NECO Pumping Systems

Similar documents
Service Manual #40. Installation and Service Instructions 4000 Series Pumps

INSTALLATION AND SERVICE INSTRUCTIONS FOR 1008 AND 1010 SERIES PUMPS

Installation and Service Instructions 1008 & 1010 Size Pumps

Service Manual #67. Installation and Service Instructions 6000, 7000 & 8000 Series Magnetically Coupled Pumps

Installation and Service Instructions 1018, 1020, 1022, & 1024 Size Pumps

Installation and Service Instructions 1012, 1014, 1015, & 1017 Size Pumps

Installation and Service Instructions. ST Series Pumps

ASL Technologies, LLC Quality Policy

NECO Pumping Systems

INSTALLATION AND SERVICE INSTRUCTIONS C SERIES PUMPS

TECHNICAL SERVICE MANUAL INSTALLATION, START UP, TROUBLESHOOTING, SERIES SG-04, SG-05 & SG-07 spur gear PUMPS

INSTRUCTION MANUAL INTERNAL GEAR PUMP TITAN G-4124A SERIES=> FLANGED TITAN G-124A SERIES => FLANGED MODELS:

CONTENTS INSTALLATION TECHNICAL SERVICE MANUAL TECHNICAL SERVICE MANUAL. General INSTALLATION, START UP, TROUBLESHOOTING,

Operating Manual for Rotary Gear Pumps CMI, S.A. (Mendaro, Guipuzkoa, Spain)

TECHNICAL SERVICE MANUAL

TECHNICAL SERVICE MANUAL

TECHNICAL SERVICE MANUAL GENERAL PURPOSE BRACKET MOUNTED PUMPS SERIES 115 MODELS G, GX2, H and HX4

TECHNICAL SERVICE MANUAL GENERAL PURPOSE JACKETED PUMPS SERIES 230 MODELS HX4, KK, LQ, Q, M, N

CONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1

TECHNICAL SERVICE MANUAL

END SUCTION CENTRIFUGAL PUMPS

OPERATION MANUAL INTERNAL GEAR PUMP. Models: NG-H, NG-HL, NG-K, NG-KK, NG-L, NG-LQ, NG-LL, NG-LS, NG-Q, NG-QS. Tel: Fax:

TECHNICAL SERVICE MANUAL

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

OPERATING INSTRUCTIONS ZDX 7-1/2AS

BOILER FEED SYSTEM OPERATION AND MAINTENANCE MANUAL

WMTA6 LN SERIES SEAL-LESS MAG-DRIVE MULTI-STAGE TURBINE PUMPS

TECHNICAL SERVICE MANUAL

OPERATING INSTRUCTIONS ZDX 1/12CS

TECHNICAL SERVICE MANUAL

PRODUCT OBSOLETED 4Q16

Aqua Ultraviolet Sunami Series Pumps 1/3HP, 3/4HP, 3HP, 4HP, 5HP

TECHNICAL SERVICE MANUAL HEAVY-DUTY BRACKET MOUNTED PUMPS SERIES 120 and SERIES 124 MODELS J, K, KK, L, LQ, LL AND LM

This manual presents installation, servicing, troubleshooting, and maintenance for M PUMPS CM MAG-M SERIES Information that may be required regarding

TECHNICAL SERVICE MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart

M-3025CB-AV Fuel Pump

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

MODEL 900 IMPELLER-TYPE FLOW METER

TROUBLESHOOTING TABLE

TECHNICAL SERVICE MANUAL HEAVY-DUTY PUMPS SERIES 332 AND 260 MODELS Q, M, N AND R

READ THIS MANUAL CAREFULLY BEFORE USING THE PUMP

AK / AV 4 & 5 SERIES Metallic Vertical Centrifugal Pumps Installation and Maintenance Instructions

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND SERVICE INSTRUCTIONS HD SERIES PUMPS STANDARD DUTY MODELS

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

Operating instructions Form no safety definitions

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

ZDM Positive Displacement Flow Meter User Instructions

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

PUMPS STEAM TURBINES BUILDING & FIRE WASTEWATER SERVICE PUMP CLINIC 15 MECHANICAL SEAL DESIGN, OPERATION AND MAINTENANCE PROBLEMS

barmesapumps.com IB SERIES & 3500 RPM Installation, Operation & Maintenance Manual End Suction Centrifugal Pumps

Model 8329 Table of Contents

MODEL 200 MULTI-JET FLOW METER

DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.

