85.3 52.4 64.4 64.5 71.6 57.7 80.6 50.2 61.0 61.0 66.9 55.4 75.6 48.0 57.3 57.4 61.7 52.9 70.1 45.6 75 69.3 50.1 78.0 42.1 87.5 32.2 65.1 47.8 73.5 39.8 82.7 30.5 60.5 45.4 68.7 37.5 77.4 28.7 55.5 42.8 63.3 35.0 71.7 26.8 2250 80 69.4 57.0 78.1 49.1 87.6 40.7 65.2 54.8 73.6 46.8 82.8 38.5 60.6 52.3 68.7 44.5 77.5 36.2 55.5 49.8 63.4 42.0 71.8 33.8 85 69.6 63.9 78.3 56.1 87.7 50.9 65.3 61.7 73.7 53.8 82.9 45.6 60.8 59.4 68.8 51.5 77.6 43.3 56.4 56.5 63.4 49.0 71.9 40.9 90 70.7 70.7 78.4 63.0 87.9 54.8 67.4 67.4 73.8 60.8 83.0 52.6 63.8 63.8 68.9 58.4 77.7 50.3 59.9 59.9 63.5 55.9 71.9 47.9 75 71.2 52.1 80.0 43.4 89.6 64.0 66.8 49.8 75.4 41.1 84.6 31.4 62.1 47.3 70.3 38.7 79.2 29.6 56.8 44.7 64.8 36.2 73.2 27.2 2500 80 71.3 59.6 80.2 51.0 89.8 41.9 66.9 57.3 75.4 48.7 84.7 39.6 62.1 54.8 70.4 46.3 79.2 37.3 56.8 52.2 64.8 43.8 73.3 34.9 85 71.5 67.0 80.3 58.5 89.9 49.5 67.1 64.8 75.6 56.2 84.8 47.2 62.7 62.6 70.4 53.8 79.3 44.9 58.5 58.5 64.9 51.3 73.4 42.5 90 73.4 73.4 80.5 65.9 90.1 57.1 69.9 69.9 75.7 63.6 85.0 54.8 66.2 66.2 70.5 61.3 79.5 52.5 62.1 62.1 64.9 58.8 73.5 50.0 75 72.8 54.0 81.7 44.6 91.4 34.0 68.3 51.6 76.9 42.3 86.2 32.2 63.4 49.1 71.7 39.8 80.6 30.1 54.9 46.5 66.0 37.3 74.5 27.7 2750 80 73.0 61.9 81.9 52.7 91.6 42.9 68.4 59.6 77.0 50.4 86.3 40.7 63.4 57.1 71.8 47.9 80.7 38.3 58.0 54.5 66.1 45.4 74.6 35.8 85 73.2 69.9 82.0 60.7 91.7 51.1 68.8 67.7 77.1 58.4 86.5 48.8 64.5 64.6 71.9 55.9 80.8 46.4 60.4 60.4 66.1 53.4 74.7 43.9 90 75.9 75.8 82.3 68.6 92.0 59.2 72.2 72.2 77.3 66.3 86.7 56.9 68.4 68.4 72.0 63.9 81.0 54.5 64.1 64.2 66.2 61.4 74.8 52.0 75 74.2 55.8 83.2 45.7 93.0 34.8 69.5 53.3 78.3 43.4 87.6 32.9 64.5 50.8 72.9 40.9 81.9 30.5 59.0 48.1 67.1 38.3 75.7 28.2 3000 80 74.4 64.2 83.4 54.3 93.1 43.9 69.7 61.8 78.4 52.0 87.8 41.6 64.5 59.3 73.0 49.5 82.0 39.2 59.1 56.7 67.1 46.9 75.8 36.7 85 74.8 72.7 83.6 62.8 93.4 52.5 70.3 70.4 78.6 60.4 87.9 50.2 66.4 66.3 73.1 58.0 82.1 47.8 62.0 62.0 67.2 55.4 75.8 45.3 90 78.1 78.1 83.9 71.2 93.7 61.2 74.3 74.4 78.8 68.8 88.2 58.9 70.3 70.3 73.2 66.4 82.3 56.4 65.9 65.9 67.3 63.9 75.9 53.9 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity 12 SSA5-PRC 002-EN
System Performance Data Table 3 Gross Cooling Capacities (MBH) - TTA100RD Condensing Unit with TTH100BD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 90.2 67.0 100.0 54.6 110.7 40.7 86.8 65.2 96.4 52.9 106.8 39.3 83.1 63.4 92.5 51.1 102.5 37.8 79.2 61.4 88.3 49.1 98.1 46.6 2720 80 90.3 76.9 100.2 64.7 110.8 52.0 86.9 75.2 96.5 63.0 106.9 50.3 83.2 73.3 92.6 61.2 102.6 48.5 79.3 71.4 88.3 59.2 98.1 46.6 85 90.9 87.0 100.4 74.9 111.0 62.1 87.6 85.4 96.7 73.1 107.0 60.4 84.2 83.7 92.7 71.2 102.7 58.6 80.5 80.5 88.5 69.3 98.1 56.8 90 93.7 93.7 100.6 84.7 111.3 72.3 91.0 91.0 96.8 82.9 107.2 71.5 88.0 88.0 92.8 81.1 102.9 68.8 84.8 84.8 88.6 79.2 98.3 66.9 75 92.5 70.2 102.3 56.5 113.1 41.7 88.9 68.3 98.6 54.8 109.0 40.3 85.1 66.4 94.5 52.9 104.6 38.8 81.0 64.4 90.2 51.0 100.0 48.2 3060 80 92.6 80.9 102.6 67.6 113.2 53.6 89.0 79.2 98.8 65.9 109.1 51.9 85.2 77.3 94.6 64.0 104.7 50.1 81.2 75.4 90.3 62.0 100.0 48.2 85 93.6 92.1 102.8 78.5 113.5 64.7 89.9 89.9 98.9 76.8 109.3 63.0 86.8 86.8 94.7 74.9 104.9 61.2 83.5 83.5 90.3 73.0 100.1 59.3 90 97.5 97.5 103.1 89.3 113.9 75.9 94.5 94.5 99.1 87.6 109.6 74.1 91.4 91.4 95.0 85.8 105.1 72.3 88.0 88.0 90.7 83.9 100.3 70.4 75 94.3 73.0 104.3 58.3 104.8 42.7 90.6 71.2 100.4 56.5 110.8 41.3 86.7 69.3 96.2 54.6 106.3 39.5 82.5 67.2 91.7 52.7 101.6 49.6 3400 80 94.6 84.6 104.6 70.3 115.2 55.1 90.9 82.9 100.6 68.5 111.0 53.4 87.0 81.1 96.4 66.6 106.4 