, RED Electronically Controlled Inverter Driven Circulation Pump Twin Execution ENERGY EFFICIENCY OF CIRCULATING PUMPS Directive of the European Parliament COMMISSION REGULATION (EC) No. 641/2009 and 622/2012 Eco-design Directive of Energy Using Products (ErP Directive - Energy related Products). The European Union wants to improve the design of equipment that consume significant energy e.g. (televisions, refrigerators, washing machines, boilers, pumps, and motors etc.). To improve eco design providing environmental sustainability, reducing negative environmental impact as the consequence of production, use and disposal of products. The objective of the Directive is to force manufacturers and importers to produce and distribute products with high energy efficiency, and carbon output. The criteria for eco-design will be an integral part of the declaration of conformity (CE), which is a necessary requirement/mark for products being sold in the EU. This Regulation shall not apply to: a) drinking water circulators b) circulators integrated in products and placed on the market not later than 1 January 2020 as replacement for identical circulators integrated in products and placed on the market no later than 1 August 2015. The replacement product or its packaging must clearly indicate the product(s) for which it is intended. This Regulation shall apply in accordance with the following timetable: 1. from 1 January 2013, glandless standalone circulators shall meet the efficiency level (EEI) less than 0.27, with the exception of those specifically designed for primary circuits of thermal solar systems and of heat pumps. 2. from 1 August 2015, glandless standalone circulators and glandless circulators integrated in products shall meet the efficiency level (EEI) less than 0.23. This Regulation shall apply to: Stand-alone* or integrated** circulators with the motor immersed in the pumped medium, with hydraulic power from 1 up to 2500 W, designed for use in heating systems or in secondary circuits of cooling distribution systems. * Stand alone circulators are commonly available on the market. ** circulators integrated in products are component of a device, such as boilers, heat pumps, etc. 11
RE 25-80/180 can adapt to current needs of the system with proportional or constant pressure regulation. : After selecting level pump recognizes the lowest resistance of the system and automatically adjusts its own strain. : After selection pump works in three different speeds. Energy savings Easy handling and installation Robust and compact construction for long-lasting Automatic venting Low noise operation Single body, which allows a variety of mounting positions Flow Q up to 4,5 m 3 /h Pressure H up to 8 m Power 7-75 Watt Nominal pressure 10 Bar Permissible mediums of water with over 20% of glycol. Medium temperature from +5 C to +95 C with max. surroundings 0,05 bar < 75 C temperature of medium 0,28 bar < 90 C temperature of medium The energy index EEI <= 0,24 - Part 2 Control Δp or constant speed Insulation Class: F 12
RE 25-120/180 Night mode Energy savings Easy handling and installation Plug & Play Robust and compact construction for long-lasting Automatic venting Low noise operation Flow Q up to 11 m 3 /h Pressure H up to 12 m Power 10-180 Watt Nominal pressure 10 Bar Permissible mediums of water with over 20 % of glycol. Medium temperature from +2 C to +110 C with max. surroundings 0,05 bar < 75 C temperature of medium 0,28 bar < 90 C temperature of medium The energy index EEI <= 0,21 - Part 2 Insulation Class: F 13
RE 40-120/250 Night mode Energy savings Easy handling and installation Plug & Play Robust and compact construction for long-lasting Automatic venting Low noise operation Flow Q up to 23 m 3 /h Pressure H up to 12 m Power 25-480 Watt Nominal pressure 6/10 Bar Permissible mediums: of water with over 20% of glycol. Medium temperature from +2 C to +110 C with max. surroundings 0,05 bar < 75 C temperature of medium 0,28 bar < 90 C temperature of medium The energy index EEI <= 0,21 - Part 2 Insulation Class: F 14
RE 40-180/250 D option, twin pump Easy operation and simple installation Communication - Ethernet connection - 1 relay output - 2 digital inputs Flow Q up to 31 m 3 /h Pressure H up to 18 m Power 20-800 Watt Nominal pressure 6/10 Bar Permissible mediums of water with over 20 % of glycol. Medium temperature from -10 C to +110 C with max. surroundings 0,5 bar < 50 C temperature of medium 0,8 bar < 80 C temperature of medium 1,4 bar < 110 C temperature of medium The energy index EEI <= 0,27 - Part 2 Methods of control - Current Control (limit current) - Power Control (limit power) - Constant pressure control (Δp-c) - Dp prop (Δp-v) - Option settings QH curve at fixed speeds - Constant speed Insulation Class: H 15
