ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST

Similar documents
The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector

Electrical Hazards in Construction

CAL/OSHA ELECTRICAL LOW VOLTAGE

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

ELECTRICAL. 60 Minutes

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

Surface Regulations and Policies

NEC 2011 Code Changes

CHAPTER 10 ELECTRICAL

2014 NEC Changes (Homestudy)

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

FACT SHEET Standard: Electrical Safety

CHAPTER 10 ELECTRICAL. Notes:

Jacks and Hoists Self Inspection Checklist

A Look at the 2017 NEC Significant Changes

2014 NEC Changes Part 1 (Homestudy)

Unqualified persons: People with little or no such training related to electrical equipment and safety.

ENGINEERING SPECIFICATION

AVOIDING ELECTROCUTION HAZARDS

Electrical Safety. Recognizing & Controlling Hazards

Commercial & Industrial Wiring (2014 NEC) (Homestudy)

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Photovoltaic Solar Plan Review

Spring Test 10 due 05/11/2013

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

Metering and Service Installation:

Powered Industrial Vehicle Policy

ELECTRICAL SAFETY-RELATED WORK PRACTICES

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

PORTABLE LADDERS SELF INSPECTION CHECKLIST. Portable Wooden Ladders

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

ELECTRICAL GROUNDING SAFETY PROGRAM

Spring Test 7 due 05/03/2013

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

2016 Photovoltaic Solar System Plan Review List

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 1 8 Hours

REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

10 Commercial, Industrial, Agricultural Services

Inspector Training Workshops Module One Photovoltaic Labeling based on 2008 NEC

Energized Electrical Work

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

Design Standard. Purpose: Design Standard:

ARKANSAS ELECTRICIANS

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

Generator Fire Safety: Generator assemblies should be located outside the building.

Specific Purpose Equipment and Installations -- OSHA Standard

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

VP, Facilities and Construction Management

2011 NEC Code Updates Part 3

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Chapter 8 Interior Wiring and Lighting

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES

2014 NEC Analysis Part 2

ACI Hoist & Crane. Festoon System. 689 S.W. 7th Terrace Dania, FL (954) Fax (954) Toll Free A-HOIST ( )

Operating procedures relating to the use of electrical equipment and installations

Temporarily Approved Solar Photovoltaic System Electrical Schematics

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

8300 Series Installation Guidelines

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

INSTALL SERVICE- ENTRANCE SYSTEMS

Technical Summary of Battery Energy Storage Systems

Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE)

ELECTRIC VEHICLE CHARGING FOR BUILDINGS

2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code.

Evaluating Water-Damaged Electrical Equipment

Load Side PV Connections

Owner's/Installation Manual

SINGLE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

ELECTRICAL AREA CONTROLLED ACCESS PROCEDURE SP-18 NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18

Electrical Equipment and Terminology

Installation Instructions for Load Management Kit A051C329

BAL3000 FLUORESCENT EMERGENCY BALLAST Specification-grade: Up to 3500 lumens One or two-lamp emergency illumination

(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test

OBAE, OBAEXU, ON BOARD Battery Chargers

SECTION 300 OVERHEAD SERVICE

Technical Manual. DLM Module. This manual should remain with the unit.

Air Curtain. Installation, Operating and Maintenance Instructions

City of Manhattan Beach Community Development

Electrical Safety Program

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL

DIVISION 311 MISCELLANEOUS ELECTRICAL RULES

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

Cellwatch Electrical Installation

Transcription:

Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Guidelines: This checklist covers regulations issued by the U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) under the general industry standards subpart S - 29 CFR 1910.303; 1910.305; and 1910.335 and the construction standards subpart K - 29 CFR 1926.403 and 1926.405 which were adopted by reference. It also includes regulations issued by the New Jersey Department of Community Affairs under the Uniform Fire Code (N.J.A.C. 5:70) and the New Jersey Department of Education (N.J.A.C. 6A:26-6.2). The Uniform Fire Code has adopted the model code of the Building Officials and Code Administrators International, Inc. known as the BOCA National Fire Prevention Code/1996" by reference. It applies to all electrical use systems. This checklist does not cover: installations in ships, watercraft, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles. Definitions of terms appearing below in bold, italicized font are provided at the end of the checklist to help you understand some of the questions. This checklist does not address voltages greater than 600 volts (nominal). For these voltages, consult the OSHA regulations. Examination, Installation, and Use of Equipment Please Circle 1. Are instructional spaces provided with sufficient outlets to satisfy the programs needs with not less than two duplex outlets remotely located? [N.J.A.C. 6A:26-6.2(f)3] 2. Are only approved conductors and equipment used for electrical installations? [N.J.A.C. 5:70-3.2(a)1{F-310.7} and 29 CFR 1910.303(a)] Note: Conductors and equipment must be listed or labeled by a recognized testing laboratory, such as Factory Mutual (FM). 03/2017 35

3. Is equipment used and installed in accordance with instructions on listing or label? [N.J.A.C. 5:70-3.2(a)1{F310.7}, 29 CFR 1910.303(b)(2) and 1926.403(b)(2)] 4. Is electrical equipment free from recognized hazards that are likely to cause death or serious physical harm to students and teachers? [N.J.A.C. 5:70-3.2(a)1{F-310.1}, and 29 CFR 1910.303(b)(1) and 1926.403(b)(1)] Note: This paragraph was the most frequently cited violation in 1989 in vocational facilities. Violations included: male plugs had fibre insulators and were not dead fronted; metal junction boxes were being used on extension cords; metal junction boxes were being used on the ends of pendants; receptacles were loose in their mountings; there were open light sockets exposing live parts; an electric outlet strip had an open neutral reading when tested with a circuit analyzer; on/off switch boxes for fans were not secured to the wall; heavy items were hanging from the lighting fixtures; floor mounted receptacles were loose in their mountings; receptacles were broken; and electric cords were frayed, loose, and had exposed wires. 5. Are multi-plug adaptors, such as cube adaptors and un-fused plug strips, prohibited? [N.J.A.C. 5:70-3.2(a)1{F-310.4}] 6. Are junction boxes covered? [N.J.A.C. 5:70-3.2(a)1{F- 310.4}] 7. Are electrical motors free of excessive accumulations of oil, dirt, waste and debris? [N.J.A.C. 5:70-3.2(a)1{F-310.8}] 8. Are unused fixtures, circuits, wiring and electrical devices or fixtures removed or properly secured in place? [N.J.A.C. 5:70-3.2(a)1{F-310.9}] Splices 9. Are conductors spliced or joined by using suitable devices or by brazing, welding or soldering with a fusible metal or alloy? [29 CFR 1910.303(c) and 1926.403(e)] 10. Are soldered splices first joined so as to be mechanically and electrically secure and then soldered? [29 CFR 1910.303(c) and 1926.403(e)] 11. Are splices, joints and free ends of conductors covered with adequate insulation? [N.J.A.C. 5:70-3.2(a)1{F-310.6}, 29 CFR 1910.303(c) and 1926.403(e)] 03/2017 36

Arcing Parts 12. Are the parts of electrical equipment which ordinarily produce arcs, sparks, flames or molten metal enclosed or separated and isolated from all combustible material? [29 CFR 1910.303(d) and 1926.403(f)] Marking 13. Is electrical equipment marked with the manufacturer's identity? [29 CFR 1910.303(e) and 1926.403(g)] 14. Is electrical equipment marked with the voltage, current, wattage or other ratings as necessary? [29 CFR 1910.303(e) and 1926.403(g)] 15 Are the markings durable enough to withstand the working environment? [29 CFR 1910.303(e) and 1926.403(g)] Identification of Disconnecting Means and Circuits 15. Is each disconnecting means for motors and appliances legibly marked to indicate its purpose, unless located and arranged so the purpose is evident? [29 CFR1910.303(f) and 1926.403(h)] 17. Is each service, feeder and branch circuit at its disconnecting means or over-current device legibly marked to indicate its purpose, unless located and arranged so the purpose is evident? [29 CFR 1910.303(f) and 1926.403(h)] Note: Circuit breaker panels should be marked to clearly indicate the purpose of each circuit breaker. Note: Circuit breakers applied in compliance with series combination ratings should be legibly marked in the field to indicate so. [NFPA 110.22(B)] 600 Volts, Nominal, or Less Working Space about Electric Equipment 18. Is access and working space provided around electrical equipment to provide ready and safe operation and maintenance? [29 CFR 1910.303(g)(1) and 1926.403(i)] 03/2017 37

