Easy-On II Terminations

Similar documents
PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

High Voltage Copper, Smooth Aluminum Shield/Sheath

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

High Voltage Joints and Terminations up to 72,5 kv 145 kv

INSTALLATION PRODUCTION TESTS

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

High Voltage Aluminum, Smooth Aluminum Shield/Sheath

Medium Voltage Power Cables

Loadbreak Apparatus Connectors

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

PRODUCT SHEET. Elastimold advanced connection system (shear bolt)

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

PRODUCT BROCHURE. Elastimold advanced connection system (shear bolt)

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

Branch Splice QS-2001B

15 kv and 25 kv Thru-Bushings

600 A 15 kv class T-OP II deadbreak connector

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 35 kv class BT-TAP deadbreak connector

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

Jumpers & Load Pickup Tools

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY

600 A 35 kv class separable splices

MEDIUM VOLTAGE TERMINATIONS

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

600 A 25 kv class BT-TAP deadbreak connector

Solid Dielectric, Three Phase Reclosers CATALOG VS11

25 kv Apparatus Bushings

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

TYPE BLT DISCONNECT SWITCHES

SUBMERSIBLE SECONDARY CONNECTORS SSBC350-4LI. Cond. Range H W L

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

D-73P disconnect and bypass switches

LCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

Installation Instructions

3M Cold Shrink Splice Kits, QS T Series

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

JUMPERS & SWITCHING TOOLS

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

LCT Shielded Primary UD TRXLP LCT Shielded Primary UD TRXLP Cable

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

UNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG

UNDERGROUND TRANSMISSION SOLUTIONS

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

Number Tube I.P.S. Rod Size or O.D. Range Cable H J W

Solid Dielectric, Single Phase Reclosers

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

T YPE MZ DISTRIBUTION S TANDARD CUTOUT

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Jumpering and grounding equipment and assemblies

Our overhead products go above and beyond all others. QUICK REFERENCE. Overhead Connectors. & Covers. Overview

Disconnect & ByPass Switches

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

AMENDMENT ELECTRIC SERVICE MANUAL 2014

Medium Voltage Cable. marmonutility.com

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

4 AWG to 2000 kcmil at 15 kv, 2 AWG to 1750 kcmil at 25 kv and 1 AWG to 1500 kcmil at 34.5 kv. Stress Control

NEC 2014 Code Changes

Figure 1. HX cutout fuseholders. Positive Interruption

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Item Code Description Unit Qty Total

Wire Mesh Grip Families

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015

Medium Voltage Cables for PermaLife Nuclear Utility Applications

Kuhlman Electric Corporation Volt Instrument Transformers

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Product Number

34-SDMS-01 SPECIFICATIONS FOR

Kuhlman Electric Corporation Volt Instrument Transformers

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Transcription:

Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional kits or tapes. The termination ground (or neutral) connection has the same ampacity as the cable shield (neutral system). Sizes are available for all shielded cables in voltage classes from 15kV through 35kV. Conductor sizes through 1000 kcmil aluminum and copper cables. Porcelain insulator provides maximum resistance to moisture, industrial pollution and seacoast pollution. Porcelain is the most reliable insulator for use where insulator dryband arcing may occur. The G&W spring loaded elastomer stress control system is the most reliable method to provide continuous mechanical force to the elastomer, thereby compensating for elastomer permanent set. The resulting dielectric interfaces have high dielectric strength, prevent ingress of moisture and accommodate the thermal expansion and contraction of the cable. The electric stress control cone is a factory made soft elastomer which seals the cable shield against environmental moisture. All of the termination interior elastomer dielectric parts are factory assembled within the porcelain termination housing. Termination field assembly is as easy as pulling the two pins releasing the elastomer compression spring. No tapes, tubes, nuts or bolts. No pushing or pulling or shrinking to fit. The Easy-On II terminations E5200, E5202 and E5203 are light enough to hang from a fuse cutout. Options for external connection to the overhead system include: pin type, 6 inch copper wire lead, eyebolt, in-line sleeve, aerial, flat bus, and spade. Galvanized steel mounting brackets are available. Page 1