Installation & Operating Manual

GLYCOL PUMPS ELECTRIC PUMPS

KC 5.5, 6, 6H, 7, 8, & 10 SERIES Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

HALLMARK INDUSTRIES INC

Table of Contents Illustrations

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

TECHNICAL SERVICE MANUAL

OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS

Installation and Service Instructions. GlobalGear Series Pumps

PT-516 Pumping Trap Installation and Maintenance

OPERATION & MAINTENANCE MANUAL HANGZHOU FLYING TECHNOLOGY CO., LTD.

MODEL 1100 TURBINE FLOW METER

Ion Technologies WC33 Submersible Sump Pump

Model 1100 Turbine Flow Meter

SELF PRIMING CHEMICAL SERVICE PUMPS

TECHNICAL SERVICE MANUAL

OWNER S MANUAL SELF-PRIMING PORTABLE UTILITY PUMP

Operator s Manual. Nitro 1000 Nitro 1000X. Nitro 750 Nitro 750X. September REV0

Topic 1. Basics of Oil Hydraulic Systems

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

PUMP PRIMING INSTALLATION CHECK MOTOR ROTATION PUMP START-UP MOTOR REPLACEMENT DISASSEMBLY ELECTRICAL HOOKUP ASSEMBLY

Positive Displacement Flowmeters GM020 series instruction manual

Installation, Operation, Repair and Parts Manual

HORIZONTAL SPLIT CASING PUMP

Hydraulic Pump Troubleshooting P & BDP Series Models

Marlow Series Cast Iron Swimming Pool Pumps

Positive Displacement Flowmeters GM007 series instruction manual

VIKING HG SERIES HELICAL GEAR EXTERNAL GEAR PUMPS

End Suction Centrifugal

Positive Displacement Flowmeters GM515 series instruction manual

TECHNICAL SERVICE MANUAL

Operating & Maintenance Manual For Steam Conditioning Valve

Model Table of Contents. SERVICE & OPERATING MANUAL Original Instructions. Instructions Sheet:

DAP-625S and DAP-875S

STOP CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL

TS400Q TS800Q. Auto Pressure Control Pump Instruction Manual. ISO 9001 Certified Walrus America Inc

k. Components not properly adjusted. Refer to machine technical manual for proper adjustment of components.

GARDEN HOSE UTILITY PUMP

UV PROCESS SUPPLY, INC. CON-TROL-CURE ½ DIAPHRAGM PUMP INSTRUCTION MANUAL PART # J

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

END SUCTION CENTRIFUGAL PUMPS

TECHNICAL SERVICE MANUAL

Transcription:

INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems Fuel Oil Transfer System THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED SYSTEM IS OF THE HIGHEST QUALITY AND DESIGN. TO OBTAIN OPTIMUM PERFORMANCE FROM THIS SYSTEM, IT IS IMPORTANT THAT YOU READ THESE INSTRUCTIONS CAREFULLY AND PAY PARTICULAR ATTENTION TO ANY HIGHLIGHTED INSTRUCTIONS. WE ARE CONFIDENT THAT YOU WILL RECEIVE MANY YEARS OF TROUBLE FREE SERVICE FROM YOUR NECO FUEL OIL TRANSFER SYSTEM. www.necoequipment.com NECO Pumping Systems a Division of NECO Equipment Company Inc., 20 S. 2 nd St., Souderton, PA 18964, 215-721-2200, (Fax) 215-721-0434, sales@necoequipment.com, www.necoequipment.com, 10/04.

