PRODUCTS BULLETIN PRODUCTS CATALOGUE

Similar documents
SMOKE DAMPER - CLASS F MODEL BMSD

COMBINATION FIRE/SMOKE DAMPER - CLASS F MODEL BMFSD (3 HR) / MODEL BEMFSD (1½ HR)

Fire Dampers Catalogue

Shutter Fire Damper Type FSD GFSD 4/1.1/B/1

Standard Installation Fire Damper Models: 319, 319(SS), D39

INSTALLATION INSTRUCTIONS MODEL KFD-555

LLOYD INDUSTRIES INC.

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

table of contents PRODUCT SUMMARY 2

We make dampers easy for you!

BC 03. Fire Dampers FD-GB-30-AS LISTED

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39

CURTAIN TYPE FIRE DAMPER

Model FD-350. Static Rated Fire Dampers 3 Hour Fire Resistance Rating. Application. Ratings. Construction Standard Optional.

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39

Fire, Smoke, and Combination Fire Smoke Dampers

MODEL 151B FIRE DAMPER

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

Standard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

DAMPERS WE CONTROL AIR

Fusible Link (replaceable) Horizontal Mount

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

CFSD Series. Product Description

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

Model FSD-212. Combination FIRE SMOKE DAMPERS

Model FSD-331 Combination Fire Smoke Dampers

Introduction to Johnson Controls Dampers

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

Motorized Fire Dampers

MOTORIZED VOLUME DAMPER

A. Product Data: For each type of product. TLC ENGINEERING FOR ARCHITECTURE - PROJECT NO AIR DUCT ACCESSORIES

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Variable Air Volume Dampers

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Life Safety Dampers. Fire Combination Fire Smoke Smoke Ceiling Radiation

CCS Zone/Bypass Damper Assembly

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

SECTION AXIAL HVAC FANS

Installation, Operation and Maintenance Instructions

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

Model DFD-350. Dynamic Rated Fire Damper 3 Hour Fire Resistance Rating. Application. Ratings. Optional Features

AL-Maraj Central A/C Systems Accessories Mfg Co.

SECTION HVAC POWER VENTILATORS

Part # Installation,Operation and Maintenance Instructions

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features

INDEX. Chapter1 6. air master. Volume Control Dampers

SINGLE DUCT TERMINAL UNITS

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

Fusible Link (replaceable) Horizontal Mount

Control Dampers and Fire Dampers. Volume 1 - March Insulated Control Dampers. Non-Insulated Control Dampers. Framing. Accessories.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION DUCTWORK ACCESSORIES

ARROW INDUSTRIAL PRODUCTS

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

ROOFMASTER STEF-HT ROOF FAN

SECTION CENTRIFUGAL HVAC FANS

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

POWERS Controls No. 4 Pneumatic Damper Actuator

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

YCCS Zone/Bypass Damper Assembly

Installation, Operation and Maintenance Manual

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

YCCS Zone/Bypass Damper Assembly

WE GUIDE AIR LOUVERS

7/S5 FIRE DAMPER FD40. v 2.9 (en)

CONTROL DAMPERS. Models 1810 & Model Model Model 1370

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

Model FD Static Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

Automatic Roof Door Vents

Installation, Operation and Maintenance Manual

FSD60/MFSD60 Multi-blade Fire Damper

I nsulati o n CATALOG OF MATERIALS, TOOLS & ACCESSORIES

Life Safety Dampers - International. Fire Combination Fire Smoke Smoke Ceiling Radiation

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

MULTI-BLADE FIRE DAMPERS

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper.

