EA07. Generator Automatic Voltage Regulator Operation Manual

Similar documents
EA06. Generator Automatic Voltage Regulator Operation Manual

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

EA16. Generator Automatic Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

PM300E Voltage Regulator Instruction Manual

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

EG3002. Electronic Engine Governor Controller User Manual

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

GCU-10. Automatic Engine Control Unit Operators Manual

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

EG1069X. Generator Electronic Governor Controller Operation Manual

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

EG3000. Generator Electronic Governor Controller Operation Manual

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

INSTRUCTION MANUAL FOR

XR500B Universal Voltage Regulator

VOLT POT 1K R220. OPEN FOR 60 Hz STAB A.V.R. R220. Installation and maintenance

FAULT FINDING MANUAL. For Stamford AC Generators

TRAC-3 TENSION READOUT AND CONTROL

Coleman Air Diversion Controller Model C40

TROUBLESHOOTING GENERATOR UNITS

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

PRODUCT SERIES: DPG-2100

INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

R231 A.V.R. Installation and maintenance R 231. This manual is to be given to. the end user. Armature 6- Field. Slow-blow fuse 250V 8 A

ESC2301. Universal Electronic Governor Controller Operation Manual

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Coleman Air Diversion Controller Model C40

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

R250 A.V.R. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

INDEX Section Page Number Remarks

BTB TYPE AUTOMATIC TRANSFER SWITCH (ATS)

60 Series Engine Controls

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ

CONTROL FEATURES AVAILABLE OPTIONS

SPECIFICATIONS LOW COST 2404R CHARGER

Boston Gear Ratiotrol

Unit 32 Three-Phase Alternators

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

DKG-114 MANUAL AND REMOTE START UNIT

Flight Systems. Replacement for KASSEC DESCRIPTION

Coleman Air C440-HVM 440 Amp Diversion Controller Version 3.2

EE30181A DC Electronic Load 300 Watt

AA4006 Speed Sensitive Trip Unit. User Manual

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

8,000 Watt Diesel Generator

XP800i POWER INVERTER OWNER S MANUAL

VAC Electrical Requirements. VDC Electrical Requirements

Owner s Manual. PowerVerter PV1000HF, PV1800HF & PV3000HF DC-to-AC Inverters. Contents. Reliable AC Power Wherever You Need It!

A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

Door Operator Conversion Package: Type M to PM/SSC or HPM/SSC with Board 1Ø4

ENGINE GOVERNING SYSTEMS

AFM500X Automatic Flashing Module

DPD72PG1 BILEVEL STEP MOTOR DRIVER PACK With RAMPING PULSE GENERATOR

RigMaster Power Service and Repair Manual Document # S901009

SPECIFICATIONS LOW COST 2404S CHARGER

4291 en /a R220 A.V.R. Installation and maintenance

ESD5500E Series Speed Control Unit

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

OWNER S MANUAL. Please read installation and operation instruction before using this Power inverter.

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

DPBHV001, DPZHV002. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

Explanation 1 Input External Switch 2 Input Hipot Safety Switch

AC Anywhere. User Manual. Power Inverter. (Class II product) Please read the installation and operations instructions before using the Power Inverters

Experiment 3. The Direct Current Motor Part II OBJECTIVE. To locate the neutral brush position. To learn the basic motor wiring connections.

XP600/1100/2000 INSTALLATION AND OPERATION MANUAL

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

XENON POWER SUPPLY 4000 Watt Gladiator IV

Application Engineering

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

SPECIFICATIONS SR

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007)

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

HQST 500W (12V) HQST 1000W (12V) Modified Sine Wave Inverter. User Manual

Handout Activity: HA773

Application Engineering

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave

XR500D-277V Special Voltage Regulator

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

Vehicle Security System

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

13,000 Watt Diesel Generator AGi13P E

THE MODEL D1025 MKII BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-276

ATOTH-G Series BLDC Motor Controller. User s Manual

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

Boston Gear Ratiotrol DC Motor Speed Control

Transcription:

