Section Fume Hoods Specifications 6/1/14 LABORATORY FUME HOODS

Similar documents
F. VAV hoods shall have a restricted bypass plate.

LABORATORY FUME HOODS OF 5

General Purpose Walk-In Fume Hood

General Purpose Walk-In Fume Hood

TEST REPORT: CHM12-01-LSM

SECTION ISOLATOR SERIES LABORATORY FUME HOODS

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE

SECTION LABORATORY FUME HOODS

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section )

FUME HOOD SELECTION GUIDE

Supreme AirLV- FUME HOODS. KEWAUNEE encouraging new discovery LOW CONSTANT VOLUME

Bedcolab Vanguard Laboratory Fume Hoods

new fume hoods providing performance and protection

SECTION LABORATORY FUME HOODS UNIFLOW LE SERIES

Supreme Air. Fume Hoods KEWAUNEE LABORATORY. encouraging new discovery

Laboratory Demonstration Space Located at Price Research Center North Winnipeg. Fume Hoods. ehpricesales.com

Fume Hoods Overview OVERVIEW

RDM. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features

LABORATORY FUME HOODS

BMC. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION M E M B E R

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features

SECTION LABORATORY FUME HOODS

CORPORATION DURALAB CORPORA

Ducting & Ventilation Components

Requires Ductwork and Blower

Protector XStream Laboratory Hood is shown with SpillStopper Work Surface , Protector Acid Storage Cabinet and Protector

Protector Special Application Hoods Laboratory Hoods for Radioisotope, Perchloric Acid and Acid Digestion Use Fiberglass 28, Demonstration and Canopy

PERCHLORIC ACID FUME HOOD H25. Fume Hoods. 48"- 60"- 72"- 96" long

Selection of DODGE E-Z KLEEN Polymer and Stainless Steel Housed Ball Bearings. P = (X x F R ) + (Y x F A ) F A C o

VentureClad Insulation Jacketing Tapes 1577 Series

LABORATORY FUME HOODS

Model ND-2 Specification

Polycarbonate & Laminate Half Trays

SECTION DUCTWORK ACCESSORIES

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter

How to Use the Chemical Compatibility Chart. Vials and Closures >> Chemical Compatibility Chart

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT

Protector Demonstration Hoods

P17 Tempra Pro plugs, mobile sockets, fixed sockets, surface mounting sockets and appliance inlets - IP 66/67-63 A A

Small on price, big on boot

Supreme Air Fume Hood Option Availability

MM PISTON PUMP

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

Ventilated Balance Enclosures

th Avenue Spring Lake, MI Ph:

Fume Hood Operation & Maintenance Manual

MM PISTON PUMP

SECTION WELDING FUME EXHAUST SYSTEM

NuAire, Inc Fernbrook Lane Plymouth, MN U.S.A

LABORATORY CABINETRY AND SPECIALTIES: FUME HOODS

Protector XL Floor-Mounted Laboratory Hoods Features & Benefits

Protector XStream Laboratory Hoods

Physical properties of PET resins. 1. Intrinsic Viscosity (IV)

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

User s Manual. LabShield. Laboratory Fume Hoods. Air Foil By-Pass Models: 6714, 6716, ADA Models: 8796, 8798, Demonstration Hood 6725G

The Industrial Choice. Model TFBD. Model FBD FIBERGLASS AXIAL FLOW FANS. Model FDP / FRV / FBD / TFBD / VTFBD

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

General applications Chemical plant, oil refinery, power plant, steam, Dowtherm, fused alkali, fuel oil and gas

SECTION AXIAL HVAC FANS

3.5 Exposure Control Measures

A. Each cabinet must be constructed and installed in accordance with EN12469:2000.

Accessories Standard Service Fixture Kits

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

How to Use a Chemical Fume Hood Safely

Design Standard - Fume Hoods & Fume Hood Exhausts

FR PVC COATED RAINWEAR

SECTION HVAC POWER VENTILATORS

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

AUDIO-VISUAL EQUIPMENT

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD

Laboratory Design Standards

Section 3 - Chemical/Environmental Resistance Part 1 - XR-5 Fluid Resistance Guidelines

Laboratory Fume Hoods & Enclosures

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD

Replacement Tubes for Gillian Gas Detection Pumps

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

Swivel Joints Flexmaster Joints Part Number NH NH NH NH NH NK NK

Ductless Nanoparticle Containment Enclosures

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD

DetectAir KEWAUNEE FILTERED FUME HOODS. encouraging new discovery

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

HYPRA Prisinter 16/32/63 A

Strength, resilience, rigidity - these are all attributes needed to combat arduous and aggressive conditions. Tufflite has them all.