Model FDD Dynamic Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

Dampers. Louvers. Caring for Human Life & Property (FIRE, SMOKE & HVAC) NAFFCOFlow.com

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A

CEILING DAMPERS GENERAL PRODUCT OVERVIEW CEILING DAMPERS MODELS 0716, , 0714 & 0722 FOR SQUARE, RECTANGULAR OR ROUND DUCTS

SV-UNOBOX FAN. Mutassim Al-Daour factory for Metal Industries SV-7

Section Content. Straight Curve Optional Equipment and Devices

Inside Front cover White

ACCESS DOORS GENERAL PRODUCT OVERVIEW

FAN POWERED TERMINAL UNITS

NR series. Circular CAV air volume control terminals with system powered mechanical regulator

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

SINGLE DUCT AIR TERMINAL UNITS

SD-1250 and SD-1600 Series Smoke Dampers

to obtain the specified voids due

Transcription:

FIRE DAMPERS WE SAVE LIVES PRODUCTS BULLETIN PRODUCTS CATALOGUE

Dubai Head Office: Tel: +971 4 706 97777 Fax: +971 4 706 9787 Abu Dhabi Branch: Tel: +971 2 645 0107 Fax: +971 2 645 0167 Email: beta@betag.com P.O. Box 50708, Dubai United Arab Emirates www.betag.com

index FDF FIRE DAMPER FOR STATIC SYSTEMS FDC FIRE DAMPER FOR STATIC SYSTEMS FDC FIRE DAMPER FOR DYNAMIC SYSTEMS ACCESS DOOR 1-4 5-9 10-14 15-16

FIRE DAMPER MODEL FDF FIRE DAMPER FOR STATIC SYSTEM - FDF MODEL - SINGLE SECTION FEATURES: U.L. Classified for static system in accordance with UL 555 & NFPA 90A. Civil Defense approved Fire rated for 1½ hour. CONSTRUCTION Casings: 1.2 mm thick manufactured from corrosion resistant galvanized mild steel Blades: Rollformed single skin interlocking galvanized curtain shutter of 0.8 mm thk Blade guide / Locking ramps: Galvanized steel locking ramps ensures positive blade closure within integral blade guide. o Fusible Link: Typical two-pleces fusible links rated at 165 F. Springs: Stainless steel coil tension spring. Mounting; Horizontal / Vertical (Installation as per instruction on page no 4) Sizes: Maximum Width 31 & Maximum Height 33 (Out to Out) Sleeves: are optional. details are as per pages 3 & 4 Casings Manufactured from corrosion Resistant galvanized steel as Standard Blade guide / Locking ramps Galvanized steel locking ramps ensures positive blade closure within integral blade guides. Springs Stainless steel coil tension spring ensuring powerful blade closure when appropriate Fubible links / release mechanism Typical two-pieces fusible links O rated at 165 F Alternative temperature rated fusible links mechanisms available Blades (Rollformed single skin interlocking galvanized high integrity curtain shutter of 0.8 mm thickness)

FIRE DAMPER MODEL FDF 80MM W + 40 MM 25MM H + 20 + X MM H - 5 MM 30 MAX W - 5 MM 30 MAX 100% Free Area fire damper FDF Figure - 2 X-DIMENSIONAL FDF Height (mm) X (mm) 100-400 40 401-750 60

FIRE DAMPER MODEL FDF CROSS SECTION DETAIL 7 Surrounding Masonry Floor or Wall 6 EXPANSION GAP Mounting Channel COVER ANGLE 38x38x3mm thk M6 Bolt & Nut 4 SLEEVE 3 2 DUCT by others BLADE FUSIBLE LINK M6 Bolt & Nut 5 FDP Firedamper 1 DUCT by others BLADE RAMP Duct Sleeve Connection SPRING 90mm as a minimum 152mm maximum Figure - 3 Surrounding Masonry Floor or Wall 7 ORDERING SYSTEM TYPE MOUNTING SIZE OPTIONS FDS - SLEEVE Size: Width x Height H: HORIZONTAL V: VERTICAL FDF: 100% Free area fire damper