EA07 Generator Automatic Voltage Regulator Operation Manual Suitable for Single or Three Phase Self Excited Brushless Generator Compatible replacement for Mecc Alte SR-7 * Not a genuine Mecc Alte product. Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw

1. SUMMARY EA07 is a self excited Analogue type Automatic Voltage Regulator. The sensing and power inputs are independent and accept power input from the auxiliary winding. The wide voltage adjustment range fulfills any voltage adjustment requirements. 2. SPECIFICATION Sensing Input 4, 5C Voltage Range 80~350VAC 1 phase 50/60Hz Power Input 3A, 5 Voltage 80 ~ 270V 1 phase 50/60Hz Output F+, F Voltage Current Exciter Field DC Resistance 10 ~ 100 Ohm Max. 63 VDC @ 220VAC Continuous 6A Max. Intermittent 7A for 10 sec Voltage Regulation < ±1% (with 4% engine governing) Voltage Build-up Residual voltage at AVR terminal > 5 VAC, 25Hz External VR 100K ohm 1/2 watt ± 7% The EA07 is equipped with adjustable under frequency protection and adjustable over excitation voltage protection for preventing generator from over loading or over excitation. Both protections status are indicated by two individual LED when protection is activated. Also the AVR has a built in EMI filter to prevent interference to the generator. Over Excitation Protection 40~Max VDC @ 0.3~20sec Under Frequency Protection Adjustable range 42 ~ 60 Hz EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max. 5 watt Operating temperature -40 ~ 65 C Storage temperature -40 ~ 80 C Dimensions 97mm L * 92mm W * 39mm H Weight 275g ± 2% High Temperature OUTLINE / DIMENSION 1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will not affects operation. For dimension reference, please see Figure 1. 2. Secure all wiring connection. Do not install AVR at a place with high vibrations to prevent loose connections. For safety do not touch the heat sink while in operation. 3. Fuse specification : 20mm 6.3A / 250V. UNIT : mm Outline and Drilling Diagram Figure 1 2 EA07

3. WIRING / ADJUSTMENTS 3.1 Field Excitation Wiring 3 F+, 1 F Connect AVR terminal 3 to field +, connect AVR terminal 1 to the field. NOTE The Exciter field resistance is between 10~ 100 Ohm. If field resistance is less than 10 Ohm when generator is under full load and the field voltage is under the maximum output, please series a suitable wattage (W) resistor to have the overall field resistance to equal to 10~ 100 Ohm. 3.2 Sensing / Power Input 4, 5C The rated sensing input range is 80 to 350VAC. If the generator voltage is greater than the rated, please connect through N (Neutral) to phase. (Reference from Fig.2). 3.3 Frequency Selection 6, 5A When the terminals 6 & 5A on the AVR are bridged, the system frequency is 60Hz. In the contrary, when bridge is removed the system frequency is 50Hz. 3.4 External Voltage Adjustment VR 7, 5B Connect a 100K Ohm 1/2W voltage rheostat at VR terminals to enable a ±7% voltage adjustment from rated voltage. * The terminals must be bridged when the external voltage adjustment function is none required. 3.5 Power Input 3A, 5 The Power input range is 80 to 270VAC, connecting from either main winding or auxiliary winding. 3.6 VOLT. Voltage Adjustment User can adjust the generator voltage by rotating the VOLT potentiometer on the AVR. Rotate the potentiometer clockwise to increase voltage and decreasing when rotate counterclockwise. The voltage adjust rate is less than 1% when the power factor equals to 1 to 0.8 (PF 1 to 0.8) and frequency variation within 6%. adjustment will cause voltage instability and over adjusting will cause sudden overly voltage variation under heavy load. Analogue type multi voltmeter is suggested when adjusting the voltage stability. Adjust the STAB potentiometer until the pointer on the multi voltmeter is oscillating to its minimal. 3.8 Circuit Protection AMP. Over excitation protection (Overload protection) Set the AMP Overload protection value according to the generator maximum excitation voltage (40~Max VDC). When over excitation occurs maintain the status for a short period of time then decrease the generator voltage down to residual voltage. When the Over excitation protection is activated the yellow LED will illuminate, the higher the over excitation value is the shorter delay time becomes. The generator will require stopping operation to reset. NOTE When AMP potentiometer is adjusted fully clockwise, the Over Excitation protection will be disabled. Hz. Under Frequency Protection Adjustment Hz. Is used to set the under frequency protection knee point. When the generator frequency declines to setting point, the generator voltage will also decrease in the same time to prevent high excitation current from damaging the AVR or the exciter. Adjustment procedure 1. Start generator and let voltage build up. 2. Adjust engine frequency to the appropriate low frequency value. 3. Slowly adjust Hz. Potentiometer until the red LED illuminates. 4. Finally adjust the engine frequency until the LED is turned off. 4. OPERATION PROCEDURE 4.1 Please confirm the follow condition before starting the generator : Starting Setting 3.7 STAB. Stability Adjustment 1. Confirm if the AVR specification conforms to the Slowly and precise adjustment of STAB system requirements? potentiometer can change the respond time between the AVR and generator. Inadequate 2. Confirm the AVR wiring? EA07 3