Physical Data Catalog No. Voltage (kv) BIL (kv) Conductor Range Insulator Range Dry Arc Dist. (In.) Wet Leak Dist. (In.) Max. Height (In.) Dia. (In.) Weight (Lbs.) E5200 15 110 6-300.41-1.16 6.5 16.0 13.2 4.13 4.5 E5260 15 110 4/0-1000.86-1.82 7.5 18.0 19.3 5.88 12.0 E5202 25 150 6-250.41-1.16 11.5 27.5 17.4 4.13 7.5 E5265 25 150 4/0-1000.86-1.82 7.5 18.0 19.3 5.88 12.0 E5203 34.5 200 6-2/0.41-1.16 11.5 27.5 16.8 4.13 7.5 E5263 34.5 200 4/0-1000.86-1.82 11.0 27.0 22.3 5.88 16.0 Notes: All dimensions are in inches. Conductor sizes are AWG and kcmil. Field Assembly Each G&W termination is complete with field assembly instructions. Only normal hand tools are required. The following is a summary of the field assembly. Page 2

s All Easy-On II terminations require a connector. They not only make the connection to the shielded underground cable, but they also are a part of the sealing system. Aluminum connectors are not recommended in corrosive environments or when a copper aerial drop wire is used. All compression connectors along with the applicable aerial connections (parallel groove, eyebolt, aerial and flat pad) meet all industry standards such as EEI TD-160 and ANSI/NEMA CC3-1973. All the aluminum connectors are tin plated. The aerial connections are either tin plated aluminum or copper alloy. The following are the connectors used on the Easy-On II termination. Easy-On II Terminations s for E5200, E5202, E5203 Pin Type - with or without parallel groove connector Conductor Range Materials Parallel Groove Materials Code 6 Str. through 300 compact Tin-Plated Aluminum Tin-Plated Aluminum Without Parallel Groove Tin-Plated Aluminum TG-1 NO-1 TG-C 3 Str. through 3/0 compact Copper Bi-Metallic Aluminum Barrel w/ Copper Pin Bronze Without Parallel Groove Bronze Without Parallel Groove PG-C NO-C PG-3 NO-3 Eyebolt Conductor Range Materials Code 2 Str. through 3/0 C.R. Tin-Plated Aluminum and Tin- Plated Bronze Eyebolt Copper Top Pin and Tin-Plated Bronze Eyebolt ES-1 ES-3 Wire Lead Conductor Range Materials Code 4 Str. through 2/0 Sol. Tin-Plated Barrel and Tin- Plated Copper Stem WL-1 Sleeve Conductor Range Materials Code 4 Str. through 2/0 Sol. Tin-Plated Aluminum CS-1 Page 3

s All Easy-On II terminations require a connector. They not only make the connection to the shielded underground cable, but they also are a part of the sealing system. Aluminum connectors are not recommended in corrosive environments or when a copper aerial drop wire is used. All compression connectors along with the applicable aerial connections (parallel groove, eyebolt, aerial and flat pad) meet all industry standards such as EEI TD-160 and ANSI/NEMA CC3-1973. All the aluminum connectors are tin plated. The aerial connections are either tin plated aluminum or copper alloy. The following are the connectors used on the Easy-On II termination. Easy-On II Terminations s for E5260,E5265,E5263 Spade Conductor Size Materials Number of Holes Code 4/0, 350, 500,750 kcmil Tin-Plated Aluminum 2 SCC Threaded Stud Only Conductor Size Materials Threads Code 4/0 to 500 kcmil 550 to 1000 kcmil Tin-Plated Aluminum 3/4-16 OLO-1 Copper 3/4-16 OLO-C Tin-Plated Aluminum 1-14 OLO-1 Copper 1-14 OLO-C Threaded Stud and Aerial Combination Conductor Size Aerial Materials Aerial Code Bronze BWB 4/0 to 1000 kcmil Tin-Plated Bronze BTB Tin-Plated Aluminum BTA Threaded Stud and Flat Pad Bus Combination Conductor Size Bus Materials Number of Holes Aerial Size 4/0 to 500 kcmil 550 to 1000 kcmil Bronze 2 FBB Tin-Plated Aluminum 2 FT2 Tin-Plated Bronze 2 FTB Bronze 4 FBB Tin-Plated Aluminum 2 FT2 Tin-Plated Aluminum 4 FT4 Tin-Plated Bronze 4 FTB Page 4

Ordering Information The Easy-On termination is available in two size series for each voltage class, 15 through 34.5kV. The first is the E5200 series which uses small diameter porcelains for conductor sizes through 250 kcmil. The second is the E5260 series which uses large diameter porcelains for conductor sizes through 1000 kcmil. Fill the blanks in the catalog number with the proper codes for voltage, conductor, connector and mounting or grounding option. Page 5

Ordering Information The Easy-On termination is available in two size series for each voltage class, 15 through 34.5kV. The first is the E5200 series which uses small diameter porcelains for conductor sizes through 250 kcmil. The second is the E5260 series which uses large diameter porcelains for conductor sizes through 1000 kcmil. Fill the blanks in the catalog number with the proper codes for voltage, conductor, connector and mounting or grounding option. Page 6

Ordering Informaton- Brackets Brackets are galvanized steel. Easy-On II provides two bracket options. G&W Electric Company 3500 W. 127th St. Blue Island, IL 60406 USA 708.388.5010 Fax 708.388.0755 www.gwelec.com Catalog LVT EO11 October, 2011 Page 7