CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

Similar documents
AC MOTOR TYPES. DESCRIBE how torque is produced in a single-phase AC motor. EXPLAIN why an AC synchronous motor does not have starting torque.

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

2014 ELECTRICAL TECHNOLOGY

DEPARTMENT OF EI ELECTRICAL MACHINE ASSIGNMENT 1

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

R07 SET - 1

Pretest Module 21 Units 1-3 AC Generators & Three-Phase Motors

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

The Wound-Rotor Induction Motor Part I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Electrical Machines -II

Unit III-Three Phase Induction Motor:

VALLIAMMAI ENGINEERING COLLEGE

Doubly fed electric machine

Date: Name: ID: LABORATORY EXPERIMENT NO. 8 INDUCTION MOTOR/GENERATOR 8-1

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad

Lesson 16: Asynchronous Generators/Induction Generators

Synchronous Generators I. Spring 2013

Contents. Review of Electric Circuitd. Preface ;

Induction Generator: Excitation & Voltage Regulation

(d) None of the above.

Renewable Energy Systems 13

Lecture 20: Stator Control - Stator Voltage and Frequency Control

Synchronous Generators I. EE 340 Spring 2011

Regulation: R16 Course & Branch: B.Tech EEE

CHAPTER 1 INTRODUCTION

NOVEL METHOD OF EVALUATING THE STEADY- STATE PERFORMANCE CHARACTERISTICS OF THREE PHASES SELF EXCITED INDUCTION GENERATOR

DC CIRCUITS ELECTROMAGNETISM

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

ELECTRIC MACHINES OPENLAB 0.2 kw

ECE 325 Electric Energy System Components 6 Three Phase Induction Motors. Instructor: Kai Sun Fall 2016

ESO 210 Introduction to Electrical Engineering

CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL

Pretest Module 21 Unit 4 Single-Phase Motors

694 Electric Machines


INTRODUCTION. I.1 - Historical review.

Induction Motor Control

Fachpraktikum Elektrische Maschinen. Theory of Induction Machines

Converteam: St. Mouty, A. Mirzaïan FEMTO-ST: A. Berthon, D. Depernet, Ch. Espanet, F. Gustin

10. Starting Method for Induction Motors

Institute of Technology, Nirma University B. Tech. Sem. V: Electrical Engineering 2EE305: ELECTRICAL MACHINES II. Handout: AC Commutator Motors

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR CLASSIFICATION. 2010, The McGraw-Hill Companies, Inc.

CHAPTER 4 HARDWARE DEVELOPMENT OF DUAL ROTOR RADIAL FLUX PERMANENT MAGNET GENERATOR FOR STAND-ALONE WIND ENERGY SYSTEMS

2-marks question bank UNIT I - TRANSFORMERS UNIT II: AC MACHINES

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

ROTOR RESISTANCE SPEED CONTROL OF WOUND ROTOR INDUCTION MOTOR

EE6401 ELECTRICAL MACHINES I UNIT I: MAGNETIC CIRCUITS AND MAGNETIC MATERIALS PART: A 1. Define EMF and MMF. 2. Name the main magnetic quantities

ECE1750, Spring Motor Drives and Other

9. Examples of hydro energy conversion

Study and Measure the Active and Reactive Power Developed By a Three Phase Induction Generator with Capacitive Load

SIMULINK Based Model for Determination of Different Design Parameters of a Three Phase Delta Connected Squirrel Cage Induction Motor

CHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

Electrical Machines II. Week 5-6: Induction Motor Construction, theory of operation, rotating magnetic field and equivalent circuit

Chapter 3.2: Electric Motors

ANALYSIS OF WIND AND PV SYSTEMS 4.1 Wind Energy Conversion Systems (WECS)

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

CHAPTER THREE DC MOTOR OVERVIEW AND MATHEMATICAL MODEL

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR


R13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]

St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad

Electrical Machines and Energy Systems: Overview SYED A RIZVI

GROUP OF INSTITUTIONS :: PUTTUR UNIT I SINGLE PHASE TRANSFORMERS

Starting of Induction Motors

Dev Bhoomi Institute Of Technology LABORATORY Department of Electrical And Electronics Engg. Electro-mechanical Energy Conversion II

Synchronous Motor Drives

VIII. Three-phase Induction Machines (Asynchronous Machines) Induction Machines

ROTATING MAGNETIC FIELD

INDUCTION MOTOR. There is no physical electrical connection to the secondary winding, its current is induced