FIRE DAMPER MODEL FDF INSTALLATION & OPERATING INSTRUCTIONS 1 >> The damper 1 should be installed centrally within surrounding masonry floor or wall 7 2>> The damper 1 should be installed in a rectangular galvanized steel sleeve 2 with a min. thickness of 1.2 mm This sleeve should be attached to the damper not to the builder s work using the mounting channels by 6mm dia 5 bolts spaced at not more than 255mm centres. Bolts for mounting channels located maximum 45 and 145 mm from corners of sleeve and frame, perspectively. 3>> The damper is suitable only for rectangular space and can not be used for annular space. 4>> Allowance for expansion between sleeve and builder s work in both horizontal and vertical planes to be 3mm per 305mm of length. 5>> The sleeve 2 should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90mm and maximum of 152mm beyond the floor or wall. 6>> The cover angles 3 should be attached to the sleeve by 6mm dia 4 bolts at a minimum of 225mm centres, and should form a complete frame around the sleeve and cover over the expansion gap 6 required between sleeve and wall opening. The four corner of the cover angles are not to be welded. The bolts connecting the cover angles to the sleeve to be 102mm maximum from the corners. 7>> The expansion gap 6 should be filled with compressible, non-combustible material (mineral wool). 8>> The cover angle 3 should be of such a size as always to from a cover over the wall opening by 25mm minimum and should be manufactured from a minimum size of 38*38*3mm steel angle 9>> A fusible link UL tested Elsie brand which is rated at 165 degree F is used. 10>> The duct-sleeve connection to be of double S slip type. Breakaway joints shown shall have no more than two No. 10 (4.8 mm dia.) sheet metal screws on each side and on the bottom located in the center of the slip pocket and shall penetrate both sides of the slip pocket. Breakaway joints for horizontal ducts (vertical fire damper) shall be provided on the top, bottom and on the sides with double S slip type as illustrated. Breakaway joints for vertical ducts (horizontal fire damper) shall be provided on both other opposite sides with double S slip type. Connecting ducts shall not be continued and shall terminate at the sleeve. Installation shall comply with NFPA 9OA. 11>> All fixing of frames must be positioned clear of damper blade path so as not to impede proper closure.

FIRE DAMPER FOR STATIC SYSTEM - FDC MODEL - SINGLE & MULTIPLE SECTIONS SINGLE SECTION FDC (100% FREE AREA) FDC (NOT 100% FREE AREA) MULTIPLE SECTION FDC (NOT 100% FREE AREA)

FIRE DAMPER FOR STATIC SYSTEMS - FDC MODEL - SINGLE & MULTIPLE SECTIONS FEATURES: UL classified for static systems in accordance with UL 555 & NFPA 90A Civil Defence Approved O Fusible link set at 165 F Fire rated for 1½ hour Mounting type: vertical MAXIMUM UL CLASSIFIED SIZES (OUT TO OUT) section SINGLE MULTIPLE MAXIMUM WIDTH ( ) 36 72 MAXIMUM HEIGHT ( ) 36 72 CONSTRUCTION Riser Angle (Optional) galvanized steel 0.9mm min thick Steel Rivet Sleeve (Optionally by Fire Damper Manufacturer) more details in installation and operating instructions Casing roll formed 0.9 mm thick manufactured from galvanized steel coil Blade guide / locking ramp galvanized steel locking ramp ensures positive blade closure within integral blade guide Springs stainless steel coil tension spring ensuring powerful blade closure when appropriate Bottom Angle galvanized steel 0.9mm min thick Figure 1 Fusible link O set at 165 F Blades roll formed single skin interlocking galvanized steel (.8mm thick) of high integrity curtain shutter Sleeve (optionally by fire damper manufacturer) Blade Fusible link Locking ramp Blade Fusible link Locking ramp Blade Riser angle (optional) Fusible link Steel rivet Locking ramp Spring Cross sectional view multiple section Cross sectional view single section Figure 2