Catalog June Mounted Bearings

Thermo Scientific Hamilton Air Flow Products. Table of Contents

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter

Dynaform Fiberglass Structural Shapes. Design Guide. High Performance Composite Solutions. Corrosion Resistant. Fire Retardant.

P17 plugs, mobile sockets and surface-mounting sockets «New range 16 and 32 A»

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

Completing Your Fume Removal System

Transcription:

1.01 SUMMARY A. Section Includes: Fume hoods LABORATORY FUME HOODS B. Related Sections 1. Division 12 Section - 12345 - Steel Laboratory Casework 2. Division 12 Section - 12346 - Agility Adaptable Furniture Systems. 3. Division 15 - Plumbing utilities final connections to casework and fume hoods. 4. Division 15 - Mechanical, HVAC ductwork, equipment, final connections to fume hoods. 5. Division 16 - Electrical utilities and final connections to casework and fume hoods. 1.02 FUME HOODS A. Fume hood superstructures shall be of double wall construction, with the exterior shell fabricated of 18 gauge, high quality, mild cold rolled steel and the inner wall liner fabricated of 1/4 thick non asbestos corrosion resistant Glastic Liner Board. Interior to be metal free with bright white interior liners. Liner to provide superior resistance to chemicals and high temperatures. Other Fume Hood Liners are available when specified. B. The exterior shell with its attached liner shall be rigid and self-supporting without reliance on the outer wall for support and stability. Access to fixture valves contained between the exterior and interior walls shall be through removable panels on the interior liner wall. Exterior access panels on both sides should provide easy access for maintenance and for adding additional service fixtures in the future. Interior access panels to have PVC soft gaskets on both sides to eliminate seepage into sidewalls. Interior and exterior panels are attached to a full perimeter epoxy coated steel frame for strength and durability. C. Screws and other fastening devices shall not be visible nor exposed, with the superstructure flush and smooth. The exterior shell finished with baked-on, chemically resistant finish to match the other metal furniture in the laboratory. D. The Fume Hood shall be provided with vertically operated counter-balanced sash, with the sash fabricated from ¼ ANSI II automotive safety glass, laminated safety glass, 1 2014 Hanson Lab Furniture, Inc. All rights reserved.

36 high safety glass, shall provide an optimal unobstructed sight line into the fume hood. 30 full vertical sash opening for easier set up of lab processes and apparatus. The counter-balance shall hold the sash at any position in its travel, without creep. The sash shall move forward without binding, and shall be easily operable at any point along its full width. Horizontal, Combination, Double Sided, and Split sash designs are available when specified. E. Bottom air foil to be stainless steel. A stainless steel vented finger pull attached to the bottom sash allowing smooth air passing through the work surface. Air Foil to be flush sill design with smooth air passing along work surface. F. Light fixtures shall be mounted on the exterior roof of the Fume Hood. Light fixtures shall be 2 bulb T8 electronic ballast vapor proof fluorescent light fixtures. Fluorescent lighting is located away from fumes and gives for superior interior illumination. Provided two fixtures on 8-0 Fume Hoods or longer. Explosion proof and incandescent fixtures available when specified. G. Interior baffles shall be fabricated from the same material as the interior liner. Provide single point fixed baffle for optimum air flow. Fixed baffles available when specified. H. Fume Hood shall be provided with 4 x 24 rectangular exhaust duct collar(s), fabricated from type 304 stainless steel for superior corrosion resistance. Provide a 4 x 36 exhaust collar on 94 fume hoods. Provide two (2) 4 x 24 exhaust collars on 120 fume hoods. I. The Fume Hoods shall be equipped with automatic air by-pass which is not dependent upon mechanical or electrical linkage, and which allows a relatively constant velocity of air passing through the face with the sash at any position. J. The Fume Hoods shall be provided with a low flow alarm (optional) which provides audible and visual indications when the face velocity has dropped below a predetermined setting, when specified. K. Service fixtures mounted inside of the Fume Hoods shall consist of valves controlled from the exterior of the Fume Hood. Fixture components exposed on the interior of the Fume Hood shall be Water Saver Brand Color Tech epoxy coated and color coded to the type of service provided. Service fixture holes shall be provided with caps for adding service fixtures in the future. 2 2014 Hanson Lab Furniture, Inc. All rights reserved.

