ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

Similar documents
Common Bus and Line Regeneration

Variable Speed Pumping

Power Quality Solutions POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS

Steve Schouten. Donna Densmore

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

VFD Best Practices: Getting the Most from Your VFD Investment

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Table of Contents. Foreword...xiii. Chapter One Introduction, Objectives of the Guide...1

ABB n.v Power Quality in LV installations

Uptime. All the time.

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

Electric Motor Controls BOMA Pre-Quiz

Shaft Grounding Rings. Protecting VFD Driven Motors from Bearing Currents

Oftentimes, that isn't the end of the story for the engineer.

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

Variable Frequency Drives

SDC,Inc. SCR-Regenerative Ac Drive

Benefits of VFD for single to three phase conversion

ELECTRICAL POWER and POWER ELECTRONICS

Introduction to Power Electronics - A Tutorial. Burak Ozpineci Power Electronics and Electrical Power Systems Research Center

Question Number: 1. (a)

AC Adjustable Speed Drives (ASD s)

INTRODUCING THE NEW MINI INVERTERS BY READY-LITE

Technical News. Drives: benefits, operation, pitfalls and harmonic solutions. Issue #59 - January 2011

The Perfect Fit. Introducing the Next Generation of SINAMICS PERFECT HARMONY GH180 Air-Cooled Drive. usa.siemens.

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp

MGE TM Galaxy TM 7000 GFC

Variable Frequency Drive Basics

When to use a Soft Starter or an AC Variable Frequency Drive

SECTION 3 HPS CENTURION R REACTORS AND RC DV/DT FILTERS

RELIABILITY THROUGH TECHNOLOGY

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

Integration of Large Wind Farms into Electric Grids

Technical Explanation for Inverters

For motors controlled

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

smartvar Dynamic VAR Compensator

AC Line / Load Reactors

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

AC/DC FFE converter power module

ENERGY EFFICIENT MOTORS AND POWER SAVING Dr. K. Brahmanandam E.E.E Department, M.V.S.R.E.C, Hyderabad, India

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

MGE TM Galaxy TM 7000

ECE1750, Spring Motor Drives and Other

PowerFlex 6000 Medium Voltage AC Drives

PRODUCT SPECIFICATIONS


Industrial Motors. But first..servos!

Product brochure. Medium voltage AC drive ACS 1000, ACS 1000i 315 kw 5 MW, kv

AC DRIVES. AC Drives. The word "drive" is used loosely in the industry. It seems that people involved

DRIVE THE WATER CYCLE. January 10 TH 2013

Ignition Coil Current Waveforms 2007 Honda Accord SE 4CYL

VLT HVAC Drives Technical Reference Supplement

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

Power Quality and Energy Management

Electrical Drives I. Week 11: Three phase Induction Motor Starting

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Technical Data Sheets

Transforming Energy.. For Advanced Technology

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

RLW. Reactors. mtecorp.com. Smaller, lighter protection. Power quality. Solved.

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number)

Construction of Magnetic Buzzer

Yaskawa Electric America Unit Troubleshooting Manual Section One: Introduction & Checks Without Power GPD 506/P5 and GPD 515/G5 (0.

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

Technical Data Sheets

Tower Electronic Systems

The cement and minerals industry

SitePro UPS 400Vac / CE. GE Consumer & Industrial August 2004

FINHRM FINHRM5 FINHRMA FINHRMAC

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Application Note CTAN #127

Variable speed application guidelines

.3 Section Waste Management and Disposal.

Handout Activity: HA773

TLE Series UPS 400/500 kw With eboost Technology

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

EMC Issues in Electric Drives

VARIABLE FREQUENCY DRIVES

TLE Series UPS 160/200/225/250 kw with eboost Technology

Technical Data Sheets

EPRLAB FAQ v1.0 Page 1 / 8 Copyright EPRLAB December 2015

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Power Factor and Harmonics Primer

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

Technical Data Sheets

VoltPro VP4 Automatic Voltage Regulator

TLE Series UPS 750/1000 kw With eboost Technology

MTE AC Line / Load Reactors Price book

Power Supplies and Overcurrent Protection (fuses)

Transcription:

ASHRAE - Variable Speed Drives By Dan Watkins, LEED BD+C Bornquist, Inc.