51.5 83.0 79.2 91.8 64.6 101.6 49.6 85 95.8 95.8 104.8 82.0 115.6 67.2 92.8 92.8 100.8 80.1 111.3 65.4 89.6 89.6 96.5 78.4 106.7 63.6 86.1 86.1 91.9 76.4 101.7 61.7 90 100.7 100.7 105.2 93.6 116.0 79.2 97.6 97.6 101.2 91.9 111.6 77.5 94.3 94.3 97.0 90.2 106.9 75.6 90.8 90.8 92.6 88.3 101.9 73.7 75 95.9 75.6 106.0 60.0 116.6 43.6 92.1 73.8 101.9 58.2 112.4 41.8 88.1 71.9 97.6 56.3 107.7 40.0 83.8 69.9 93.0 54.3 102.9 51.0 3740 80 96.3 88.2 106.3 72.9 116.9 56.5 92.6 86.5 102.2 71.0 112.5 54.8 88.6 84.7 97.8 69.1 107.9 52.9 84.6 82.8 93.2 67.1 102.9 51.0 85 98.5 98.5 106.6 85.2 117.4 69.5 95.4 95.4 102.4 83.5 112.9 67.7 92.0 92.0 98.0 81.6 108.2 65.9 88.4 88.4 93.3 79.7 103.1 63.9 90 103.6 103.6 107.1 97.7 117.6 82.1 100.4 100.4 103.0 96.1 113.1 80.3 96.9 96.9 98.8 94.4 108.3 78.5 93.2 93.2 94.3 92.6 103.3 76.6 75 87.5 78.1 107.4 61.5 118.0 44.1 93.5 76.3 103.3 59.7 113.7 42.3 89.3 74.4 98.9 57.8 109.0 40.5 84.9 72.4 94.1 55.8 104.0 52.3 4080 80 97.9 91.5 107.8 75.3 118.3 57.9 94.1 89.9 103.6 73.4 113.9 56.1 90.2 88.1 99.1 71.5 109.1 54.3 85.6 85.6 94.3 69.5 104.0 52.3 85 100.9 100.9 108.1 88.3 118.9 71.7 97.6 97.6 103.8 86.6 114.3 69.9 94.2 94.2 99.3 84.7 109.5 68.0 90.5 90.5 94.5 82.8 104.3 66.1 90 106.1 106.1 108.8 101.7 119.2 84.9 102.8 102.8 104.7 100.1 114.6 83.2 99.2 99.2 100.4 98.4 109.7 81.3 95.4 95.4 95.5 95.5 104.5 79.4 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity Table 4 Gross Cooling Capacities (MBH) - TTA120RD Condensing Unit with TWE120CD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 107.4 80.1 119.5 65.4 132.6 48.7 103.7 90.1 115.4 63.4 128.2 47.2 99.2 75.9 110.9 61.3 123.4 45.5 94.5 73.5 105.9 59.0 118.1 43.6 3200 80 107.6 92.0 119.8 77.6 132.7 62.3 103.7 90.1 115.6 75.9 128.4 60.4 99.3 87.9 111.0 73.5 123.5 58.6 94.6 85.5 106.0 71.2 118.2 56.2 85 108.4 104.2 120.2 89.8 133.1 74.6 104.7 102.4 115.9 87.8 128.6 72.7 100.7 100.4 111.2 85.6 123.7 70.6 96.3 96.3 106.1 83.3 118.4 68.5 90 112.1 112.1 120.4 101.6 133.6 86.9 109.0 109.0 116.0 99.6 129.0 84.9 105.4 105.4 111.3 97.5 124.0 83.0 101.6 101.6 106.3 95.3 118.6 80.7 75 110.3 84.0 122.4 67.8 135.5 50.0 106.2 95.0 118.1 65.8 131.0 48.4 101.7 79.7 113.4 63.6 126.0 46.7 96.8 77.3 108.3 61.3 120.6 44.8 3600 80 110.5 97.0 122.8 81.2 135.7 64.4 106.4 95.0 118.4 79.2 131.2 62.5 101.9 92.8 113.6 77.0 126.2 60.4 97.1 90.5 108.4 74.7 120.7 58.2 85 108.9 110.5 123.0 94.3 136.3 77.9 107.6 107.6 118.6 92.3 131.6 75.9 104.0 104.0 113.8 90.2 126.5 73.8 100.1 100.1 108.5 87.9 120.9 71.6 90 116.7 116.7 123.5 107.3 136.8 91.3 113.4 113.4 119.0 105.3 132.0 89.3 109.7 109.7 114.1 103.2 126.8 87.2 105.7 105.7 109.0 101.0 121.2 85.0 75 112.6 87.5 124.9 70.0 137.8 51.1 108.8 99.6 120.4 68.0 133.3 49.5 103.7 83.2 115.6 65.8 128.2 47.7 98.6 80.8 110.3 63.5 122.6 45.5 4000 80 113.0 101.6 125.3 84.6 138.2 66.3 108.8 99.6 120.8 82.5 133.5 64.3 104.0 102.0 115.8 80.3 128.4 62.3 99.4 95.3 110.5 77.9 122.8 60.1 85 114.7 114.7 125.6 98.6 138.9 80.9 111.3 111.3 121.0 96.6 134.1 79.0 107.5 107.5 116.0 94.4 128.8 76.8 103.4 103.4 110.6 92.2 123.0 74.6 90 120.8 120.8 126.1 112.6 139.5 95.5 117.3 117.3 121.6 110.7 134.5 93.5 113.4 113.4 116.7 108.7 129.1 91.4 109.3 109.3 111.5 106.6 123.3 89.1 75 114.6 90.8 126.9 72.1 139.7 52.1 111.0 104.1 122.4 70.0 135.2 50.4 105.5 86.5 117.4 67.8 130.0 48.3 100.3 84.1 111.9 65.5 124.5 46.2 4400 80 115.2 106.0 127.5 87.7 140.4 68.1 111.0 104.1 122.8 85.6 135.5 66.1 106.3 102.0 117.7 83.4 130.2 64.0 101.5 99.8 112.2 81.0 124.5 61.8 85 118.1 118.1 127.8 102.6 141.1 83.8 114.5 114.5 123.1 100.6 136.1 81.8 110.6 110.6 117.9 98.5 