3. Confirm correct frequency selected? 4. Confirm the generator rated voltage with the AVR sensing input? 5. Adjust VOLT potentiometer fully counterclockwise? Adjust STAB potentiometer to the center position? Adjust AMP potentiometer fully clockwise? 4.2 Starting Generator 1. Reconfirm all setting and wiring. ATTENTION The AVR reading AC voltage are all average value. 2. Start generator and adjust to rated frequency. The first measured voltage value should be under the rated voltage. If not, then reconfirm the start setting. 3. Slowly adjust VOLT potentiometer to the rated voltage, at this time the generator voltage may become unstable. Adjust the STAB. potentiometer anticlockwise, until the oscillation stabilizes. Over adjustment may cause short oscillation when load applied or load type varies. SUGGESTION Adjust the STAB. potentiometer to the point where the oscillation occurs and then adjust the potentiometer counterclockwise by 1/6 of rotation. 4. If voltage can not be adjusted or to the rated value, please check to see if the generator frequency is too slow (Under frequency protection activated). If residual voltage is below 5VAC, then please execute field flashing to help build up the residual voltage. 5. Make sure the generator and AVR are both under normal operation conditions. 6. The voltage adjustable range should be ±1% under no load or full load. If the adjustable range in not within such range, please check the below : Generator under frequency (Lower than low frequency protection knee point). Severely deformed generator output wave form. Capacitive load over ratio (Power factor in lead). Change the AVR and restart. Under over excitation voltage protection (Overload protection). 4.3 Field Flashing When the regulator is operated with the generator for the first time, the polarity residual magnetism may not correct or the magnitude not enough. If the generator does not build-up after startup, shut down the prime mover and proceed with the following steps: 1. Stop generator operation, disconnect AVR + and wirings then apply a DC source (Not grounded) of not more than 12VDC, to generator F+ (Positive) and F (Negative) in series with a limiting resistor of 3 to 5 ohms 20 watt. 2. Allow approximately 3 seconds before removing the dc source. 3. Start generator and measure residual voltage at generator leads 3A, 5. If measured voltage is greater then 5VAC please carefully reconnect all AVR wirings. Please repeat field flashing procedure if less than 5VAC residual voltage is measured. 4. If residual voltage is greater than 5VAC, but AVR still unable to build up voltage, please replace with another AVR. WARNING Overly field flashing may damage the AVR or generator excitation winding. 4.4 Maintenance Regular maintenance to make sure the AVR surface is clean and free from oil or moisture. All connection terminals and wirings must be firmly tightened and no signs of visible oxidation or erosion. ATTENTION All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test equipment must not be used. Use of such equipment could damage the AVR. 4 EA07

F+ F- O/E U/F AMP. HZ. STAB VOLT EXCITER EA07 12 10 8 6 4 2 OUT IN STATOR 11 9 7 5 3 1 Figure 2 Diagram Use only original supplied spare protection fuse for fuse replacement. Please accept our sincere apology if any modification in performance, specification or appearance is made without prior notice. EA07 5