Adjustable Frequency Drive Fundamentals How does a VFD actually work VS Pumping Analysis VS Pumping Features Harmonics VFDs and Motors

How does a VFD actually work?

How does a VFD actually work?

How does a VFD actually work? Frequency Controls Motor Speed

How does a VFD actually work?

Converts AC to DC, then DC to AC 460 V, 60 Hz 640 V, DC 307 V, 40 Hz

Basic Drive Diodes Change AC to DC Capacitors Filter the DC Transistors Switch DC to AC

V/Hz Curve Depends on ApplicaCon

Extended Frequency OperaCon

Extended Frequency OperaCon

Extended Frequency OperaCon

So, why do we want to do variable speed pumping?

Variable Speed Pumping Applications = GPM 2 GPM 1 RPM 2 RPM 1 = HEAD 2 HEAD 1 GPM 2 GPM 1 2 HEAD 2 = HEAD 1 RPM 2 RPM 1 2 HP 2 HP 1 = = HP 2 HP 1 GPM 2 GPM 1 3 RPM 2 RPM 1 3

Variable Speed Pumping Applications Determine applicability of Variable Volume/Variable Speed Where applicable utilize a system s variable volume characteristics and apply variable speed pumping to maximize the total energy savings and control in the system Primary Only or Primary/Secondary Pumping Arrangements Enhanced System Control Variable Speed Reduction Capability Pressure Sensor Location

Variable Speed Pumping Applications

Variable Speed Pumping Applications 12.5HP - Constant

Variable Speed Pumping Applications

Variable Speed Pumping Applications 12.5HP - 7.5HP Depending on Flow 10HP 15HP

Variable Speed Pumping Applications

Variable Speed Pumping Applications 12.5HP HP 2 = 900 12.5 1800 3 HP 1 = 1.6 HP 1.6HP

Variable Speed Pumping Applications

Variable Speed Pumping ApplicaCons - Applicability The question of applicability of Variable Volume/ Variable Speed on your system is based on the system s inherent operating characteristics. In system s with generally steady load characteristics and/or limited volume variation - Variable Speed is not generally applied due to poor payback calculations. In system s with varying load characteristics and greater volume variation - Variable Speed is generally applied, based on a payback analysis.

Variable Speed Pumping ApplicaCons - Sensor LocaCon ΔP Sensor/Transmitter SOURCE SOURCE ΔP Sensor/ Transmitter

Variable Speed Pumping ApplicaCons - Sensor LocaCon Coil 10-15 P.D. Control Valve 10-15 P.D. Typical Total P.D. 20-30 Typical Setting Equals Design Pressure Drop Across the Coil, Control Valve, and Circuit Setter.

Variable Speed Pumping ApplicaCons - Sensor LocaCon SOURCE SOURCE Pump Trim 5 P.D. ΔP Sensor/ Transmitter PumpOverhea d 0-15% P.D. Typical Setting Equals Total Pump Head Minus Noted Pressure Drops Piping Loss 3-5 P.D. Air Separator 3-5 P.D.