19. Are sufficient work clearances (see note) maintained around equipment operating at 600 volts or less? [N.J.A.C. 5:703.2(a)1{F-310.3}, 29 CFR 1910.303(g)(1)(i) and 1926.403(i)(1)(i)] Note: Working distances around electrical equipment varies according to the nominal voltage to the ground, exposed live parts and year equipment was installed. These distances vary from 2.5 to 4 feet. Consult the OSHA regulations for details. 20. Are required working spaces around electrical equipment kept free of stored materials? [29 CFR 1910.303(g)(1)(ii) and 1926.403(i)(1)(ii)] 21. When there are live parts normally exposed on the front of switchboards or motor control centers, is the working space in front of such equipment greater than or equal to 3 feet? [29 CFR 1910.303(g)(1)(iv) and 1926.403(i)(1)(iv)] 22. Is illumination provided for all working spaces around service equipment, switchboards, panel boards and motor control centers installed indoors? [N.J.A.C. 5:70-3.2(a)1{F310.1} and 29 CFR 1910.303(g)(1)(v)] 23. Is there a minimum head-room of 6 feet, 6 inches of working space about service equipment, switchboards, panel boards, or control centers? Also, where the electrical equipment exceeds 6 feet 6 inches, the minimum headroom shall not be less than the height of the equipment. [29 CFR 1910.303(g)(1)(vi) and 1926.403(i)(1)(v); NFPA 70 110.26(E)] 600 Volts, Nominal, or Less Guarding of Live Parts 24. Are live parts of electrical equipment operating at 50 volts or more guarded against accidental contact by approved cabinets, or other forms of approved enclosures? [29 CFR 1910.303(g)(2)(i) and 1926.403(i)(2)(i)] Note: Splices should be in junction boxes or other proper enclosures. The requirement to guard the particular live part is not applicable in any of the following situations: (a) when the live part is located in a room, vault, or similar enclosure that is Accessible only to qualified persons. (b) when permanent, substantial partitions or screens are arranged so that only qualified persons will have access to the space within reach of the live parts. Any openings in such partitions or screens shall be so sized and located that persons are not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them. 03/2017 38

(c) when the live part is located in a suitable balcony, gallery, or platform so Elevated and arranged as to exclude unqualified persons. (d) when the live part is elevated 8 feet or more above the floor or other working surface. 25. In areas where electrical equipment would be exposed to physical damage, are the enclosures or guards so arranged and of such strength to prevent such damage? [29 CFR 1910.303(g)(2)(ii) and 1926.403(i)(2)(ii)] Note: Incandescent and fluorescent light bulbs should be guarded if subject to physical damage. Light fixtures should have protective plates. 26. Are entrances to rooms or other guarded locations containing exposed live parts Marked with conspicuous warning signs forbidding unqualified persons to enter? [29 CFR 1910.303(g)(2)(iii) and 1926.403(i)(2)(iii)] 27. When normally enclosed live parts are exposed for maintenance and repair, are theyguarded to protect unqualified persons from contact? [29 CFR 1910.335(a)(2)(ii)] 28. Are safety signs, safety symbols, or accident prevention tags used where necessary to warn students/teachers about electrical hazards? [29 CFR Wiring Methods - General Requirements 29. Are metal raceways, cable armor, and other metal enclosures for conductors metallically joined together into a continuous electric conductor including connections to all boxes, fittings, and cabinets as to provide effective electrical continuity? [29 CFR 1910.305(a)(1)(i) and 1926.405(a)(1)(i)] 30. Is wiring in ducts used to transport dust, flammable vapors and exhaust from commercialtype cooking equipment prohibited? [29 CFR 1910.305(a)(1)(ii) and 1926.405(a)(1)(ii)] 03/2017 39