INSTALLATION AND OPERATING INSTRUCTIONS 1. The damper 1 should be installed centrally within the surrounding masonry / gypsum floor or wall 7 2. The damper 1 should be installed in rectangular galvanized steel sleeve 2 (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder s work using steel rivets 5 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½ ) 3. The damper is suitable only for rectangular space and can not be use for annular space. 4. Allowance for expansion between sleeve and builders work in both horizontal and vertical planes to be 3mm per 305 mm of length and width. 5. The sleeve 2 (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1. 6. The mounting angles 3 should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap 6 required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts. 7. The mounting angles 3 should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle. O 8. A fusible link is UL tested, Elsie brand, set at 156 F 9. The duct--sleeve connection to be of as per what shown in (figure5) page 8 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A 10. All fixing of frames must be positioned clear of the damper blade path so as not to impede proper closure. Sleeve Thickness (mm) 0.9 1.2 1.5 2 TABLE 1 7 Surrounding Masonry Gypsum Floor or wall/partition 6 expansion gap DUCT by others without riser angle (not 100% free area) DUCT by others without riser angle (100% free area) 5 Steel rivet dia.4.8x12 (mm) (35 mm) Mounting angle 3 35x35x2.5 Mounting angle 4 35x35x2.5 SLEEVE 2 (optionally by fire damper mfg.) Riser angle (optional) FDC 1 Fire damper Duct Sleeve (Connection) Figure 3 90mm as minimum 152mm maximum (CROSS SECTION DETAILS) SINGLE SECTION FDC FIX TO WALL 11. In Multiple Section FD, center cross section point which obtain from attaching four individual section are welded from two sides. In multiple section FD, individual section FD attached with each other by steel rivet 4.8mm dia, space between rivet not more than 12. 225 mm centers, and (½ ) 13 mm from the corners. 13. Multiple section FD is enclosed with a single rectangular galvanized steel sleeve (optionally by Fire Damper Manufacturer). The fixing of the sleeve to the FD frame using steel rivet 4.8mm dia. Space not more than 225mm center to center and (½ ) 13mm from corners. Sleeve (optionally by Fire Damper Manufacturer) thickness as per what mentioned on Table no.1 14. The maximum size of the multiple fire damper assembly that is assembled is 72 x72. 15. In multiple section FD, The maximum size of the individual section that are attached together is 36 x36. 35mm Figure 4 (FRONT VIEW) MULTIPLE SECTION FDC WITH SLEEVE Center cross section welded point from both sides 35mm

DUCT - SLEEVE CONNECTIONS HEMMED S SLIP INSIDE SLIP JOINT DOUBLE S SLIP PLAIN S SLIP STANDING S SLIP STANDING S SLIP (ALTERNATE BAR) STANDING S SLIP (ANGLE REINFORCED) STANDING S SLIP (BAR REINFORCED) Figure - 5 EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE Figure - 6 ASSEMBLY PROCEDURES: 1. Fix the damper A into the sleeve B matching their center axis and hole provision using steel rivet 2. If the riser angle (optional) is use then, fix the riser angle F (optional) into the fire damper sleeve matching their hole provision using steel rivet. If not go to step no. 3. 3. Fix the fire damper with sleeve into the concrete / gypsum wall E opening by a front mounting angle C 35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm per 305 mm of length and width. 4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle D 35 x 35 matching their hole provision using M8 Hex bolt and nut.

* SINGLE SECTION Type Mounting Size Options ORDERING SYSTEM riser angle FDC 100% FREE AREA Vertical FDC (100%) Free area H W FDC-sleeve (optionally by FD Manufacturer) size: Width x Height SIZES RANGE ( mm ) 80-825 100-915 ( inches ) 3.2-32.5 4-36 X ( mm ) 25 50 75 90 H ( mm ) 80 -- 150 151 -- 450 451 -- 650 651 -- 825 H-5mm W-5mm 116 mm Figure - 7 H-5+X mm FDC NOT 100% FREE AREA Type Mounting Size Vertical Options FDC not 100% Free area FDC-sleeve (optionally by FD Manufacturer) size: Width x Height H W SIZES RANGE ( mm ) ( inches ) 100 915 100-915 4-36 4-36 H-5mm W5 - mm 116 mm Figure - 8 * MULTIPLE SECTION FDC NOT 100% FREE AREA Type Mounting Size Options Vertical FDC-sleeve (optionally by FD Manufacturer) size: Width x Height H-5mm FDC not 100% Free area SIZES RANGE W-5mm H Multiple section ( mm ) ( inches ) above 915 1830 above 36 72 116 mm W above 915 1830 above 36 72 Figure - 9