L. Electrical components provided shall be UL approved and labeled. Provided as standard, two (2) electrical 120V, duplex receptacles, one (1) light switch, each mounted to the outside of the fume hood front posts and florescent light. Electrical plates shall be stainless steel. Electrical fixtures shall be field wired by others. Pre-wiring (optional) of Fume Hoods: Electrical fixtures and lights to be internally wired at the factory to a junction box at the top of the hood. Hood shall have 2 junction boxes, one located at the far left and far right sides of the hood. Electrical connections from either junction box shall provide power to all devices on hood. Hood shall be pre-wired to easily convert to 2 circuit electrical system if desired. One junction box to include a 120V duplex receptacle. M. Fume hoods to be provided with concealed wire management chase systems. The wire management system to be built into the hoods at the left and right side locations to run cords or tubing onto the hoods. Systems utilizing cords or tubing running under the sash are unacceptable. Chase to be constructed of leak-proof, flexible tubing providing electrical wire protection during routing applications. 1.03 FUME HOOD TYPES 1. Conventional By-Pass Fume Hoods provides a relatively constant volume of air to move through the Fume Hood, to ensure operator safety, regardless of the position of the sash. This is achieved through the combination of the by-pass grill, located in the Fume Hood face panel, openings at the top of the Fume hoods and under the counter airfoil and the sash opening itself. The air being exhausted through the Fume Hood comes from within the room. The room should be balanced to compensate for the volume of air exhausted. 2. Restricted By-Pass Fume Hoods shall be sufficient in size to allow 25% flow with sash closed. By-pass must be achieved through grill or louvers on face lintel panel. 3. Hanson Lab Furniture 5SA Series Bench Top Fume Hoods include: General Purpose, Hi-Line, ADA models. Conventional By-Pass or Restricted By-Pass. Widths: [47 ] [58 ] [70 ] [94 ] [120 ] [144 ] 3 2014 Hanson Lab Furniture, Inc. All rights reserved.

Depths: A depth - 31-3/8, B depth - 37-3/8, C depth - 41-3/8. 4. Hanson Lab Furniture 4SA Series Walk-In Style Fume Hoods include: Conventional By-Pass or Restricted By-Pass Widths: [47 ] [58 ] [70 ] [94 ] [120 ] [144 ] Depths: A depth - 36, B depth - 47-3/8 1.04 QUALITY ASSURANCE A. Single source responsibility: Fume hoods, casework, work surfaces, and other equipment and accessories shall be manufactured or furnished by a single furniture company. B. Manufacturer s qualifications: Modern plant with proper tools, dies, fixtures and skilled employees to produce high quality casework and equipment, and shall meet the following minimum requirements. 1. Five years or more experience in manufacture of casework and equipment of type specified. 2. Ten installations of equal or larger size and requirements conforming to ASTM Specifications No. A36672. C. Stainless steel: Type 304 or 316 gauges; conforming to ASTM Specification No. A240 D. Safety Glass: ¼ thick laminated type ANSI II rated automotive safety glass. E. Lining: 3/16 thick bright white Glastic liner board 1/4 thick with smooth surface for easy cleaning and superior resistance to chemicals and high temperatures. F. Sash Cables: Aircraft type, stainless steel. Sash cable pulleys shall be 2.5 diameter roller bearing type for ease of sash travel with cable retainer to secure cables on pulley system. G. Sash Guides: Ultra high molecular polyethylene strips mounted on sash frame, stainless steel channel mounted on Fume hood body. 4 2014 Hanson Lab Furniture, Inc. All rights reserved.