General Description 4100 Models NECO s 4100 pumps are available in five sizes each, with nominal capacities ranging from 0.5 to 14 gallons per minute (1.9 to 53 liters per minute.) These pumps can handle inlet pressure to 250 psi (17 bar) and differential pressure to 500 psi (34 bar.) (Differential pressure is limited to 300 psi (20 bar) in models 4108. These pumps are self-priming and particularly suited to handle liquids of 35 to 1000 SSU (2 to 200 centipoises.) Higher viscosities can be handled at reduced speeds. These pumps are bi-rotational and designed for direct drive at standard motor speeds, with modifications available for indirect drive. Model 4100 pumps include a mechanical seal and carbon graphite idler and housing bushings. The Pumping Principle NECO s Series 4000 cast iron pumps employ the internal gear pumping principle. There are only two moving parts. Pumping action is based on a rotor, idler gear and crescent-shaped partition cast integral with the cover. Power applied to the rotor is transmitted to the idler gear with which it meshes. The space between the outside diameter of the idler and the inside diameter of the rotor is sealed by the crescent. As the pump starts, the teeth come out of mesh, increasing the volume. This creates a partial vacuum, drawing the liquid into the pump through the suction port. The liquid fills the spaces between the teeth of the idler and the rotor and is carried past the crescent partition through the pressure side of the pump. When the teeth mesh on the pressure side, the liquid is forced from the spaces and out through the discharge port. WARNING! Failure to follow these instructions could result in serious bodily injury or death. Do not attempt to work on any pump installation before completing the following steps: Disconnect the drive so that it cannot be started while work is being performed. Review the Material Safety Data Sheet (MSDS) applicable to the fluid being pumped to determine its characteristics and the precautions necessary to ensure safe handling. All pumps Vent all contain pressure residual within the hydraulic pump through oil from the the suction factory or production discharge lines. test. Determine if this is compatible with the fluid you are pumping. If the fluid is incompatible, consult the factory. Location Most series 4000 pumps are required to develop 25" mercury vacuum at 0 psi on factory test. While these pumps will develop as high as 27" of vacuum, it is sound engineering practice to avoid extreme vacuum whenever possible. Select a pipe size to reduce line friction loss to a minimum. The pump should be located as close to the source of supply as conditions permit and if possible, below the level of the liquid in the reservoir. When necessary to locate the pump in a pit, provisions should be made to safeguard against flooding. Care must be taken to properly support the suction and discharge piping so that no strain is put on the pump due to either weight or expansion. Piping strain can result in misalignment, hot bearings, worn couplings, and vibration. It is important that the piping used be clean and free of chips and scale. 2