Wiring Methods - Cable Trays 31. Are only acceptable types of cables used in cable trays? [29 CFR 1910.305(a)(3)(i)] Note: Consult 29 CFR 1910.305(a)(3)(i) for complete list of acceptable types of cables. 32. Are cable tray systems prohibited in hoist ways or where subjected to severe physical damage? [29 CFR 1910.305(a)(3)(ii)] Energy Storage Systems (ESS): Partitions, Working Spaces, Illumination and Egress 33. Is a disconnecting means provided for all ungrounded conductors derived from an ESS? Is it readily accessible and located within sight of the ESS? [NFPA 706.7(A)] 34. Where ESS and output terminals are more than 1.5m (5 ft.) from connected equipment, or where the circuits from these terminals pass through a wall or partition: [NFPA 706.7(E)] i) Is a disconnecting means provided at the ESS end of the circuit? ii) Is a second disconnecting means located at the connected equipment installed where the disconnecting means required by (i) above is not within sight of the connected equipment? 35. Is the working space measured from the edge of the ESS modules, battery cabinets, racks or trays? For battery racks, is there a minimum clearance of 25mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance? [NFPA 706.10(C)] Note: ESS modules, battery cabinets, racks or trays shall be permitted to contact adjacent walls or structure, provided the battery shelf has a free air space for not less than 90 per cent of its length. Preengineered and self-contained ESS shall be permitted to have working space between components within the system in accordance with the manufacturer s recommendations and listing of the system. 03/2017 40

36. Is illumination provided for working spaces associated with ESS and their equipment and components? [NFPA 706.10(E)] Note: Additional luminaires shall not be required where the work space is illuminated by an adjacent light source. The location of the luminaires shall not do either of the following: i) Expose personnel to energized systems components while performing maintenance on the luminaires in the system space ii) Create a hazard to the system or system components upon failure of luminaire 37. Are personnel doors intended for entrance to and egress from rooms designated as ESS open in the direction of egress and equipped with listed panic hardware? [NFPA 706.10(D)] 03/2017 41

Definitions: Approved means acceptable to the authority enforcing this checklist. The authority enforcing this checklist is the New Jersey Department of the Labor and the New Jersey Department of Education. Approved for the purpose means determined by a nationally recognized testing laboratory, inspection agency or other organization concerned with the product evaluation as part of its listing and labeling program. Branch circuit means the circuit conductors between the final over current device protecting the circuit and the outlet(s). Disconnecting means refers to a device, or group of devices, or other means by which the conductors of a circuit can be disconnected from their source of supply. Energy storage systems mean one or more components assembled together capable of storing energy for use at a future time. They include but not limited to batteries, capacitors, and kinetic energy devices (e.g. flywheels and compressed air). These systems can have ac or dc output for utilization and can include inverters and converters to change stored energy into electrical energy. Feeder means all circuit conductors between the service equipment, or the generator switchboard of an isolated plant, and the final branch-circuit over current device. Luminaire means a lighting fixture. Qualified person means one familiar with the construction and operation of the equipment and the hazards involved. Whether an employee is considered to be a "qualified person" depends upon various circumstances in the workplace. It is possible and, in fact, likely for an individual to be considered "qualified" with regard to certain equipment in the workplace, but "unqualified" as to other equipment. A person who is undergoing on-the-job training and who, in the course of such training, has demonstrated an ability to perform duties safely at his or her level of training and who is under the direct supervision of a qualified person is considered to be a qualified person for the performance of those duties. Raceway means a channel designed expressly for holding wires, cables, or busbars, with additional functions as permitted. Raceways may be of metal or insulating materials, and the term includes rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit, liquid tight flexible metal conduit, flexible metallic tubing, flexible metal conduit, electrical metallic tubing, under floor raceways, cellular concrete floor raceways, cellular metal floor raceways, surface raceways, wireways, and busways. Service means the conductors and equipment for delivering energy from the electricity supply system to the wiring system of the premises served. 03/2017 42