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

CHAPTER 1 INTRODUCTION

Load Test On 3 Phase Slip Ring Induction Motor Lab Manual

Research and Reviews: Journal of Engineering and Technology

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Asynchronous slip-ring motor synchronized with permanent magnets

Permanent Magnet Motors for ESP Applications Updating the Track Record of Performance. Lorne Simmons VP Sales & Marketing

Unit 34 Single-Phase Motors

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

Workshop on Grid Integration of Variable Renewable Energy: Part 1

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

SYLLABUS 1. SYNCHRONOUS GENERATOR 9 2. SYNCHRONOUS MOTOR 8

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

Electrical Machines-I (EE-241) For S.E (EE)

Principles of Doubly-Fed Induction Generators (DFIG)

AUCOM WHITE PAPER SERIES GET YOUR MOTOR RUNNING. An introduction to reduced voltage starting of three phase induction motors

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

CHAPTER 6 POWER QUALITY IMPROVEMENT OF SCIG IN WIND FARM USING STATCOM WITH SUPERCAPACITOR

SYNCHRONOUS GENERATOR (ALTERNATOR)

Statcom Operation for Wind Power Generator with Improved Transient Stability

ST.ANNE S COLLEGE OF ENGINEERING AND TECHNOLOGY ANGUCHETTYPALAYAM, PANRUTI

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Electrical Theory. Generator Theory. PJM State & Member Training Dept. PJM /22/2018

Abstract- A system designed for use as an integrated starter- alternator unit in an automobile is presented in this paper. The

Commission 400Hz Power Supply

CHAPTER 2 SELECTION OF MOTORS FOR ELECTRIC VEHICLE PROPULSION

NZQA registered unit standard version 3 Page 1 of 5. Demonstrate and apply knowledge of electrical machines

ELECTRIC MACHINES EUROLAB 0.3 kw

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

Transcription:

100 CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR 6.1 INTRODUCTION Conventional energy resources are not sufficient to meet the increasing electrical power demand. The usages of non conventional energy become necessary to bridge power crisis. Wind energy provides opportunity to share the power demand. Induction generators are dominating as major power supplying units. Non-conventional resources becoming conventional resources without which the increasing electrical power demand cannot be met with. Induction generators are often used in wind turbines due to their ability to produce real power at varying speeds. Induction generators are excited externally to produce a rotating magnetic field. While operating as an induction generator, the reactive power is supplied externally either from electrical grid or from externally connected capacitor bank. Induction generators are rugged in construction, requiring no brushes and commutators.

101 6.1.1 Need for Induction Generator In order to meet required power demand and to feed rural areas induction generators may be employed. Compared to conventional synchronous generators, induction generators have the following advantages: i) No sustained short circuit current problem ii) iii) iv) Elimination of synchronizing problem Elimination of hunting problem Extraction of more power from the machine compared to motor operation. 6.1.2 Advantages and Disadvantages of Induction Generator Induction generator can also be operated in parallel with synchronous generator to supplement the increased power demand. The importance of any generator depends on factors such as primary source, type of load, and speed of the turbine. In comparison with other generators, induction generators are simple in construction, capability to run independently, less expensive compared to conventional synchronous generators, stand-alone operation and no fixed frequency, less maintenance and only electro magnets are used. Though there are various advantages, still induction generators suffer from poor power factor, voltage and frequency regulation. Also, reactive energy is to be supplied from the grid or capacitor bank. 6.1.3 Classification of Induction Generators Induction generators can be classified based on rotor construction, excitation, and type of prime movers used. Based on rotor construction, induction generators are classified as squirrel cage induction generator in

102 which rotor core is filled with aluminum or copper bars in the rotor slots which are short circuited using end rings and wound rotor induction generator in which the rotor is wound for similar number of poles as in the stator. Based on excitation, induction generators are classified as Grid connected induction generator and Self-excited induction generator.when an induction motor is driven above the synchronous speed, it receives the reactive power from the grid and supplied real power to the load. The simple arrangement of grid connected induction generator is shown in Figure 6.1. The operation of grid connected system is comparatively simple as the voltage and frequency are controlled by the grid. Figure 6.1 Grid connected induction generator Figure 6.2 shows self-excited induction generator in which reactive power is supplied from a capacitor bank, connected across stator terminals.