Proper Installation Unsatisfactory pump installations are usually characterized by poor suction conditions for the specific liquid being handled. Suction conditions should be minimized to prevent vaporization of the liquid. If vacuum conditions force the liquid to vaporize, cavitation will occur, resulting in loss of capacity, premature wear and noisy operation. When handling high viscosity liquids, the speed of the pump must be reduced and the size of the lines increased to prevent cavitation. Consult the factory for NPSH requirements. Note: Pipe line friction increases at a rapid rate with an increase in viscosity. For a given pump and motor, larger pipe lines are necessary to maintain the same pump pressure when changing from a thin fluid to a thick one. Most Series 4000 pumps are supplied with both ports on the same plane. Pumps with this type of porting arrangement should always be installed with the ports facing upward to insure proper priming. When pipes are installed, an inverted "U" bend should be incorporated into the suction line close to the pump for priming purposes. There is an inlet and an outlet side to the pump. There must always be at least one pipe installed on each side. Viewing the pump from the shaft end, the inlet port is on the right for clockwise rotation and on the left for counter-clockwise rotation. Pumps should be filled with fluid at installation and never be allowed to run dry. Every pump installation should have a good foundation. Its structure should be sufficiently strong to hold the pump rigid and to absorb any strain or shock that may be encountered. The installation should be leveled, checked for proper piping alignment, and then fastened securely. Method of Drive Direct drive through a traditional flexible coupling is recommended. However, do not expect the flexible coupling to compensate for misalignment. Contact the coupling manufacturer to determine the maximum amount of misalignment to which the coupling can be subjected. Series 4000 pumps can be driven in either direction of rotation. The seal chamber communicates with the neutral zone and therefore the seal is subjected to approximately one half of the discharge pressure. All pump and motor units must be properly aligned during assembly and periodically checked, since misalignment may occur later due to abuse or other conditions. Pipe strain can force the pump and motor shafts out of alignment. Therefore, all piping to the pump must be properly supported. Do not allow the pump to act as a pipe support. External Relief Valve Protection All Series 4000 models are positive displacement pumps. As the pump rotates, liquid is positively delivered to the discharge side of the pump. If the discharge line is closed off, pressure will increase until the drive stalls and/or fails, the pump breaks or ruptures, or the piping bursts. To prevent this from happening, the use of an external pressure relief valve is required. A relief valve that directs the flow back to the supply tank is recommended. The relief on Series 4000 pumps is designed for overpressure protection only. It is not intended as a flow/pressure control device or for any similar use. Continuous operation of the relief valve will result in excessive heat buildup within the pump cavity, which could cause serious internal damage. Make certain the adjusting screw of the relief valve is set properly for the application. 3

Strainer Protection Strainers are used to remove contaminated particles from the fluid system and extend pump life. Every pump should be protected from these particles by a strainer in the suction line. Strainer size and mesh of screen are determined by the rate of flow and viscosity of the fluid. Consult the strainer manufacturer for recommendations. Install the strainer according to the designated direction of flow, locating it so that it is accessible for servicing. Use a duplex type strainer when shutdown during service is not possible. Provide a vacuum gauge in the suction line for determining when the strainer requires cleaning. Make certain strainer baskets are properly reinforced so as not to collapse under 30" Hg. vacuum. WARNING! All of NECO s pumps contain residual hydraulic oil from the factory test. Determine if this is compatible with the fluid you are pumping. If the fluid is incompatible, consult the factory. Do not run the pump dry, this could cause severe damage to the seal, bushings and/or metal parts. Startup Prior to starting the pump, double-check the following: Pressure and vacuum gauges should be installed as close as possible to the pump. Rotate pump shaft to ensure it turns freely without binding. Recheck alignment and ensure all guards are in place. Make sure piping is independently supported and no strain is being transmitted to the pump. Make sure the safety relief valve is installed correctly. Check pump rotation. Open suction and discharge gate valves. Check for any leaks once valves are open. After completing these checks the pump can be started. CAUTION! The pump should not be run dry. If after approximately 60 seconds there is no discharge of liquid, stop the pump and investigate the possible cause. Failure to comply with this could cause severe damage to the internal seals, bushing and/or metal parts. Service WARNING! Failure to follow these instructions could result in serious bodily injury or death. Do not attempt to work on any NECO s pump installation before completing the following steps: Disconnect the drive so that it cannot be started while work is being performed. 4