FIRE DAMPER FOR DYNAMIC SYSTMES - FDC MODEL - SINGLE SECTION FDC (100% FREE AREA) FDC (NOT 100% FREE AREA)

FIRE DAMPER FOR DYNAMIC SYSTEMS - FDC MODEL - SINGLE SECTION FEATURES: MAXIMUM UL CLASSIFIED SIZE (OUT TO OUT) UL classified for dynamic systems in accordance with UL 555 & NFPA 90A Civil Defense approved O Flusible link set at 165 F Fire rated for 1½ hour Mounting type: vertical 2 Flow rating is 2000 cfm / ft Static pressure is4 in.wc SECTION SINGLE MAXIMUM WIDTH ( ) MAXIMUM HEIGHT ( ) 36 36 CONSTRUCTION Steel Rivet Riser Angle (Optional) galvanized steel 0.9mm min thick Sleeve (Optionally by Fire Damper Manufacturer) more details in installation and operating instructions Casing roll formed 0.9mm thick manufactured from galvanized steel coil Blade guide / locking ramp galvanized steel locking ramp ensures positive blade closure within integral blade guide Springs stainless steel coil tension spring ensuring powerful blade closure when appropriate Bottom Angle galvanized steel 0.9mm min thick Figure 1 Fusible link O set at 165 F Blades roll formed single skin interlocking galvanized steel (.8mm thick) of high integrity curtain shutter Blade Riser Angle (optional) Fusible link Steel rivet Locking ramp Srings Cross sectional view single section Figure 2

INSTALLATION AND OPERATING INSTRUCTIONS 1. The damper 1 should be installed centrally within the surrounding masonry / gypsum floor or wall 7 2. The damper 1 should be installed in rectangular galvanized steel sleeve 2 (optionally by Fire Damper Manufacturer) with a minimum thickness of 0.9mm. this sleeve should be attached to the damper not to the builder s work using steel rivets 5 4.8mm dia. and spaced at not more than 225mm centers and 13 mm from corners (½ ) 3. The damper is suitable only for rectangular space and can not be use for annular space. 4. Allowance for expansion between sleeve and builders work in both horizontal and vertical planes to be 3mm per 305 mm of length and width. 5. The sleeve 2 (optionally by Fire Damper Manufacturer) should be of suitable length to extend through the wall to enable the fitting of the cover angles and ductwork. Minimum of 90 mm and maximum 152 mm beyond the floor or wall / include thicknesses of sleeve in table 1. 7. The mounting angles 3 should be of such a size as always to form an overlap with the wall / floor by 25 mm minimum and should be manufactured from a minimum size of 35x35x2.5mm Gl angle. O 8. A fusible link is UL tested, Elsie brand, set at 156 F Sleeve Thickness (mm) 9. The duct--sleeve connection to be of as per what shown in (figure4) page 13 Connecting ducts shall not be continuous and shall terminate at the sleeve. Installation shall comply with NFPA 90A 10. All fixing of frames must be positioned dear of the damper blade path so as not to impede proper closure. 0.9 1.2 1.5 2 TABLE 1 6. The mounting angles 3 should be attached to the sleeve (optionally by Fire Damper Manufacturer) by 8mm dia 4 bolts at a maximum of 225mm centers, and should form a complete frame around the sleeve and cover over the expansion gap 6 required between sleeve and wall / floor opening. The four corners of the mounting angles are not to be welded. The bolts connecting the mounting angles to the sleeve to be 102 mm maximum from the corners. Mounting angles will be send in loose parts. 7 Surrounding Masonry Gypsum Floor or wall/partition 6 expansion gap DUCT by others without riser angle (not 100% free area) DUCT by others without riser angle (100% free area) 5 Steel rivet dia.4.8x12 (mm) Mounting angle 3 35x35x2.5 Mounting angle 4 35x35x2.5 SLEEVE 2 (optionally by fire damper mfg.) Riser angle (optional) FDC 1 Fire damper (35 mm) Duct Sleeve (Connection) Figure 3 90mm as minimum 152mm maximum (CROSS SECTION DETAILS) SINGLE SECTION FDC FIX TO WALL