RE 50-120/280 permanent magnets and integrated electronic which the pumps can adapt to current needs of the system. D option, twin pump It is used for circulation of water or a mixture of water/glycol in heating systems, air conditioning systems and circulation systems. Easy operation and simple installation Communication - Ethernet connection - 1 relay output - 2 digital inputs Flow Q up to 39 m 3 /h Pressure H up to 13 m Power 26-800 Watt Nominal pressure 6/10 Bar Permissible mediums: of water with over 20% of glycol. Medium temperature from -10 C to +110 C with max. surroundings 0,5 bar < 50 C temperature of medium 0,8 bar < 80 C temperature of medium 1,4 bar < 110 C temperature of medium The energy index EEI <= 0,26 - Part 2 Methods of control - Current Control (limit current) - Power Control (limit power) - Constant pressure control (Δp-c) - Dp prop (Δp-v) - Option settings QH curve at fixed speeds - Constant speed Insulation Class: H 16
RE 50-180/280 D option, twin pump Easy operation and simple installation Communication - Ethernet connection - 1 relay output - 2 digital inputs Flow Q up to 45 m 3 /h Pressure H up to 17 m Power 20-1000 Watt Nominal pressure 6/10 Bar Permissible mediums of water with over 20% of glycol. Medium temperature from -10 C to +110 C with max. surroundings 0,5 bar < 50 C temperature of medium 0,8 bar < 80 C temperature of medium 1,4 bar < 110 C temperature of medium The energy index EEI <= 0,26 - Part 2 Methods of control - Current Control (limit current) - Power Control (limit power) - Constant pressure control (Δp-c) - Dp prop (Δp-v) - Option settings QH curve at fixed speeds - Constant speed Insulation Class: H 17
Dimensions Model Diameter DN mm PN kg RE 25-80/180 1 25 180 10 BAR 2,4 RE 25-120/180 1 25 180 10 BAR 3,2 RE 40-120/250-40 250 6/10 BAR 9 RE 40-180/250-40 250 6/10 BAR 56 RE 50-120/280-50 280 6/10 BAR 30 RE 50-180/280-50 280 6/10 BAR 30 Model h DN D2 b b1 b2 b4 l a RE 25-80/180 180 25 1-80 48-108 - RE 25-120/180 180 25 6/4 117 - - - 190 53 RE 40-120/250 250 40-146 - - - 260 65 RE 40-180/250 250 40 - - 198 - - 355 65 RE 50-120/280 280 50 - - 200 - - 355 70 RE 50-180/280 280 50 - - 200 - - 355 70 Pump Component Housing Material Cast Iron Impeller Polyamid (For RE 25-80/180) PES (For RE 25-120/180,RE 40-120/250) Stainless Steel (For 40-180/250, RE 50-120/280, RE 50-180/280) Shaft Ceramics (For RE 25-80/180) Stainless Steel (For 25-120/180, RE 40-120/250, RE 40-180/250, RE 50-120/280, RE 50-180/280) Bearings Ceramics (For RE 25-80/180) Graphite (For 25-120/180, RE 40-120/250, RE 40-180/250, RE 50-120/280, RE 50-180/280) Ventricular Wall for RE 25-80/180, RE 25-120/180, RE 40-120/250 Stainless Steel Seperating Bush for RE 40-180/250, RE 50-120/280, RE 50-180/280 Rotor Can Stainless Steel 18
D 32-100/180-TWIN RED Electronically Controlled, Inverter Driven, Twin Execution Circulation Pump Twin pump Night Mode Energy savings Easy handling and installation Plug & Play Robust and compact construction for long-lasting Automatic venting Low noise operation Flow Q up to 11 m 3 /h Pressure H up to 10 m Power 10-180 Watt Nominal pressure 10 Bar Permissible mediums: of water with over 20 % of glycol. Medium temperature from +2 C to +110 C with max. surroundings 0,05 bar < 75 C temperature of medium 0,28 bar < 90 C temperature of medium The energy index EEI <= 0,21 - Part 2 Insulation Class: H 19
D 40-180/250-TWIN RED Electronically Controlled, Inverter Driven, Twin Execution Circulation Pump Twin pump Easy operation and simple installation Communication - Ethernet connection - 1 relay output - 2 digital inputs Flow Q up to 31 m 3 /h Pressure H up to 18 m Power 20-800 Watt Nominal pressure 6/10 Bar Permissible mediums of water with over 20% of glycol. Medium temperature from -10 C to +110 C with max. surroundings 0,5 bar < 50 C temperature of medium 0,8 bar < 80 C temperature of medium 1,4 bar < 110 C temperature of medium The energy index EEI <= 0,27 - Part 2 Methods of control - Current Control (limit current) - Power Control (limit power) - Constant pressure control (Δp-c) - Dp prop (Δp-v) - Option settings QH curve at fixed speeds - Constant speed Insulation Class: H 20
D 50-180/280-TWIN RED Electronically Controlled, Inverter Driven, Twin Execution Circulation Pump Twin pump Easy operation and simple installation Communication - Ethernet connection - 1 relay output - 2 digital inputs Flow Q up to 45 m 3 /h Pressure H up to 17 m Power 20-1000 Watt Nominal pressure 6/10 Bar Permissible mediums of water with over 20% of glycol. Medium temperature from -10 C to +110 C with max. surroundings 0,5 bar < 50 C temperature of medium 0,8 bar < 80 C temperature of medium 1,4 bar < 110 C temperature of medium The energy index EEI <= 0,26 - Part 2 Methods of control - Current Control (limit current) - Power Control (limit power) - Constant pressure control (Δp-c) - Dp prop (Δp-v) - Option settings QH curve at fixed speeds - Constant speed Insulation Class: H 21
D Electronically Controlled, Inverter Driven, Twin Execution Circulation Pump Dimensions Model Diameter DN mm PN kg RED 32-100/180 1¼" 32 180 10 BAR 8,2 RED 40-180/250 40 250 6/10 BAR 56 RED 50-180/280 50 280 6/10 BAR 59 Model h DN D2 b b1 b2 b4 l a RED 32-100/180 180 32 2" 297 190 56 RED 40-180/250 250 40 403 355 65 RED 50-180/280 280 50 403 355 70 Pump Component Housing Shaft Bearings Ventricular Wall for For RED 32-100/180) Seperating Bush for RED 40-180/250, RED 50-180/280 Rotor Can Material Cast Iron PES (For RED 32-100/180) Stainless Steel (RED 40-180/250, RED 50-180/280) Stainless Steel Graphite Stainless Steel Stainless Steel 22