Review the Material Safety Data Sheet (MSDS) applicable to the liquid being pumped to determine its characteristics and the precautions necessary to ensure safe handling. Vent all pressure within the pump through the suction or discharge lines. Troubleshooting SYMPTOM: NO FLUID IS DELIVERED. Power is not on. Net positive suction head available (NPSHA) is lower than required for the inlet conditions and the vapor pressure of the liquid pumped. Calculate NPSHA and redesign piping if necessary. Leaks in suction line or port passages. These can be detected by submerging the pressure line from the discharge side of the pump into a pail of liquid where the air will be seen in the form of bubbles. Direction of shaft rotation is incorrect. Pump shaft is not rotating. The coupling is defective or the tongue and groove are not engaged. The relief valve setting is too low. Liquid is discharging through the by-pass port. SYMPTOM: CAPACITY IS TOO LOW. There are leaks in the suction line. Suction losses are too high. The suction lift is too great or the suction line too small or too long. This can be detected by installing a vacuum gauge directly at the pump suction. The maximum vacuum at the pump suction should never exceed 15" of mercury. Vaporization caused by higher vacuums will generally result in capacity dropoff. Suction conditions must be redesigned. Pump speed is too slow. The strainer is too small or obstructed. The suction port or pipe is not immersed deeply enough in the liquid. Piping is improperly installed, permitting an air pocket to form in the pump. Increased clearances or wear in the pump will sometimes cause the pump to deliver an insufficient supply of fluid. This can generally be corrected by reducing the thickness of the cover gaskets. A folded gasket or a slight amount of dirt can exaggerate the problem and cause leakage. SYMPTOM: PUMP WORKS SPASMODICALLY. Leaky suction line. Varying suction conditions. Air or vapor in the fluid. 5

SYMPTOM: EXCESSIVE POWER DRAW. Pressure too high. Liquid is more viscous than originally expected. Suction or discharge lines obstructed. Insufficient horsepower. Drive shaft and pump misaligned. Pump binding due to insufficient end clearance. Pump shaft is bent. Misalignment within the pump due to bad piping or poor installation, causing strain or distortion. SYMPTOM: PUMP IS NOISY Pump is cavitating due to inadequate suction conditions. Misalignment of coupling. Coupling is set too close to pump. Vibration of pump due to worn or bent shaft. Air leaks on suction side of pump or air entrainment in the fluid. SYMPTOM: PUMP LEAKS Cover bolts need tightening or cover gasket is defective. Worn or defective seal. www.necoequipment.com 6

WARRANTY The components of each NECO Fuel Oil Transfer system, when purchased as regular factory selections, are warranted against failure due to defects in design, material, or construction, from date of factory shipment within the periods and under the conditions noted below: PUMPS All NECO pumping assemblies are warranted against mechanical failure for a period of One (1) year. If any component of the pumping assembly fails within this period, NECO Equipment Company will, at its option, repair or replace the pump assembly on a no charge exchange basis FOB factory, Souderton, Pennsylvania. MOTORS Motors, when equipped with standard NECO overload protection systems and maintained according to factory instructions, are warranted for One (1) year. NECO Equipment Company will make, at its option, a no charge repair or replacement at the factory or at the authorized motor warranty station. VALVES Valves are warranted for One (1) year. If any mechanical component of the valve fails within this period, NECO Equipment Company will, at its option, repair or replace the valve component parts on a no charge exchange basis FOB factory. COMPLETE SYSTEM The complete NECO system as a whole, including all accessories and components not mentioned above, is warranted functionally and mechanically for a period of One (1) year, when installed, operated, and maintained in accordance with the manufacturer s recommendations. NECO Equipment Company is responsible only for repairing or replacing its products in accordance with the terms and conditions set forth above. There are no warranties, either expressed or implied, extending beyond those stated on the face hereof, and NECO Equipment Company Inc. expressly disclaims all other warranties, including any implied warranties of mechanical ability or fitness for a particular purpose. NECO Equipment Company also disclaims any liability whatsoever for incidental or consequential damages, including damage to property, damage for loss of use, loss of time, loss of profits, loss of income or any other incidental or consequential damages. NECO Equipment Company Inc. neither assumes nor authorizes any other person to furnish any warranties, or assume for it any liability in connections with the sale of its products. This warranty does not include mechanical seals, gauges, transportation, or labor costs for exchange or installation or repaired or replaced material. Final determination of warranty shall be made only by the factory upon return and inspection of returned material. No material is to be returned without a return material authorization (RMA) which may be obtained by calling or writing the factory, advising what will be shipped and the reason for the return. NECO Pumping Systems a Division of NECO Equipment Company Inc., 20 S. 2 nd St., Souderton, PA 18964, 215-721-2200, (Fax) 215-721-0434, sales@necoequipment.com, www.necoequipment.com, 10/04.