Variable Speed Cost Savings Easy Pump Balancing Variable Flow Systems Pressure Booster Packages

Variable Speed Pumping Easy Pump Balancing X Pump Selected at: 1000 GPM @ 100 40 HP required. Duty Point: 30 HP Oversized by 15% 15 head on TDV

Variable Speed Pumping

Variable Speed Pumping

Variable Speed Pumping Variable Volume System

Variable Speed Pumping Example Pump Selected at: 1000 GPM @ 100 Variable Speed and System curves shown 20 Control Head 725 RPM Minimum

Variable Speed Pumping Example PE Motor

Variable Speed Pumping Example PE Motor

Variable Speed Pressure BoosCng Height of building 12 stories 150 _. stacc li_ 30 PSI City pressure 30 PSI required at the top 50 piping pressure drop at design flow

Variable Speed Pressure BoosCng Pump Selected at: 300 GPM @ 200 30 HP required. Duty Point: 25 HP 2950 RPM Minimum Speed

Variable Speed Pressure BoosCng

Pumps Application-Specific Capabilities Compressors

Flying Start Synchronizes the drive to the speed of a coasting fan Searches for the fan s speed in both directions Applies DC braking if needed Provides a smooth start

Vibration Avoidance Avoids speed that can cause mechanical resonant vibration Up to four frequency bands of individual sizes Simple, prompted automated setup

Other Pump-Protection Functions Dry pump detection Over-flow ( end of curve ) protection

Power Line Harmonics Their Cause and Solutions

What are Harmonics? A sinusoidal waveform is a pure frequency All waveforms have a fundamental frequency Harmonics are integer multiples of the fundamental frequency The first harmonic is the fundamental frequency

What is Harmonic Distortion? Harmonic distortion results when harmonics currents are combined with a fundamental frequency The resulting waveform is no longer a pure sine wave Harmonic currents operate at the same time as the fundamental, but at faster rate Harmonic currents are additive, producing a distorted sine wave Fundamental = 60Hz 5th Harmonic = 300Hz

Why are Harmonics a concern? Overheating of power distribution transformers Overheating of conductors, especially neutral wiring Overheating of induction motors Torque reduction of induction motors Overheating of power factor correction capacitors Nuisance tripping of circuit breakers Blown fuses

Why are Harmonics a concern? Carrier current signals Lighting systems (Leviton) Some security systems Sensitive electronic equipment Communication Research Computers Airport Electronics Medical Security Stand-by generators

What Causes Harmonics? NON-LINEAR LOADS - Loads which do not draw sinusoidal current from the line Non-incandescent lighting Computers Uninterruptible power supplies Telecommunications equipment Copy machines Battery chargers Electronic variable speed drives Any load with an AC to DC power converter

Harmonics For a typical 6 pulse inverter, these multiples are: Fundamental = 60 Hz 5th Harmonic = 60 x 5 = 300 Hz 7th Harmonic = 60 x 7 = 420 Hz 11th Harmonic = 60 x 11 = 660 Hz 13th Harmonic = 60 x 13 = 780 Hz 17th Harmonic = 60 x 17 = 1,020 Hz

One Drive in Different Buildings Strong Power Line Total harmonic voltage distortion 1.1% Weak Power Line Total harmonic voltage distortion 5.1%

IEEE 519-1992 Designed to protect the utility power grid Measured at the Point of Common Coupling (PCC) This recommendation focuses on the point of common coupling (PCC) with the consumer-utility interface. some harmonic effects are unavoidable at some points in the system. (IEEE Std 519-1992, sec. 10.1) The PCC is not at the wiring to an individual device

Drive Manufactures Addressing Harmonics Some just ignore the problem Build in DC link chokes Built in line reactors Build special 12 and 18 pulse drives Optional separate filters Product Selection Goal: Select products that give you performance without excess cost

Harmonic Reduction: DC Link Reactors Generally a standard part of the drive; not an option.