130.7 79.7 106.4 106.4 112.4 96.2 124.9 77.5 90 124.4 124.4 128.6 117.8 141.4 98.9 120.7 120.7 124.0 115.9 136.4 97.0 116.7 116.7 119.0 113.9 130.9 94.9 112.4 112.4 113.8 111.9 125.0 92.8 75 116.4 93.9 128.7 74.0 141.3 52.9 112.9 108.3 124.1 71.9 136.7 51.0 107.0 89.6 118.9 69.7 131.5 48.9 101.7 87.2 113.4 67.4 125.9 46.8 4800 80 117.3 110.2 129.0 90.3 142.2 69.8 112.9 108.3 124.5 88.6 137.3 67.8 108.3 106.3 119.3 86.4 131.9 65.7 102.8 102.8 113.7 84.0 126.0 63.4 85 121.1 121.1 129.8 106.4 143.1 86.6 117.4 117.4 124.9 104.4 138.0 84.6 113.4 113.4 119.6 102.3 132.4 82.4 109.0 109.0 113.9 100.1 126.4 80.1 90 127.6 127.6 130.8 122.7 143.5 102.4 123.8 123.8 126.1 120.9 138.3 100.5 119.7 119.7 121.2 118.9 132.7 98.5 115.2 115.2 115.3 115.4 126.7 96.3 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity SSA5-RPC 002-EN 13
System Performance Data Table 5 Gross Cooling Capacities(MBH)-TTA150RD Condensing Unit with TWE160CD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 141.6 113.6 156.6 91.0 178.8 66.9 136.3 108.9 150.0 87.9 171.4 63.9 129.3 105.4 142.7 84.6 163.4 60.9 122.1 101.5 134.7 81.0 154.5 57.8 4300 80 142.9 129.6 157.4 109.7 176.2 86.7 137.0 126.3 150.8 106.6 168.5 83.9 130.4 122.4 143.5 103.2 160.0 80.6 123.3 118.0 135.6 99.6 150.3 77.3 85 144.4 144.4 158.5 126.6 174.1 105.3 139.4 139.4 152.0 123.5 166.9 102.3 134.0 134.0 144.8 120.0 159.2 99.2 128.0 128.0 136.9 116.1 150.6 95.6 90 151.7 151.7 159.4 144.1 174.9 124.2 147.0 147.0 152.9 140.5 167.8 121.1 141.1 141.1 145.9 136.7 160.2 117.9 135.0 135.0 138.3 132.4 151.6 112.5 75 145.5 118.0 159.9 94.6 182.3 68.2 139.2 114.6 153.0 91.5 174.5 65.3 132.2 110.9 145.5 88.2 166.3 62.2 124.6 106.9 136.9 84.2 157.1 58.9 4800 80 146.6 136.6 160.7 115.5 178.1 89.9 140.5 133.1 153.9 110.8 169.5 87.0 133.8 128.7 146.4 108.8 161.0 83.6 126.9 123.5 138.3 105.1 157.1 82.8 85 150.0 150.0 162.2 133.9 177.6 112.4 144.8 144.8 155.3 130.6 170.1 107.5 139.0 139.0 147.8 127.0 162.2 104.3 132.5 132.5 139.7 123.0 152.2 99.8 90 157.8 157.8 163.5 152.3 178.3 131.4 152.4 152.4 156.9 148.6 171.6 126.3 146.5 146.5 149.7 144.2 163.6 122.9 140.1 140.1 142.3 138.6 153.3 118.1 75 148.3 123.4 162.6 98.2 185.1 69.2 141.8 120.0 155.5 95.0 177.1 66.4 134.6 116.2 147.8 91.5 168.6 63.4 126.9 112.0 139.4 90.6 154.9 0.0 5300 80 149.9 142.9 163.5 121.1 179.8 92.9 144.1 138.9 156.5 117.8 172.1 89.9 135.5 135.1 149.5 112.3 163.9 97.0 128.9 128.9 141.1 108.5 159.3 85.7 85 154.9 154.9 165.2 140.6 180.5 115.7 149.3 149.3 158.2 137.2 172.8 112.5 143.2 143.2 150.6 133.4 164.6 109.3 136.8 136.8 142.3 113.9 154.4 104.7 90 163.0 163.0 167.2 159.7 182.3 136.1 157.5 157.5 160.8 155.4 174.5 132.8 151.5 151.5 151.9 151.6 166.3 129.4 144.6 144.6 145.0 145.0 155.6 124.3 75 150.7 150.7 165.4 101.7 187.4 70.5 144.1 125.1 157.7 98.4 179.3 67.6 136.8 121.2 150.3 95.0 170.6 64.5 128.9 116.8 141.2 91.5 157.3 59.8 5800 80 151.0 150.1 166.9 124.0 182.1 96.0 145.2 145.1 159.7 120.8 174.2 92.9 139.2 139.2 151.7 117.2 165.8 91.0 132.3 132.3 143.0 113.3 161.0 88.2 85 159.0 159.0 167.9 147.1 183.0 120.8 153.6 153.6 160.8 143.4 175.1 117.5 147.3 147.3 153.1 139.4 166.8 114.1 140.4 140.4 144.7 134.9 156.6 109.8 90 167.8 167.8 168.5 167.8 184.9 142.4 161.9 161.9 162.3 162.3 177.0 139.1 155.5 155.5 156.0 156.0 168.7 135.6 148.5 148.5 148.9 148.9 157.5 130.1 75 152.9 133.6 167.4 104.9 189.4 71.4 146.1 129.9 159.9 101.7 181.1 68.6 139.1 126.0 151.8 98.2 172.3 65.5 131.0 121.3 143.1 94.3 159.4 61.1 6300 80 154.3 154.3 169.0 129.6 183.9 97.7 148.8 148.8 161.6 125.5 175.9 95.7 142.2 142.2 153.5 122.7 167.3 92.4 135.3 135.3 144.8 