103 Figure.6.2 Self-excited induction generator 6.2 DESIGN PROCEDURE 6.2.1 Objective of proposed model Elder et al (1984) presented the use of self-excited induction machines as low-cost stand-alone generators. They have dealt with problem faced in guaranteeing excitation and residual magnetism. Suitable VAR sources have been suggested to control the excitation in order to maintain better regulation. Murthy et al (1988) presented suitability of using a normal threephase induction motor as a capacitor self-excited induction generator. It was found that, for low power motors, the maximum power that can be extracted as generators is 148% to 160% of the motor rating for resistive loads and 118% to 128% of motor rating for 0.8 lagging power factor loads. Compared to other generators, induction generators are very simple in construction both in terms of mechanical and electrical. Bansal (2005) compared the process of self-excitation and voltage buildup, modeling, steady-state, and transient analysis, reactive power control methods and parallel operation of Self Excited Induction Generator (SEIG). Due to

104 simplicity, induction generators can be operated in stand alone mode to supply power to remote area so as to meet excessive load demand. The design requirement of the self-excited capacitor in a dual-stator winding induction generator (DSWIG) is different from that of the conventional induction generator. Wang et al (2008) considered efficiency optimization as design aim for a self-excited capacitor for dual stator winding induction generator. In Steinmetz scheme, the induction motor may be regarded as a direct evolution from the DC shunt motor. Implementation of balanced version of induction generator in Steinmetz scheme is aimed to prevent complete de-excitation in the core, improve load ability, better voltage stability with maintained core saturation, constant speed operation and improved power factor in grid connected operation. A conventional induction machine consists of a three phase winding that carries both excitation current and load current. Proposed scheme involves provision of an extra three-phase winding in the same stator. Provision of an extra winding offers the following features as i) The exciter and load winding are magnetically coupled, with transformation of almost unity. Under balanced condition, neglecting the effect of space and phase shift between the windings, the voltage that is induced across both the windings would be almost same. ii) When both the windings are excited magnetically, core saturation can be achieved effectively than in a single wound stator.

105 iii) Under the saturated conditions, the drop due to the synchronous reactance remains within a particular range iv) The capacitance requirement for the excitation in a doubly wound machine is comparatively less than that of the single wound machine v) Since the excitation is distributed across the windings, the regulation will be better even for reactive loads. 6.2.2 Scope of the suggested model By providing an additional three phase winding in the same stator, voltage stability of induction machine as a self excited generator is analyzed. Design considerations such as better cooling to improve machine rating, effect of phase and space shift between the two windings have been neglected. Since the research deals with modification of existing machine and not complete construction, the magnetizing characteristics and the dimension of the existing machine had to be complied with. The design of the induction generator involves the study of suitability of conventional induction motor. The principle limiting factor in such application is the thermal limit of stator windings. Therefore it is evident that the induction motors can be used in generation mode only for low power operations. In stand-alone system, excitation is supplied to stator of induction machine, therefore under heavy reactive load, machine gets de-excited. Due to small air-gap, machine offers high reactance, which leads to poor voltage regulation.

106 As a separately excited grid connected system, power factor does not depend on load but slip. For every load, there is unique power factor, which is out of control. Since excitation and working current, flow through the same winding the power factor is poor. 6.2.3 Design Specifications Capacity of the machine: 2.2 kw, 3-phase, 415 V, 4.5 A, 50 Hz, 4- pole squirrel cage induction motor. The main dimensions of the machine Diameter of the bore = 0.17m Length of the core = 0.10 m Turns per phase T s = 396 Number of stator slots = 36 Slot depth 17 mm and slot width 5mm Flux density in core B av = 1.0 Wb/m 2 Current density in the winding = 6.0 A/ mm 2 Flux in the air gap = 2 x Core depth x Length of core x B av = 2 x 1.7 x 10-2 x 10 x 10-2 x 1 = 34 x 10-4 Wb Design of exciter winding E s = 4.44 x f x x T s x k w 400 = 4.44 x50 x 34 x 10-4 x T s x 0.95

107 T s = 589 There are 12 coils Turns per coil = 49 The excitation winding is connected in delta with 22 SWG Current in the exciter winding = 6 x x (0.711) 2 / 4 = 2 A Design of load winding (400/ 3) = 4.44 x 50 x 34 x 10-4 x Ts x 0.95 Turns per phase T s = 340 The number of turn per coil = 28 (20 SWG) Current in the load winding = 6 x x (0.914) 2 / 4 = 4A These two windings are placed in the stator core as two double layered windings, with load winding at the bottom and the excitation winding occupying the top position. 6.2.4 Determination of Critical Capacitance A simple algorithm has been developed to predict the minimum value of capacitance necessary for self-excitation and to maintain the generator terminal voltage at a preset value under specific load and speed conditions (Harrington et.al 1998). In order to determine equivalent circuit parameters, no load and blocked rotor tests are carried out. Test results are shown in Table 6.1