Harmonic Reduction: AC Line Reactors Often used when the drive has no built-in filtering

DC Link + AC Line Reactors? Typical example (from drivesmag.com) no reactors 62% current distortion 3% DC reactor 31% current distortion 3% AC reactor 37% current distortion 3% DC reactor + 3% AC reactor 28% current distortion Remember, the goals are: Keep harmonic distortion from causing a problem Avoid wasting money

12-Pulse (and Higher) Rectifier to the rest of the drive Theoretically eliminates the 5th and 7th harmonics Uses two sets of input diodes to the power line

12-Pulse (and Higher) Rectifier But 12 pulse is no different than 6 pulse unless a phase-shifting transformer is used Shifts the phase of voltage applied to each rectifier Might not be supplied with the drive Δ Y transformer to the power line to the rest of the drive

Connects in parallel with the power line to correct harmonic distortion Active Filter

Comparing All Harmonic Solutions

Adjustable Frequency Drives and Motor InteracCon

Drive and Motor Interaction Audible Motor Noise Motor Overheating Motor Insulation Stress Motor Bearing Damage

Audible Motor Noise Caused by the pulses of electrical energy that the drive uses to power the motor The loudness depends on Motor design Pulse frequency Motor current

Drive and Motor Interaction Audible Motor Noise Motor Overheating Motor Insulation Stress Motor Bearing Damage

Motor Overheating Variable Torque Not a concern for variable torque applications Variable torque applications require little motor current at low speed A properly adjusted variable torque drive will not cause a motor driving a variable torque load to overheat

Drive and Motor Interaction Audible Motor Noise Motor Overheating Motor Insulation Stress Motor Bearing Damage

Motor Insulation Stress Shows up first as an over current trip, ground fault trip or fuse blowing in bypass Motor insulation looks and smells good Megger or Hi Pot test shows shorting between windings or from a winding to ground

Cause of Motor Insulation Stress When current is switched, a coil generates a back voltage The faster the change (dv/dt), the greater the back voltage This can arc through motor insulation

Minimizing Motor Insulation Stress Better motor insulation Standard Motor NEMA MG 1, Part 30: 1000 V peak voltage, 2 µs rise time Special-Purpose Motor NEMA MG 1, Part 31: 1600 V peak voltage, 0.1 µs rise time

Minimizing Motor Insulation Stress Better motor insulation Short wire length to the motor The longer the motor leads, the less the effect of the diodes.

Short Wire Length to the Motor 1000 V 10 Foot Motor Lead 90 Foot Motor Lead 210 Foot Motor Lead Waveforms are for a soft switching drive 200 V/div vertical; 0.2 µs/div horizontal

Slow Switching Power Components So_ Switching IGBT Standard IGBT 90 ft motor leads 200 V/div vertical; 0.5 µs/div horizontal

Output Reactor

Output Reactor Waveforms Drive did not have soft switching No Reactors No Reactors No Reactors With Reactors With Reactors With Reactors 10 Ft Motor Lead 90 Ft Motor Lead 210 Ft Motor Lead 200 V/div vertical; 2 µs/div horizontal

Output dv/dt Filter

Output dv/dt Filter Waveforms Drive did not have soft switching No Filter No Filter No Filter dv/dt Filter dv/dt Filter dv/dt Filter 10 Ft Motor Lead 90 Ft Motor Lead 210 Ft Motor Lead 200 V/div vertical; 2 µs/div horizontal

Reduce the DC Bus Voltage 208 and 230 V: no problem 460 V: some problems, particularly with 10 HP and smaller motors 575 V: more potential problems

Drive and Motor Interaction Audible Motor Noise Motor Overheating Motor Insulation Stress Motor Bearing Damage

Motor Bearing Damage This can cause a washboard pattern to be etched into the bearings Capacitive coupling can couple voltage from the stator to the rotor If this gets too high, voltage can discharge through the motor bearings

Motor Bearing Damage Solutions Reduced motor peak voltage Drives which reduce motor insulation stress also reduce the possibilities of bearing damage

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Sleeve Ceramic bearings SKF Insocoat TM bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft

Motor Bearing Damage Solutions Reduced motor peak voltage Fewer pulses from the drive Insulate the bearings Conductive bearing grease Tighter motor manufacturing tolerances Ground the motor shaft Next presentation topic!

Thank You! Questions?