117.8 162.5 91.0 85 163.1 163.1 170.4 153.0 185.1 125.5 157.2 157.2 163.1 149.3 177.0 122.3 150.8 150.8 155.4 144.5 168.6 118.8 143.6 143.6 147.2 140.0 159.2 115.1 90 171.9 171.9 172.4 172.4 187.3 148.5 165.8 165.8 166.3 133.1 179.2 145.2 159.3 159.3 159.8 159.8 170.7 141.5 152.1 152.1 152.4 152.4 161.4 137.5 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity Table 6 Gross Cooling Capacities(MBH)-TTA180RD Condensing Unit with TWE180CD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 161.3 118.6 177.5 98.5 204.7 77.6 156.0 115.6 171.5 95.5 197.9 74.8 150.1 112.2 165.0 92.4 170.5 64.3 143.7 108.6 157.9 89.1 182.5 68.6 4800 80 162.0 135.3 178.6 115.2 195.8 94.6 156.7 132.1 172.7 112.1 189.2 91.8 150.8 128.8 166.2 108.9 182.0 88.7 144.5 125.1 159.2 105.4 174.3 85.4 85 165.0 146.7 179.4 131.7 197.1 110.8 159.6 143.4 173.5 128.6 190.6 106.9 153.6 139.6 167.1 125.3 183.5 105.0 147.2 135.6 160.2 121.7 175.8 101.4 90 161.2 160.1 180.0 148.2 198.3 127.5 156.7 156.3 174.2 145.1 191.8 124.5 152.0 152.0 167.8 141.8 184.6 121.3 147.1 147.1 160.9 138.2 177.0 116.8 75 165.9 124.4 182.3 102.1 209.8 79.0 160.3 121.3 176.0 99.1 202.7 76.2 154.1 117.9 169.2 95.8 194.9 73.1 147.4 114.1 161.8 92.4 186.5 69.9 5400 80 166.7 142.4 183.5 120.4 200.9 97.6 161.1 139.7 177.3 117.4 194.0 94.7 155.0 136.2 170.6 113.9 186.5 91.6 150.7 127.7 163.2 110.3 176.0 86.9 85 170.4 154.0 184.4 138.9 202.3 115.9 164.6 150.3 178.3 135.6 195.5 112.8 158.5 146.3 171.5 132.3 188.1 109.6 151.4 140.0 164.3 128.6 180.0 104.4 90 167.8 167.8 185.1 157.2 203.4 134.2 163.2 163.2 179.0 153.9 196.6 131.1 158.4 158.4 175.2 145.4 189.3 127.7 153.2 153.2 167.7 141.7 181.2 124.1 75 169.9 129.9 186.3 105.5 213.9 80.2 164.0 126.8 179.9 102.3 206.5 77.5 157.6 123.2 172.8 99.0 198.5 74.4 150.6 119.4 165.1 95.4 189.6 71.1 6000 80 170.7 150.2 187.6 125.5 205.1 100.5 167.9 141.1 181.2 122.3 198.0 97.6 161.3 138.2 174.2 118.8 190.2 93.2 154.2 133.5 166.6 115.1 181.6 90.8 85 169.7 166.0 188.6 145.6 206.6 120.5 168.0 153.7 182.2 142.3 199.5 117.3 157.2 154.5 175.2 139.0 191.8 114.0 150.9 150.0 167.7 135.2 183.5 110.5 90 174.0 174.0 193.1 159.3 207.8 140.5 169.4 169.4 186.6 156.2 200.7 137.3 164.2 164.2 179.4 146.2 193.1 134.0 158.3 158.3 171.6 148.2 184.8 130.3 75 173.2 135.3 189.8 108.6 217.4 81.5 167.1 131.9 183.1 105.5 209.8 78.7 160.5 128.4 175.8 102.0 201.4 75.5 153.3 124.4 167.9 98.4 192.3 72.3 6600 80 177.8 150.3 191.2 130.4 208.7 103.1 171.4 146.7 184.5 127.1 201.9 100.1 164.8 142.9 177.2 123.5 193.8 96.9 157.4 138.5 169.4 119.8 185.0 93.4 85 172.3 168.8 192.2 152.2 210.3 124.7 166.8 165.0 185.6 148.8 203.0 121.6 160.8 160.3 178.4 145.4 195.0 118.2 155.2 155.2 170.6 141.4 186.4 114.5 90 179.6 179.6 197.2 166.4 211.5 146.6 174.6 174.6 190.3 162.7 204.2 143.4 169.0 169.0 183.0 158.7 196.3 139.8 163.2 163.2 174.9 154.1 187.8 136.1 75 176.1 140.4 192.8 111.6 220.3 82.6 169.9 136.9 185.9 108.4 212.4 79.7 163.0 133.2 178.4 104.9 203.8 76.6 155.7 129.4 170.3 100.6 194.4 73.3 7200 80 175.8 174.7 195.3 158.6 213.4 128.9 170.7 170.6 188.5 155.1 206.0 125.8 164.9 164.9 181.1 150.5 197.8 122.2 159.1 159.1 173.1 147.5 189.0 118.5 85 181.5 155.7 194.2 135.2 212.4 105.8 175.1 151.8 187.4 131.7 204.7 102.8 148.1 130.0 179.9 129.5 196.2 99.5 160.4 142.8 171.9 124.1 187.2 95.7 90 184.3 184.3 201.5 172.7 214.7 152.5 179.1 179.1 194.4 168.7 207.3 149.2 173.5 173.5 186.7 164.3 199.2 145.6 167.2 167.2 178.4 159.3 190.4 141.8 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity 14 SSA5-PRC 002-EN