DUCT - SLEEVE CONNECTIONS HEMMED S SLIP INSIDE SLIP JOINT DOUBLE S SLIP PLAIN S SLIP STANDING S SLIP STANDING S SLIP (ALTERNATE BAR) STANDING S SLIP (ANGLE REINFORCED) STANDING S SLIP (BAR REINFORCED) Figure - 4 EXPLODED ASSEMBLY FOR FDC TYPE WITH SLEEVE Figure - 5 ASSEMBLY PROCEDURES: 1. Fix the damper A into the sleeve B matching their center axis and hole provision using steel rivet 2. If the riser angle (optional) is use then, fix the riser angle F (optional) into the fire damper sleeve matching their hole provision using steel rivet. If not go to step no. 3. 3. Fix the fire damper with sleeve into the concrete / gypsum wall E opening by a front mounting angle C 35x35 matching their hole provision using M8 Hex bolt and nut. Opening size should have clearance of 3 mm per 305 mm of length and width. 4. Finally when the Fire Damper with sleeve is already fitted to the wall, fix the back mounting angle D 35 x 35 matching their hole provision using M8 Hex bolt and nut.

ORDERING SYSTEM FDC 100% FREE AREA riser angle Type Mounting Size Options FDC-sleeve (optionally by FD Manufacturer) H-5mm Vertical FDC (100%) Free area size: Width x Height W - 5 m m H-5+X mm H W SIZES RANGE ( mm ) ( inches ) 80-825 3.2-32.5 100-915 4-36 X ( mm ) 25 50 75 90 H ( mm ) 80 -- 150 151 -- 450 451 -- 650 651 -- 825 116 mm Figure - 6 FDC not 100% FREE AREA Type Mounting Size Options FDC-sleeve (optionally by FD Manufacturer) H-5mm size: Width x Height Vertical W-5mm FDC not 100% Free area 116 SIZES RANGE ( mm ) ( inches ) Figure - 7 mm H 100-915 4-36 W 100-915 4-36

ACCESS DOOR Beta Access Doors are made of Galvanized mild steel sheets of 1.20mm thickness The Insulation is Manson thickness is 1 3 3 Higher Insulation thickness can also be provided, upon request. The Density is 24kg/ m (1.5 lb/ft ) Opening and Closing is achieved through a Cam Lock ORDERING SYSTEM TYPE SIZE SIZE: WIDTH X HEIGHT ACD. ACCESS DOOR WITHOUT HINGES ACDH; ACCESS DOOR WITH HINGES WIDTH + 2 X 25 HEIGHT - 5 HEIGHT + 2 x 25 Figure 1 ACCESS DOOR ASSEMBLY WITH 1 CAM LOCK & HINGE WIDTH - 5 CAM LOCK CONTINOUS HINGE 20 25 WIDTH - 5 HEIGHT - 5 25

ACCESS DOOR WIDTH + 2X25 HEIGHT - 5 HEIGHT + 2 X 25 WIDTH - 5 Figure - 2 ACCESS DOOR ASSEMBLY WITH 2 CAM LOCK CAM LOCK FRAME WIDTH - 5 DOOR PANEL - A DOOR PANEL - B 25 20 25 HEIGHT - 5