H. Sash Pulley: Nylon tired ball bearing sheaves 2.5 diameter. I. Sash pull: Corrosion resistant stainless steel. J. By-Pass Grill: Punched louvered powder coated. K. Light Fixture: UL approved vapor proof florescent. PART 2 PRODUCTS 2.01 MANUFACTURER Laboratory furniture and fume hood manufacturer: Hanson Lab Furniture, Inc. 814 Mitchell Road Newbury Park, CA 91320 805-498-3121 2.02 FUME HOOD MATERIALS A. Steel: High quality, cold rolled mild steel, free of scales, buckles or other defects, conforming to ASTM Specifications No. A36672. 2.03 FUME HOOD FINISH 1. Pretreatment: Thoroughly clean surface of grease, dirt and oil in an alkaline solution, rinse, then immersed in a phosphatizing solution. Bake entire unit with metallic phosphate coating to provide excellent bond for subsequent finish and aid in prevention of corrosion. 2. Finish Coat: Apply one coat of environmentally non-hazardous thermosetting Epoxy Powder Coated finish. This material shall meet the most stringent air quality standards. The final finish shall meet the following test data with no more than slight discoloration but no change of gloss and no loss of adhesion with exposure to the following chemicals: Acetate, Amyl Acetate, Ethyl Acetic Acid 98% Acetone Acid Dichromate 5% 5 2014 Hanson Lab Furniture, Inc. All rights reserved.

Alcohol, Butyl Alcohol, Ethyl Alcohol, Methyl Ammonium Hydroxide 28% Benzene Carbon Tetrachloride Chloroform Chromic Acid 60% Cresol Dichloroacetic Acid Dimethylformamide Dioxane Ethyl Ether Formaldehyde 37% Formic Acid 90% Furfural Gasoline Hydrofluroic Acid 37% Hydrofluoric Acid 48% Hydrogen Peroxide 30% Iodine, Tincture of Methyl Ethyl Ketone Methylene Chloride Monochlorobenzene Napthalene Nitric Acid 20% Nitric Acid 30% Nitric Acid 70% Phenol 90% Phosphoric Acid 85% Silver Nitrate, Saturated Sodium Hydroxide 10% Sodium Hydroxide 20% Sodium Hydroxide 40% Sodium Hydroxide, Flake Sodium Sulfide, Saturated Sulfuric Acid 33% Sulfuric Acid 77% Surfuric Acid 96% Surfuric Acid 77%, and Nitric Acid 70%, equal parts Toluene Trichloroethylene Xylene1 Zinc Chloride, Saturated 3. Adhesion and flexibility: No peeling, cracking or exposure of metal when painted surface is bent 180 degrees over ¼ diameter mandrel. 2.04 PERFORMANCE REQUIREMENTS 1. The Fume Hoods, when properly installed in a laboratory and connected to an exhaust fan of the proper capacity, shall contain and remove fumes generated within the Fume Hood. The average face velocity range should be between 100 and 125 FPM. (Averages higher or lower are acceptable in some instances depending upon the materials being used). 6 2014 Hanson Lab Furniture, Inc. All rights reserved.

2. The Fume Hood shall operate at any setting within these ranges. The Fume Hood design shall be such that it will exhaust light or heavy gases efficiently, when the Fume Hood is used for ordinary laboratory work in a room free from cross drafts, and without high thermal loads of other special conditions. No reverse flows of air will be allowed along the sides, bottom or front of the Fume Hood. 3. Fume Hoods to be been tested within their test facility to conform to American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE) Standard 110-1995 and is UL 1805 Classified. Bench top fume hoods shall meet (ASHRAE) Standard 110-1995 specification for 60 LFM at 18 sash opening for low airflow design. Performance test results for measurement of face velocities are available upon request. In addition, Hanson Lab Furniture, Inc. Fume Hoods have been tested and approved by the City of Los Angeles. PART 3 EXECUTION 3.01 INSTALLATION A. Installation: 1. Install fume hoods and equipment in accordance with manufacturer's instructions. 2. Install equipment plumb, square, and straight with no distortion and securely anchored as required. 3. Secure work surfaces to casework and equipment components with material and procedures recommended by the manufacturer. B. Accessory installation: Install accessories and fittings in accordance with manufacturer's recommendations. 3.02 ADJUSTING A. Repair or replace defective work, as directed by Architect or Owner upon completion of installation. 7 2014 Hanson Lab Furniture, Inc. All rights reserved.

B. Adjust sash, fixtures, accessories and other moving or operating parts to function smoothly. 3.03 CLEANING Clean equipment, touch up as required. 3.04 PROTECTION OF FINISHED WORK A. Provide all necessary protective measures to prevent exposure of equipment to other construction activity. B. To prevent hoods from damage by work of other trades, advise contractor of necessary precautions. END OF SECTION 8 2014 Hanson Lab Furniture, Inc. All rights reserved.