System Performance Data Table 7 Gross Cooling Capacities(MBH)-TTA200RD Condensing Unit with TWE210CD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 186.6 148.4 205.0 118.5 232.6 87.2 179.7 142.2 196.6 114.6 223.5 83.6 0.0172.1 138.0 187.6 110.5 213.7 79.9 163.2 133.3 178.0 106.1 202.8 76.1 5600 80 188.6 169.2 206.0 142.7 224.8 112.4 181.2 164.9 197.6 138.7 215.7 123.4 173.3 160.3 189.5 134.7 206.2 104.7 164.6 154.9 179.9 130.0 195.7 100.4 85 189.8 189.2 207.7 158.3 226.2 136.4 183.1 183.1 199.4 160.3 217.3 132.6 177.0 177.0 190.8 156.1 208.4 128.6 169.4 169.4 181.2 151.5 197.9 124.3 90 198.8 198.8 209.0 186.9 227.3 160.5 192.4 192.4 200.9 187.6 218.5 156.7 185.7 185.7 192.8 178.2 209.2 152.7 178.3 178.3 183.2 172.9 199.5 146.1 75 191.8 154.0 209.2 123.2 236.9 88.8 184.3 150.0 200.2 119.1 227.4 85.3 175.8 145.5 191.2 115.1 217.3 81.7 170.4 144.0 181.3 111.7 206.0 77.5 6300 80 193.7 179.2 210.2 150.3 229.1 116.2 185.8 173.9 202.1 146.4 219.8 112.5 177.3 168.6 193.1 142.2 209.8 108.7 168.9 162.9 183.0 139.1 199.1 104.1 85 197.0 197.0 212.5 174.0 230.7 143.0 190.4 190.4 203.9 171.1 222.0 139.4 183.1 183.1 195.0 165.4 212.2 135.4 175.4 175.4 185.5 160.6 201.3 130.9 90 206.6 206.6 214.4 197.3 231.9 170.2 200.1 200.1 206.1 193.3 223.7 163.5 192.9 192.9 197.2 188.1 214.2 159.4 184.9 184.9 188.1 182.1 203.3 156.0 75 195.8 161.4 212.4 127.8 240.3 90.4 187.6 157.0 204.0 123.8 230.6 86.7 178.8 153.2 194.2 119.4 220.2 83.0 169.9 147.7 184.0 114.8 208.6 79.0 7000 80 197.6 186.7 214.3 157.7 232.6 120.3 190.0 181.7 205.4 153.6 222.9 116.4 179.5 178.4 197.0 142.6 213.0 112.3 171.2 171.0 186.7 141.7 201.7 108.5 85 203.3 203.3 216.5 182.9 235.0 150.1 196.1 196.1 208.1 178.8 225.4 146.0 189.0 189.0 198.6 174.2 215.3 141.2 180.9 180.9 188.5 153.8 204.0 137.3 90 213.5 213.5 219.1 207.7 237.2 176.5 206.5 206.5 210.9 202.5 227.7 172.4 198.9 198.9 201.3 200.3 218.2 168.2 190.5 190.5 191.3 191.3 206.9 163.4 75 198.9 168.3 215.3 132.2 243.1 91.7 190.6 163.7 206.2 128.0 233.1 88.1 181.6 158.7 196.7 123.7 222.5 84.5 174.2 159.0 186.3 119.0 210.5 80.4 7700 80 202.8 202.4 218.4 161.2 235.6 124.2 191.4 190.5 209.6 157.2 225.9 120.2 183.7 183.7 199.8 152.8 215.5 116.1 175.4 175.4 189.2 148.0 203.8 111.5 85 208.6 208.6 220.5 191.8 237.9 156.5 201.6 201.6 211.1 185.8 227.9 152.7 194.0 194.0 201.8 182.0 217.8 148.3 185.5 185.5 191.3 176.2 206.4 143.4 90 219.6 219.6 220.8 219.4 240.6 184.8 212.1 212.1 212.8 212.3 231.4 180.7 204.4 204.4 204.9 204.9 221.0 176.4 195.7 195.7 196.0 196.0 209.6 171.2 75 201.5 174.7 217.7 146.3 245.4 93.2 193.0 169.8 208.5 70.9 235.2 89.6 183.9 164.8 198.9 127.9 224.3 85.9 174.2 159.0 188.2 123.1 212.1 81.6 8400 80 202.8 202.4 221.5 167.9 238.0 127.6 195.3 195.3 211.9 163.6 228.3 123.7 187.8 187.8 202.2 159.1 217.4 119.6 179.3 179.3 191.5 153.9 206.0 115.0 85 213.8 213.8 223.3 199.4 240.4 163.0 206.3 206.3 214.0 194.3 230.4 159.0 198.4 198.4 204.4 188.8 220.0 154.4 189.6 189.6 193.9 182.6 208.4 149.6 90 224.8 224.8 225.1 225.1 244.1 193.1 217.3 217.3 217.3 217.3 234.1 188.7 209.2 209.2 209.6 209.6 223.4 184.0 200.1 200.1 200.4 200.4 211.8 179.8 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity Table 8 Gross Cooling Capacities (MBH) - TTA240RD Condensing Unit with TWE240CD Air Handler Unit Ambient Temperature (F) Enter 85 95 105 115 Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 210.5 148.3 236.3 126.6 264.6 97.2 203.8 144.5 229.3 122.9 256.9 94.5 196.5 140.4 221.5 118.8 248.5 91.5 188.5 136.0 212.9 114.5 239.3 88.3 6400 80 210.7 167.2 236.5 145.6 264.8 122.8 204.2 183.1 229.5 141.8 257.1 119.1 196.7 159.2 221.6 137.8 248.7 125.3 188.6 154.8 213.1 133.5 239.5 110.9 85 210.9 185.9 