108 Table 6.1 No load and blocked rotor test (IG) Test Voltage(V) Current(A) Power (W) No load 415 1.45 184 Blocked rotor 180 4.0 640 From no load X 0 = V ph / I ph = 159.27 From blocked rotor test Z ph = V ph / I ph = 25.98 R s +R r = w sc /3 I ph 2 = 13.33 X s +X r = ( Z 2 ph - R 2 ph ) X s =X r = 11.15 X M = X 0 -X s = 148.12 Power rating = 3 x 400 x 4 = 2771.2 VA Z b characteristics impedance = V 2 ph / VA = 57.73 Figure 6.3 shows equivalent circuit of induction machine considering load winding. Per unit values, considering power rating are as follows: R s R r X M X s =X r = 0.084 p.u = 0.147 p.u = 2.56 p.u = 0.193p.u

109 From the equivalent circuit, the minimum value of exciting capacitor can be determined. C min = 1/ (2 fz b X c ) = 23.12µF A capacitor bank has been designed with different tapings based on this value of capacitance. X c is capacitive reactance Figure 6.3 Equivalent circuit of Load winding (IG) 6.3 TESTING In order to determine the performance of double winding induction generator, series of testing have been carried out. Considering each winding individually, magnetization characteristics were obtained. Table 6.2 shows the change of output voltage with exciting current, corresponding magnetization characteristic is shown in Figure 6.4.

110 Table 6.2 Magnetization characteristics of excitation winding Exciting current (A) Voltage (V) 0.52 120 0.84 200 0.94 240 1.48 360 1.65 400 1.84 440 1.95 460 Figure 6.4 Magnetization characteristics of load winding (IG)

111 Table 6.3 Single winding induction generator with resistive load Speed (rpm) Voltage (V) Load Current (A) Capacitance (µf) Exciting current(a) 1407 415 0 24 0.62 1384 415 0.6 26 0.63 1320 415 1.0 30 0.64 1275 415 1.6 36 0.64 1225 415 2.0 42 0.64 1200 415 2.5 50 0.68 Figure 6.5 Capacitance characteristics (SWIG)

112 Table 6.4 Double Winding Induction Generator with resistive load Speed (rpm) Voltage (V) Load Current (A) Capacitance (µf) Exciting current(a) Power factor 1360 415 1.1 10 0.58 0.91 1370 415 1.7 16 0.54 0.97 1378 415 2.2 16 0.52 0.98 1370 415 2.7 22 0.52 0.98 Figure 6.6 Capacitance characteristics (DWIG)

113 6.3.1 Performance comparison and inferences Major observations based on the test results Load ability: Considering single winding induction generator, with reference to Table 6.2 for a load current of 2A, Voltage per phase = 230 V Exciting capacitance = 42µF Capacitive reactance =0.013 Exciting current = 3.0A Load current Total load current = 2A =3.61A Considering double winding induction generator, with reference to Table 6.3 for a load current of 2.2A, Voltage per phase = 230 V Exciting capacitance = 16µF Capacitive reactance =0.005024 Exciting current = 1.16A Load current = 2.2A Total load current =2.48A

114 For a given load, the total current in the double winding induction generator is comparatively less than the single winding induction generator. Therefore rating versus volume of material is reduced in double winding induction generator. Value of exciting capacitor for single winding induction generator is 42µF, where as for double winding induction generator it is 16µF. Major objectives are verified practically. Controllability of voltage is much smoother in a double winding induction generator than the conventional induction generator. Constant frequency and voltage operation is possible by reducing the capacitance so that the machine operates at a lesser slip. Since the excitation component is supplied in the separate set of winding, there is improvement in the power factor. 6.4 SUMMARY The provision of an additional winding in the stator has improved the load ability of the induction machine as a generator. The experimental results also illustrate the capability of this machine to operate as constant frequency, constant voltage source. Though this property depends on characteristics of the prime mover. The separation of excitation in the grid connected operation yields a marginally better power factor.the controllability of power factor can be obtained using power electronic converters. By proving an extra winding, excitation component is isolated from the grid which overcomes the problem of drawing reactive power from the grid. The voltage stability is achieved without compromising the power quality and without subjecting any complications on the existing system.