236.7 164.5 265.0 141.8 204.2 182.1 229.6 160.7 257.4 138.2 196.8 178.0 221.8 156.7 248.9 134.2 188.7 173.6 213.2 152.4 239.6 130.0 90 211.6 204.6 237.1 183.4 265.3 160.8 205.3 201.2 229.9 179.6 257.6 157.1 198.7 197.6 222.0 175.6 249.1 153.2 191.7 191.7 213.3 171.2 239.8 148.9 75 217.4 154.9 243.9 131.0 272.6 100.4 210.5 151.0 236.5 127.2 264.6 97.7 202.8 146.8 228.3 123.0 255.8 94.6 194.4 142.3 219.3 118.6 246.1 91.3 7200 80 217.8 175.5 244.1 151.7 272.9 126.6 210.7 171.6 236.7 147.9 264.8 122.8 203.0 167.3 228.4 143.7 256.0 118.8 194.5 162.8 219.4 139.3 246.3 114.5 85 218.1 195.8 244.4 172.3 273.1 147.4 211.0 191.9 236.9 168.4 265.1 143.6 203.1 187.7 228.6 164.3 256.2 139.5 194.6 183.2 219.6 159.9 246.4 135.2 90 219.7 216.6 244.8 192.9 273.4 168.1 213.4 213.3 237.2 189.0 265.3 164.3 206.9 206.9 228.9 184.8 256.3 160.2 200.3 200.3 219.8 180.4 246.6 155.9 75 223.4 161.0 250.3 135.0 279.4 103.4 216.2 157.0 242.6 131.1 271.1 100.6 208.2 152.7 234.0 126.8 261.9 97.5 199.5 148.1 224.7 122.3 251.8 94.1 8000 80 223.8 183.2 250.5 157.3 279.7 130.1 216.7 201.0 242.8 153.3 271.3 126.2 208.4 174.9 234.2 149.1 262.1 122.1 199.6 170.2 224.8 144.6 252.0 117.7 85 224.2 204.9 251.0 179.5 279.9 152.4 216.7 201.0 243.1 175.6 271.6 148.6 208.6 196.7 234.4 171.3 267.5 149.0 200.1 192.4 225.0 166.8 252.2 140.0 90 226.9 226.9 251.2 201.5 280.4 174.8 221.1 221.1 243.3 197.6 271.8 170.9 214.8 214.8 234.6 193.3 267.8 172.8 207.9 207.9 225.1 188.8 252.3 162.3 75 228.6 166.7 255.8 138.6 285.2 106.1 221.1 162.6 247.8 134.6 276.6 103.3 212.8 158.2 238.9 130.3 267.1 100.1 203.8 153.5 229.3 125.7 256.7 96.7 8800 80 229.0 190.2 256.1 162.4 285.5 133.2 221.4 186.1 248.0 158.4 276.9 129.3 213.0 181.8 239.1 154.1 267.3 125.1 203.9 177.1 229.4 149.5 256.9 120.7 85 229.5 213.4 256.6 186.3 285.8 157.1 221.8 209.4 248.4 182.2 277.1 153.2 213.7 205.3 239.4 177.9 267.5 149.0 205.2 201.1 229.6 173.3 257.1 144.5 90 234.5 234.5 257.0 209.5 286.4 181.0 228.5 228.5 248.7 205.6 277.5 177.1 221.9 221.9 239.7 201.3 267.8 172.8 214.7 214.7 229.9 196.7 257.3 168.3 75 233.2 171.9 260.5 141.9 290.3 108.7 225.4 167.8 252.3 137.9 281.4 105.8 216.9 163.3 243.2 133.5 271.7 102.5 207.6 158.6 233.3 128.9 261.0 98.0 9600 80 233.6 196.7 260.9 167.2 290.6 136.1 225.8 192.7 252.6 163.2 281.7 132.1 217.1 188.3 243.4 158.8 271.9 127.9 207.8 183.5 233.4 154.2 261.2 123.4 85 234.2 221.4 261.6 192.6 290.9 161.5 226.6 217.6 253.1 188.4 281.9 157.5 218.5 213.6 243.8 184.0 272.1 153.2 210.0 209.4 233.7 179.4 261.3 148.7 90 241.4 241.4 262.1 217.1 291.6 186.9 235.1 235.1 253.5 213.1 282.5 182.9 228.3 228.3 244.1 208.7 272.5 178.6 220.8 220.8 234.0 204.1 261.6 174.0 1. Dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown sre gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat MBH = Total Gross Cooling Capacity SHC = Sensible Heat Capacity SSA5-RPC 002-EN 15
Fan Performance Data 5 Tons Table 9 Evaporator Fan Performance 5 Tons TTH060B - Air Handler External Static Pressure (Inches of Water Gauge) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 0.75 HP Standard Motor 1600 670.28 724.32 776.36 826.40 876.44 924.49 972.53 1018.58 - - - - - - - 1800 731.39 780.43 827.48 873.52 918.56 962.61 1006.66 1049.71 1091.75 1132.80 1172.85 - - 2000 790.51 836.56 879.61 921.64 963.69 1003.73 1043.80 1083.85 1122.90 1161.96 1199 1.01 1237 1.06 2200 865.68 907.73 947.78 986.83 1024.88 1061.94 1099.99 1135 1.04 1171 1.10 1207 1.16 1243 1.20 1278 1.27 2400 - - 986.91 1005.97 1042 1.03 1077 1.08 1112 1.14 1147 1.20 1181 1.26 1214 1.32 1248 1.38 1281 1.44 1314 1.50 1 HP or 2 HP Oversize Motor NOTE: Fan motor heat (MBh) = 3.15 x BHP Trane s factory supplied motors.in commercial equipment are definite purpose motors specifically designed and tested to operate reliably and continuosly at all catalog conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure, Our product s warranty will not be affected. Trane s factory supplied this standard product rated at 2000 CFM, and 0.3 inches of water for external static pressure. 16 SSA5-PRC 002-EN
Fan Performance Data 6 Tons Table 10 Evaporator Fan Performance 6 Tons TTH075B - Air Handler External Static Pressure (Inches of Water Gauge) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HP Standard Motor 2000 741.46 790.52 836.56 879.61 921.65 963.69 1003.75 1043.80 1083.85 1122.90 1161.96 1199 1.01 2250 801.62 847.68 890.73 930.78 969.84 1008.88 1045.95 1081.99 1117 1.05 1153 1.10 1189 1.61 1224 1.20 2500 856.81 908.86 948.91 987.94 1024.98 1059 1.12 1094 1.18 1128 1.23 1161 1.29 1195 1.35 1227 1.42 1260 1.47 2750 944.98 984 1.10 1022 1.20 1058 1.27 1093 1.30 1126 1.40 1158 1.47 1190 1.53 1221 1.61 1252 1.66 1282 1.72 1312 1.80 3000 1013 1.36 1051 1.44 1087 1.51 1121 1.59 1154 1.65 1185 1.72 1217 1.80 1246 1.87 1276 1.94 - - - - - - 2 HP Oversize Motor NOTE: Fan motor heat (MBh) = 3.15 x BHP Trane s factory supplied motors.in commercial equipment are definite purpose motors specifically designed and tested to operate reliably and continuosly at all catalog conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure, Our product s warranty will not be affected. Trane s factory supplied this standard product rated at 2500 CFM, and 0.3 inches of water for external static pressure. SSA5-RPC 002-EN 17
Fan Performance Data 8 Tons Table 11 Evaporator Fan Performance 8 Tons TTH100B - Air Handler External Static Pressure (Inches of Water Gauge) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor 2700 694.54 747.60 797.67 845.73 891.80 936.87 980.95 1023 1.02 1065 1.10 1107 1.17 - - - - 3000 752.72 800.79 846.86 891.93 934 1.02 972 1.09 1016 1.17 1056 1.26 1095 1.33 1133 1.42 1171 1.50 1209 1.59 3400 844 1.00 888 1.08 929 1.16 970 1.25 1009 1.33 1048 1.42 1086 1.57 1122 1.60 1158 1.68 1193 1.78 1228 1.86 - - 3700 881 1.20 922 1.32 962 1.40 1000 1.50 1038 1.58 1075 1.68 1110 1.77 1145 1.87 1179 1.96 - - - - - - 4000 947.56 985 1.65 1022 1.75 1058 1.85 1093 1.95 - - - - - - - - - - - - - - NOTE: Fan motor heat (MBh) = 3.15 x BHP Trane s factory supplied motors.in commercial equipment are definite purpose motors specifically designed and tested to operate reliably and continuosly at all catalog conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure, Our product s warranty will not be affected. Trane s factory supplied this standard product rated at 3400 CFM, and 0.3 inches of water for external static pressure. 18 SSA5-PRC 002-EN
Fan Performance Data 10 Tons Table 12 Evaporator Fan Performance 10 Tons TWE120C - Air Handler External Static Pressure (Inches of Water Gauge) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor 3200 - - - - 543 0.60 580 0.66 617 0.73 653 0.81 688 0.88 723 0.96 756 1.04 788 1.12 850 1.29 3400 - - 528 0.62 564 0.69 600 0.76 635 0.83 670 0.91 703 0.99 736 1.07 768 1.15 800 1.24 860 1.41 3600 516 0.66 551 0.73 586 0.79 620 0.86 653 0.94 686 1.02 718 1.10 749 1.18 781 1.27 811 1.36 870 1.54 3800 537 0.76 570 0.83 603 0.90 636 0.97 668 1.05 699 1.13 730 1.21 761 1.30 791 1.38 820 1.48 877 1.67 4000 561 0.87 593 0.95 624 1.02 655 1.10 686 1.18 716 1.26 746 1.35 775 1.43 804 1.53 832 1.62 866 1.81 4200 587 1.01 617 1.08 647 1.16 677 1.24 706 1.32 735 1.41 764 1.50 792 1.59 820 1.68 848 1.78 901 1.97 4400 613 1.15 642 1.23 670 1.31 699 1.39 727 1.48 755 1.57 782 1.66 809 1.75 836 1.84 863 1.94 915 2.15 4600 646 1.33 674 1.41 701 1.41 728 1.58 755 1.67 782 1.76 808 1.86 834 1.96 860 2.05 886 2.15 936 2.36 4800 662 1.47 689 1.56 715 1.64 741 1.73 767 1.82 793 1.92 818 2.01 844 2.11 869 2.21 893 2.31 947 2.53 NOTE: Data includes pressure drop due to wet coil and 1 filter. Fan motor heat (MBh) = 3.15 x BHP. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our productís warranty will not be affected. Trane s factory supplied this standard product rated at 4,000 cfm and 0.5 inches of water external static pressure. (Continued) External Static Pressure (Inches of Water Gauge) 1.4 1.6 1.8 2.0 CFM RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor 3 HP Oversized 3200 908 1.47 964 1.65 - - - - 3400 917 1.59 972 1.78 1024 1.88 - - 3600 926 1.73 979 1.92 1031 2.06 1080 2.33 3800 932 1.86 985 2.06 1035 2.26 1084 2.48 4000 941 2.01 993 2.22 1043 2.43 1090 2.64 4200 953 2.18 1004 2.39 1052 2.61 1099 2.83 4400 965 2.36 1014 2.57 1062 2.79 - - 4600 985 2.58 1033 2.80 - - - - 4800 990 2.75 1037 2.97 - - - - SSA5-RPC 002-EN 19
Fan Performance Data 13 Tons Table 13 Evaporator Fan Performance 13 Tons TWE160C - Air Handler External Static Pressure (Inches of Water Gauge) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2HP Standard Motor 3 HP Oversized Motor 4300 468 0.82 500 0.91 530 1.01 560 1.11 588 1.21 616 1.31 643 1.42 669 1.52 694 1.63 719 1.75 766 1.98 4500 476 0.90 506 0.99 536 1.09 565 1.19 593 1.30 620 1.40 646 1.51 672 1.62 697 1.73 721 1.85 768 2.08 4700 487 0.99 516 1.09 545 1.18 573 1.29 600 1.40 627 1.51 653 1.62 678 1.73 702 1.85 726 1.96 772 2.20 4900 491 1.06 520 1.17 549 1.27 576 1.38 603 1.48 629 1.60 654 1.71 679 1.83 703 1.94 727 2.06 773 2.31 5100 502 1.17 530 1.27 558 1.38 584 1.49 611 1.60 636 1.71 661 1.83 685 1.95 709 2.07 732 2.19 777 2.44 5300 510 1.26 538 1.37 564 1.48 590 1.59 616 1.71 641 1.82 665 1.94 689 2.06 712 2.19 735 2.31 779 2.57 5500 521 1.37 548 1.48 574 1.60 599 1.71 624 1.83 648 1.95 672 2.07 695 2.20 718 2.32 741 2.45 784 2.71 5700 532 1.49 558 1.61 583 1.72 608 1.84 632 1.96 656 2.08 679 2.21 702 2.34 724 2.47 746 2.60 789 2.86 5900 540 1.61 565 1.72 590 1.84 614 1.96 638 2.09 661 2.21 684 2.34 706 2.47 728 2.60 750 2.74 792 3.01 6100 557 1.74 575 1.86 599 1.98 632 2.11 646 2.23 669 2.36 691 2.49 713 2.62 735 2.76 756 2.90 798 3.09 6300 561 1.88 585 2.01 609 2.13 633 2.25 655 2.38 677 2.51 699 2.64 720 2.78 742 2.92 762 3.06 803 3.32 NOTE: Data includes pressure drop due to wet coil and 1 filter. Fan motor heat (MBh) = 3.15 x BHP. Trane s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product s warranty will not be affected. Trane s factory supplied this standard product rated at 5,300 cfm and 0.5 inches of water external static pressure. (Continued) External Static Pressure (Inches of Water Gauge) 1.4 1.6 1.8 2.0 2.2 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Oversized Motor 5 HP Oversized Motor 4300 - - - - - - - - - - 4500 813 2.33 - - - - - - - - 4700 816 2.45 839 2.71 - - - - - - 4900 816 2.56 858 2.82 898 3.09 - - - - 5100 820 2.70 861 2.97 901 3.24 940 3.52 - - 5300 822 2.83 863 3.10 902 3.38 941 3.67 978 3.96 5500 826 2.98 866 3.26 906 3.54 944 3.83 980 4.13 5700 870 3.14 909 3.42 909 3.71 946 4.01 983 4.31 5900 833 3.29 872 3.58 911 3.87 948 4.17 984 4.48 6100 838 3.46 876 3.74 920 4.10 951 4.36 987 4.67 6300 843 3.64 881 3.93 918 4.24 954 4.55 989 4.87 20 SSA5-PRC 002-EN